ML24310A121
| ML24310A121 | |
| Person / Time | |
|---|---|
| Site: | Diablo Canyon (SNM-2511) |
| Issue date: | 06/20/2025 |
| From: | Storage and Transportation Licensing Branch |
| To: | |
| Shared Package | |
| ML24310A117 | List: |
| References | |
| EPID L-2022-RNW-0007, CAC 001028 | |
| Download: ML24310A121 (1) | |
Text
APPENDIX TECHNICAL SPECIFICATIONS FOR THE DIABLO CANYON INDEPENDENT SPENT FUEL STORAGE INSTALLATION Docket No. 72-26 Materials License No. SNM-2511 Renewed License l
DIABLO CANYON ISFSI TABLE OF CONTENTS 1.0 USE AND APPLICATION........................................................................................... 1.1-1 1.1 Definitions.......................................................................................................... 1.1-1 1.2 Logical Connectors............................................................................................. 1.2-1 1.3 Completion Times.............................................................................................. 1.3-1 1.4 Frequency.......................................................................................................... 1.4-1 2.0 APPROVED CONTENTS........................................................................................... 2.0-1 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY........................... 3.0-1 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY.......................................... 3.0-2 3.1 Spent Fuel Storage Cask (SFSC) Integrity........................................................ 3.1-1 3.1.1 Multi-Purpose Canister (MPC).......................................................................... 3.1-1 3.1.2 Spent Fuel Storage Cask (SFSC) Heat Removal System................................. 3.1-3 3.1.3 Fuel Cool-Down.................................................................................................. 3.1-4 3.1.4 Supplemental Cooling System........................................................................... 3.1-5 3.2 Cask Criticality Control Program........................................................................ 3.2-1 3.2.1 Dissolved Boron Concentration.......................................................................... 3.2-1 4.0 DESIGN FEATURES.................................................................................................. 4.0-1 4.1 Design Features Significant to Safety................................................................ 4.0-1 4.1.1 Criticality Control............................................................................................... 4.0-1 4.1.2 Design Features Important to Criticality Control................................................. 4.0-1 4.1.3 Design Features Important to Thermal Analysis................................................ 4.0-2 4.2 Codes and Standards........................................................................................ 4.0-2 4.2.1 Alternatives to Design Codes, Standards, and Criteria...................................... 4.0-2 4.3 Cask Handling/Cask Transfer Facility................................................................ 4.0-3 4.3.1 Cask Transporter................................................................................................ 4.0-3 4.3.2 Storage Capacity................................................................................................ 4.0-3 4.3.3 SFSC Load Handling Equipment....................................................................... 4.0-3 4.3.4 CTF Structure Requirements............................................................................. 4.0-3 5.0 ADMINISTRATIVE CONTROLS................................................................................. 5.0-1 5.1 Administrative Programs.................................................................................... 5.0-1 5.1.1 Technical Specifications (TS) Bases Control Program...................................... 5.0-1 5.1.2 Radioactive Effluent Control Program................................................................ 5.0-1 5.1.3 MPC and SFSC Loading, Unloading, and Preparation Program....................... 5.0-2 5.1.4 ISFSI Operations Program................................................................................. 5.0-3 5.1.5 Cask Transportation Evaluation Program.......................................................... 5.0-3 Renewed License l
Definitions 1.1 DIABLO CANYON ISFSI 1.0 USE AND APPLICATION 1.1 Definitions
NOTE-------------------------------------------------------------
The defined terms of this section appear in capitalized type and are applicable throughout these Technical Specifications and Bases.
Term Definition ACTIONS ACTIONS shall be that part of a Specification that prescribes Required Actions to be taken under designated Conditions within specified Completion Times.
CASK TRANSFER FACILITY (CTF)
The CASK TRANSFER FACILITY includes the following components and equipment: (1) a structure used to stabilize the OVERPACK during lifts involving spent fuel not bounded by 10 CFR 50, and (2) either a stationary lifting device or mobile lifting device used to lift the OVERPACK, TRANSFER CASK, and MPC.
DAMAGED FUEL ASSEMBLY DAMAGED FUEL ASSEMBLIES are fuel assemblies with known or suspected cladding defects, as determined by a review of records, greater than pinhole leaks or hairline cracks, empty fuel rod locations that are not filled with solid Zircaloy or stainless steel rods, or those that cannot be handled by normal means. DAMAGED FUEL ASSEMBLIES if stored in an MPC, must be stored in a DAMAGED FUEL CONTAINER.
DAMAGED FUEL CONTAINER (DFC)
DFCs are specially designed enclosures for DAMAGED FUEL ASSEMBLIES or FUEL DEBRIS that permit gaseous and liquid media to escape to the atmosphere in the MPC, while minimizing dispersal of gross particulates within the MPC. A DFC can hold one DAMAGED FUEL ASSEMBLY or an amount of FUEL DEBRIS equivalent to that of an INTACT FUEL ASSEMBLY.
FUEL DEBRIS FUEL DEBRIS is ruptured fuel rods, severed rods, loose fuel pellets or fuel assemblies with known or suspected defects, which cannot be handled by normal means due to fuel cladding damage.
(continued) 1.1-1 Renewed License l
Definitions 1.1 DIABLO CANYON ISFSI 1.1 Definitions (continued)
INTACT FUEL ASSEMBLY INTACT FUEL ASSEMBLY is a fuel assembly without known or suspected cladding defects greater than pinhole leaks or hairline cracks and which can be handled by normal means. A fuel assembly shall not be classified as INTACT FUEL ASSEMBLY unless solid Zircaloy or stainless steel rods are used to replace missing fuel rods and which displace an amount of water equal to that displaced by the original fuel rod(s).
LOADING OPERATIONS LOADING OPERATIONS include all licensed activities on a TRANSFER CASK while its contained MPC is being loaded with its approved contents. LOADING OPERATIONS begin when the first fuel assembly is placed in the MPC and end when the TRANSFER CASK is suspended from or secured on the transporter. LOADING OPERATIONS does not include MPC transfer between the TRANSFER CASK and the OVERPACK.
MINIMUM ENRICHMENT MINIMUM ENRICHMENT is the minimum assembly average enrichment. Natural uranium blankets are not considered in determining minimum enrichment.
MULTI-PURPOSE CANISTER (MPC)
MPC is a sealed SPENT NUCLEAR FUEL container that consists of a honeycombed fuel basket contained in a cylindrical canister shell which is welded to a baseplate, lid with welded port cover plates, and closure ring. The MPC provides the confinement boundary for the contained radioactive materials.
NONFUEL HARDWARE NONFUEL HARDWARE is defined as burnable poison rod assemblies (BPRAs), thimble plug devices (TPDs), rod cluster control assemblies (RCCAs), wet annular burnable absorbers (WABAs), neutron source assemblies (NSAs),
instrument tube tie rods (ITTRs), and components of these devices such as individual rods.
OPERABLE/OPERABILITY A system, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instruments, controls, normal or emergency electrical power, and other auxiliary equipment that are required for the system, component, or device to perform its specific safety function(s) are also capable of performing their related support function(s).
(continued) 1.1-2 Renewed License l
Definitions 1.1 DIABLO CANYON ISFSI 1.1-3 1.1 Definitions (continued)
OVERPACK OVERPACK is a cask that receives and contains a sealed MPC for interim storage in the independent spent fuel storage installation (ISFSI). It provides gamma and neutron shielding, and provides for ventilated air flow to promote heat transfer from the MPC to the environs. The OVERPACK does not include the TRANSFER CASK.
SPENT FUEL STORAGE CASKS (SFSCs)
SFSCs are containers approved for the storage of spent fuel assemblies, FUEL DEBRIS, and associated NONFUEL HARDWARE at the ISFSI. The HI-STORM 100 SFSC System consists of the OVERPACK and its integral MPC loaded with any approved contents.
SPENT NUCLEAR FUEL SPENT NUCLEAR FUEL means fuel that has been withdrawn from a nuclear reactor following irradiation, has undergone at least one years decay since being used as a source of energy in a power reactor and has not been chemically separated into its constituent elements by reprocessing. SPENT NUCLEAR FUEL includes the special nuclear material, byproduct material, source material, and other radioactive materials associated with fuel assemblies.
STORAGE OPERATIONS STORAGE OPERATIONS include all licensed activities that are performed at the ISFSI while a SFSC containing approved contents is sitting on a storage pad within the ISFSI perimeter. STORAGE OPERATIONS does not include MPC transfer between the TRANSFER CASK and the OVERPACK.
TRANSFER CASK TRANSFER CASKs are containers designed to contain the MPC during and after loading of its approved contents and to transfer the loaded MPC to or from the OVERPACK.
TRANSPORT OPERATIONS TRANSPORT OPERATIONS include all licensed activities performed on an OVERPACK or TRANSFER CASK loaded with any approved contents when it is being moved to and from the ISFSI. TRANSPORT OPERATIONS begin when the OVERPACK or TRANSFER CASK is first suspended from or secured on the transporter and end when the OVERPACK or TRANSFER CASK is at its destination and no longer secured on or suspended from the transporter.
TRANSPORT OPERATIONS include transfer of the MPC between the OVERPACK and the TRANSFER CASK.
(continued)
Renewed License l
Definitions 1.1 DIABLO CANYON ISFSI 1.1 Definitions (continued)
UNLOADING OPERATIONS UNLOADING OPERATIONS include all licensed activities on a TRANSFER CASK while its contained MPC is being unloaded of its approved contents. UNLOADING OPERATIONS begin when the TRANSFER CASK is no longer suspended from or secured on the transporter and end when the last of its approved contents is removed from the MPC. UNLOADING OPERATIONS do not include MPC transfer between the TRANSFER CASK and the OVERPACK.
1.1-4 Renewed License l
Logical Connectors 1.2 DIABLO CANYON ISFSI 1.0 USE AND APPLICATION 1.2 Logical Connectors PURPOSE The purpose of this section is to explain the meaning of logical connectors.
Logical connectors are used in Technical Specifications (TS) to discriminate between, and yet connect, discrete Conditions, Required Actions, Completion Times, Surveillances, and Frequencies. The only logical connectors that appear in TS are AND and OR. The physical arrangement of these connectors constitutes logical conventions with specific meanings.
BACKGROUND Several levels of logic may be used to state Required Actions. These levels are identified by the placement (or nesting) of the logical connectors and by the number assigned to each Required Action. The first level of logic is identified by the first digit of the number assigned to a Required Action and the placement of the logical connector in the first level of nesting (i.e., left justified with the number of the Required Action). The successive levels of logic are identified by additional digits of the Required Action number and by successive indentions of the logical connectors.
When logical connectors are used to state a Condition, Completion Time, Surveillance, or Frequency, only the first level of logic is used, and the logical connector is left justified with the statement of the Condition, Completion Time, Surveillance, or Frequency.
EXAMPLES The following examples illustrate the use of logical connectors.
EXAMPLE 1.2-1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
LCO not met.
A.1 Verify......
AND A.2 Restore....
In this example, the logical connector AND is used to indicate that when in Condition A, both Required Actions A.1 and A.2 must be completed.
(continued) 1.2-1 Renewed License l
Logical Connectors 1.2 DIABLO CANYON ISFSI 1.2 Logical Connectors EXAMPLES (continued)
EXAMPLE 1.2-2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
LCO not met.
A.1 Stop.....
OR A.2.1 Verify....
AND A.2.2.1 Reduce....
OR A.2.2.2 Perform....
OR A.3 Remove....
This example represents a more complicated use of logical connectors.
Required Actions A.1, A.2, and A.3 are alternative choices, only one of which must be performed as indicated by the use of the logical connector OR and the left justified placement. Any one of these three ACTIONS may be chosen. If A.2 is chosen, then both A.2.1 and A.2.2 must be performed as indicated by the logical connector AND. Required Action A.2.2 is met by performing A.2.2.1 or A.2.2.2. The indented position of the logical connector OR indicates that A.2.2.1 and A.2.2.2 are alternative choices, only one of which must be performed.
1.2-2 Renewed License l
Completion Times 1.3 DIABLO CANYON ISFSI 1.0 USE AND APPLICATION 1.3 Completion Times PURPOSE The purpose of this section is to establish the Completion Time convention and to provide guidance for its use.
BACKGROUND Limiting Conditions for Operation (LCOs) specify the lowest functional capability or performance levels of equipment required for safe operation of the facility. The ACTIONS associated with an LCO state Conditions that typically describe the ways in which the requirements of the LCO can fail to be met. Specified with each stated Condition are Required Action(s) and Completion Time(s).
DESCRIPTION The Completion Time is the amount of time allowed for completing a Required Action. It is referenced to the time of discovery of a situation (e.g., equipment or variable not within limits) that requires entering an ACTIONS condition unless otherwise specified, providing the cask system is in a specified condition stated in the Applicability of the LCO.
Required Actions must be completed prior to the expiration of the specified Completion Time. An ACTIONS Condition remains in effect and the Required Actions apply until the condition no longer exists or the cask system is not within the LCO Applicability.
Once a Condition has been entered, subsequent subsystems, components, or variables expressed in the Condition, discovered to be not within limits, will not result in separate entry into the Condition unless specifically stated. The Required Actions of the Condition continue to apply to each additional failure, with Completion Times based on initial entry into the Condition.
(continued) 1.3-1 Renewed License l
Completion Times 1.3 DIABLO CANYON ISFSI 1.3 Completion Times (continued)
EXAMPLES The following examples illustrate the use of Completion Times with different types of Conditions and changing Conditions.
EXAMPLE 1.3-1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B.
Required Action and associated Completion Time not met.
B.1 Perform Action B.1 AND B.2 Perform Action B.2 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 36 hours Condition B has two Required Actions. Each Required Action has its own separate Completion Time. Each Completion Time is referenced to the time that Condition B is entered.
The Required Actions of Condition B are to complete action B.1 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND complete action B.2 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. A total of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> is allowed for completing action B.1 and a total of 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> (not 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />) is allowed for completing action B.2 from the time that Condition B was entered. If action B.1 is completed within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, the time allowed for completing action B.2 is the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> because the total time allowed for completing action B.2 is 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
(continued) 1.3-2 Renewed License l
Completion Times 1.3 DIABLO CANYON ISFSI 1.3 Completion Times EXAMPLES (continued)
EXAMPLE 1.3-2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
One system not within limit.
A.1 Restore system to within limit.
7 days B.
Required Action and associated Completion Time not met.
B.1 Complete action B.1.
AND B.2 Complete action B.2.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 36 hours When a system is determined not to meet the LCO, Condition A is entered. If the system is not restored within 7 days, Condition B is also entered and the Completion Time clocks for Required Actions B.1 and B.2 start. If the system is restored after Condition B is entered, Conditions A and B are exited, and therefore, the Required Actions of Condition B may be terminated.
(continued) 1.3-3 Renewed License l
Completion Times 1.3 DIABLO CANYON ISFSI 1.3 Completion Times EXAMPLES (continued)
EXAMPLE 1.3-3 ACTIONS
NOTE------------------------------------------
Separate Condition entry is allowed for each component.
CONDITION REQUIRED ACTION COMPLETION TIME A.
LCO not met.
A.1 Restore compliance with LCO.
4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> B.
Required Action and associated Completion Time not met.
B.1 Complete action B.1 AND B.2 Complete action B.2 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 12 hours The Note above the ACTIONS table is a method of modifying how the Completion Time is tracked. If this method of modifying how the Completion Time is tracked was applicable only to a specific Condition, the Note would appear in that Condition rather than at the top of the ACTIONS Table.
The Note allows Condition A to be entered separately for each component, and Completion Times tracked on a per component basis.
When a component is determined to not meet the LCO, Condition A is entered and its Completion Time starts. If subsequent components are determined to not meet the LCO, Condition A is entered for each component and separate Completion Times start and are tracked for each component.
IMMEDIATE COMPLETION TIME When "Immediately" is used as a Completion Time, the Required Action should be pursued without delay and in a controlled manner.
1.3-4 Renewed License l
Frequency 1.4 DIABLO CANYON ISFSI 1.0 USE AND APPLICATION 1.4 Frequency PURPOSE The purpose of this section is to define the proper use and application of Frequency requirements.
DESCRIPTION Each Surveillance Requirement (SR) has a specified Frequency in which the Surveillance must be met in order to meet the associated Limiting Condition for Operation (LCO). An understanding of the correct application of the specified Frequency is necessary for compliance with the SR.
The "specified Frequency" is referred to throughout this section and each of the Specifications of Section 3.0, Surveillance Requirement (SR) Applicability. The "specified Frequency" consists of the requirements of the Frequency column of each SR.
Situations where a Surveillance could be required (i.e., its Frequency could expire), but where it is not possible or not desired that it be performed until sometime after the associated LCO is within its Applicability, represent potential SR 3.0.4 conflicts. To avoid these conflicts, the SR (i.e., the Surveillance or the Frequency) is stated such that it is only "required" when it can be and should be performed. With an SR satisfied, SR 3.0.4 imposes no restriction.
(continued) 1.4-1 Renewed License l
Frequency 1.4 DIABLO CANYON ISFSI 1.4 Frequency (continued)
EXAMPLES The following examples illustrate the various ways that frequencies are specified.
EXAMPLE 1.4-1 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Verify pressure within limit 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Example 1.4-1 contains the type of SR most often encountered in the Technical Specifications (TS). The Frequency specifies an interval (12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />) during which the associated Surveillance must be performed at least one time. Performance of the Surveillance initiates the subsequent interval. Although the Frequency is stated as 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, an extension of the time interval to 1.25 times the interval specified in the Frequency is allowed by SR 3.0.2 for operational flexibility. The measurement of this interval continues at all times, even when the SR is not required to be met per SR 3.0.1 (such as when the equipment or variables are outside specified limits, or the facility is outside the Applicability of the LCO). If the interval specified by SR 3.0.2 is exceeded while the facility is in a condition specified in the Applicability of the LCO, the LCO is not met in accordance with SR 3.0.1.
If the interval as specified by SR 3.0.2 is exceeded while the facility is not in a condition specified in the Applicability of the LCO for which performance of the SR is required, the Surveillance must be performed within the Frequency requirements of SR 3.0.2 prior to entry into the specified condition. Failure to do so would result in a violation of SR 3.0.4.
(continued) 1.4-2 Renewed License l
Frequency 1.4 DIABLO CANYON ISFSI 1.4 Frequency EXAMPLES (continued)
EXAMPLE 1.4-2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Verify flow is within limits.
Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> prior to starting activity AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter Example 1.4-2 has two Frequencies. The first is a one-time performance Frequency, and the second is of the type shown in Example 1.4-1. The logical connector "AND" indicated that both Frequency requirements must be met. Each time the example activity is to be performed, the Surveillance must be performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> prior to starting the activity.
The use of "once" indicates a single performance will satisfy the specified Frequency (assuming no other Frequencies are connected by "AND"). This type of Frequency does not qualify for the 25 percent extension allowed by SR 3.0.2.
"Thereafter" indicated future performances must be established per SR 3.0.2, but only after a specified condition is first met (i.e., the "once" performance in this example). If the specified activity is cancelled or not performed, the measurement of both intervals stops. New intervals start upon preparing to restart the specified activity.
1.4-3 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0 APPROVED CONTENTS 2.1 Functional and Operating Limits 2.1.1 Contents To Be Stored a.
INTACT FUEL ASSEMBLIES, DAMAGED FUEL ASSEMBLIES, FUEL DEBRIS, and NONFUEL HARDWARE meeting the limits specified in Tables 2.1-1 through 2.1-10 may be stored in the SFSC System.
b.
For MPCs partially loaded with DAMAGED FUEL ASSEMBLIES or FUEL DEBRIS, all remaining INTACT FUEL ASSEMBLIES in the MPC shall meet the decay heat generation limits for the DAMAGED FUEL ASSEMBLIES. This requirement applies only to uniform fuel loading.
2.1.2 Uniform Fuel Loading Fuel assemblies used in uniform fuel loading shall meet all applicable limits specified in Tables 2.1-1 through 2.1-5. Fuel assembly burnup, decay heat, and cooling time limits for uniform loading are specified in Tables 2.1-6 and 2.1-7.
2.1.3 Regionalized Fuel Loading Fuel may be stored using regionalized loading in lieu of uniform loading to allow higher heat emitting fuel assemblies to be stored than would otherwise be able to be stored using uniform loading. Figures 2.1-1 through 2.1-3 define the regions for the MPC-24; MPC-24E/MPC-24EF; and MPC-32 models, respectively. Fuel assembly burnup, decay heat, and cooling time limits for regionalized loading are specified in Tables 2.1-8 and 2.1-9. In addition, fuel assemblies used in regionalized loading shall meet all other applicable limits specified in Tables 2.1-1 through 2.1-5.
2.2 Functional and Operating Limits Violations If any Fuel Specifications or Loading Conditions of 2.1 are violated, the following ACTIONS shall be completed:
a.
The affected fuel assemblies shall be placed in a safe condition.
b.
Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, notify the NRC Operations Center.
c.
Within 30 days, submit a special report which describes the cause of the violation, and ACTIONS taken to restore compliance and prevent recurrence.
2.0-1 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0 APPROVED CONTENTS (continued) 2.3 Alternate MPC-32 Fuel Selection Criteria The maximum allowable fuel assembly average burnup for a given MINIMUM ENRICHMENT is calculated as described below for a minimum cooling time of 5 years using the maximum permissible decay heat determined in Tables 2.1-7 or 2.1-9 as appropriate for uniform and regionalized loadings. Different fuel assembly average burnup limits may be calculated for different minimum enrichments (by individual fuel assembly) for use in choosing the fuel assemblies to be loaded into a given MPC.
a.
Choose a fuel assembly minimum enrichment E235.
b.
Calculate the maximum allowable fuel assembly average burnup for a minimum cooling time of 5 years using the following equation below:
Bu = (A x q) + (B x q2) + (C x q3) + [D x (E235)2] + (E x q x E235) + (F x q2 x E235) + G Where:
Bu = Maximum allowable average burnup per fuel assembly (MWD/MTU) q = Maximum allowable decay heat per storage location, in kilowatts, determined from Table 2.1-7 or 2.1-9 (e.g. 898 Watts, use 0.898)
E235 = Minimum fuel assembly average enrichment (wt% 235U) (e.g., for 4.05 wt%,
use 4.05)
A through G = Coefficients from Table 2.3-1.
c.
Calculated burnup limits shall be rounded down to the nearest integer.
d.
Calculated burnup limits greater than 68,200 MWD/MTU must be reduced to be equal to this value.
e.
Linear interpolation of calculated burnups between cooling times for a given fuel assembly maximum decay heat and minimum enrichment is permitted. For example, the allowable burnup for a cooling time of 5.5 years may be interpolated between those burnups calculated for 5 year and 6 years.
f.
Each ZR-clad fuel assembly to be stored must have a MINIMUM ENRICHMENT greater than or equal to the value used in Step 2.3.a.
g.
When complying with the maximum fuel storage location decay heat limits, users must account for the decay heat from both the fuel assembly and any NON-FUEL HARDWARE, as applicable for the particular fuel storage location, to ensure the decay heat emitted by all contents in a storage location does not exceed the limit.
2.01-a Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-2 TABLE 2.1-1 MPC-24 FUEL ASSEMBLY LIMITS A.
Allowable Contents 1.
Uranium oxide, INTACT FUEL ASSEMBLIES listed in Table 2.1-5, with or without NONFUEL HARDWARE and meeting the following specifications (Note 1):
Cladding type Zr (Note 2)
Initial enrichment As specified in Table 2.1-5 for the applicable fuel assembly.
Post-irradiation cooling time and average burnup per assembly:
Fuel As specified in Tables 2.1-6 or 2.1-8.
NONFUEL HARDWARE As specified in Table 2.1-10.
Decay heat per assembly As specified in Tables 2.1-7 or 2.1-9.
Fuel assembly length 176.8 inches (nominal design)
Fuel assembly width 8.54 inches (nominal design)
Fuel assembly weight 1,680 lb (including NONFUEL HARDWARE)
B.
Quantity per MPC: Up to 24 fuel assemblies.
C.
DAMAGED FUEL ASSEMBLIES and FUEL DEBRIS are not authorized for loading into the MPC-24.
D.
One NSA is authorized for loading in an MPC-24.
NOTE 1: Fuel assemblies containing BPRAs, WABAs, or TPDs may be stored in any fuel cell location. Fuel assemblies containing RCCAs or NSAs may only be loaded in fuel storage locations 9, 10, 15, and/or 16 of Figure 2.1-1. These requirements are in addition to any other requirements specified for uniform or regionalized fuel loading.
NOTE 2: Zr designates fuel-cladding material made of Zircaloy-2, Zircaloy-4 and ZIRLO.
Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI TABLE 2.1-2 Sheet 1 of 2 MPC-24E FUEL ASSEMBLY LIMITS A.
Allowable Contents
- 1. Uranium oxide, INTACT FUEL ASSEMBLIES listed in Table 2.1-5, with or without NONFUEL HARDWARE and meeting the following specifications (Note 1):
Cladding type Zr (Note 2)
Initial enrichment As specified in Table 2.1-5 for the applicable fuel assembly.
Post-irradiation cooling time and average burnup per assembly Fuel As specified in Tables 2.1-6 or 2.1-8.
NONFUEL HARDWARE As specified in Table 2.1-10.
Decay heat per assembly As specified in Tables 2.1-7 or 2.1-9.
Fuel assembly length
176.8 inches (nominal design)
Fuel assembly width
8.54 inches (nominal design)
Fuel assembly weight
1,680 lb (including NONFUEL HARDWARE)
- 2. Uranium oxide, DAMAGED FUEL ASSEMBLIES, with or without NONFUEL HARDWARE, placed in DAMAGED FUEL CONTAINERS. Uranium oxide DAMAGED FUEL ASSEMBLIES shall meet the criteria specified in Table 2.1-5 and meet the following specifications (Note 1):
Cladding type Zr (Note 2)
Initial enrichment
4.0 wt% 235U.
Post-irradiation cooling time and average burnup per assembly:
Fuel As specified in Tables 2.1-6 or 2.1-8.
NONFUEL HARDWARE As specified in Table 2.1-10.
Decay heat per assembly As specified in Tables 2.1-7 or 2.1-9.
Fuel assembly length
176.8 inches (nominal design)
Fuel assembly width
8.54 inches (nominal design)
Fuel assembly weight
1,680 lb (including NONFUEL HARDWARE and DFC) 2.0-3 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-4 TABLE 2.1-2 Sheet 2 of 2 B.
Quantity per MPC: Up to four (4) DAMAGED FUEL ASSEMBLIES in DAMAGED FUEL CONTAINERS, stored in fuel storage locations 3, 6, 19 and/or 22 of Figure 2.1-2. The remaining MPC-24E fuel storage locations may be filled with INTACT FUEL ASSEMBLIES meeting the applicable specifications.
C.
FUEL DEBRIS is not authorized for loading in the MPC-24E.
D.
One NSA is authorized for loading in an MPC-24E.
NOTE 1: Fuel assemblies containing BPRAs, WABAs, or TPDs may be stored in any fuel storage location. Fuel assemblies containing RCCAs or NSAs must be loaded in fuel storage locations 9, 10, 15 and/or 16 of Figure 2.1-2. These requirements are in addition to any other requirements specified for uniform or regionalized fuel loading.
NOTE 2: Zr designates fuel-cladding material, which is made of Zircaloy-2, Zircaloy-4 and ZIRLO.
Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI TABLE 2.1-3 Sheet 1 of 2 MPC-24EF FUEL ASSEMBLY LIMITS A.
Allowable Contents
- 1. Uranium oxide, INTACT FUEL ASSEMBLIES listed in Table 2.1-5, with or without NONFUEL HARDWARE and meeting the following specifications (Note 1):
Cladding type Zr (Note 3)
Initial enrichment As specified in Table 2.1-5 for the applicable fuel assembly.
Post-irradiation cooling time and average burnup per assembly:
Fuel As specified in Tables 2.1-6 or 2.1-8.
NONFUEL HARDWARE As specified in Table 2.1-10.
Decay heat per assembly As specified in Tables 2.1-7 or 2.1-9.
Fuel assembly length
176.8 inches (nominal design)
Fuel assembly width
8.54 inches (nominal design)
Fuel assembly weight
1,680 lb (including NONFUEL HARDWARE)
- 2. Uranium oxide, DAMAGED FUEL ASSEMBLIES and FUEL DEBRIS, with or without NONFUEL HARDWARE, placed in DAMAGED FUEL CONTAINERS. Uranium oxide DAMAGED FUEL ASSEMBLIES shall meet the criteria specified in Table 2.1-5 and meet the following specifications (Note 1 and 2):
Cladding type Zr (Note 3)
Initial enrichment
4.0 wt% 235U.
Post-irradiation cooling time and average burnup per assembly Fuel As specified in Tables 2.1-6 or 2.1-8.
NONFUEL HARDWARE As specified in Table 2.1-10.
Decay heat per assembly As specified in Tables 2.1-7 or 2.1-9.
Fuel assembly length
176.8 inches (nominal design)
Fuel assembly width
8.54 inches (nominal design)
Fuel assembly weight
1,680 lb (including NONFUEL HARDWARE and DFC) 2.0-5 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-6 TABLE 2.1-3 Sheet 2 of 2 B.
Quantity per MPC: Up to four (4) DAMAGED FUEL ASSEMBLIES and/or FUEL DEBRIS in DAMAGED FUEL CONTAINERS, stored in fuel storage locations 3, 6, 19 and/or 22 of Figure 2.1-2. The remaining MPC-24EF fuel storage locations may be filled with INTACT FUEL ASSEMBLIES meeting the applicable specifications.
C.
One NSA is authorized for loading in an MPC-24EF.
NOTE 1: Fuel assemblies containing BPRAs, WABAs, or TPDs may be stored in any fuel storage location. Fuel assemblies containing RCCAs or NSAs must be loaded in fuel storage locations 9, 10, 15 and/or 16 of Figure 2.1-2. These requirements are in addition to any other requirements specified for uniform or regionalized fuel loading.
NOTE 2: The total quantity of FUEL DEBRIS permitted in a single DAMAGED FUEL CONTAINER is limited to the equivalent weight and special nuclear material quantity of one INTACT FUEL ASSEMBLY.
NOTE 3: Zr designates fuel-cladding material, which is made of Zircaloy-2, Zircaloy-4 and ZIRLO.
Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-7 TABLE 2.1-4 MPC-32 FUEL ASSEMBLY LIMITS A.
Allowable Contents 1.
Uranium oxide, INTACT FUEL ASSEMBLIES listed in Table 2.1-5, with or without NONFUEL HARDWARE and meeting the following specifications (Note 1):
Cladding type Zr (Note 2)
Initial enrichment As specified in Table 2.1-5 for the applicable fuel assembly.
Post-irradiation cooling time and average burnup per assembly:
Fuel As specified in Tables 2.1-6 or 2.1-8, or Section 2.3.
NONFUEL HARDWARE As specified in Table 2.1-10.
Decay heat per assembly As specified in Tables 2.1-7 or 2.1-9.
Fuel assembly length 176.8 inches (nominal design)
Fuel assembly width 8.54 inches (nominal design)
Fuel assembly weight 1,680 lb (including NONFUEL HARDWARE)
B.
Quantity per MPC: Up to 32 intact fuel assemblies.
C.
DAMAGED FUEL ASSEMBLIES and FUEL DEBRIS are not authorized for loading in the MPC-32.
D.
One NSA is authorized for loading in an MPC-32.
NOTE 1: Fuel assemblies, with or without ITTRs, containing BPRAs, WABAs, or TPDs, may be stored in any fuel storage location. Fuel assemblies, with or without ITTRs, containing RCCAs or NSAs must be loaded in fuel storage locations 13, 14, 19 and/or 20 of Figure 2.1-3. These requirements are in addition to any other requirements specified for uniform or regionalized fuel loading.
NOTE 2: Zr designates fuel-cladding material, which is made of Zircaloy-2, Zircaloy-4 and ZIRLO.
Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-8 TABLE 2.1-5 FUEL ASSEMBLY CHARACTERISTICS (Note 1)
Fuel Assembly Type (Note 6)
Vantage 5 Standard, or LOPAR Cladding Material Zr (Note 5)
Zr (Note 5)
Design Initial U (kg/assy.) (Note 2) 467 467 Initial Enrichment (MPC-24, 24E, and 24EF without soluble boron credit) (wt% 235U)
(Note 4) 4.0 (24) 4.4 (24E/24EF) 4.0 (24) 4.4 (24E/24EF)
Initial Enrichment (MPC-24, 24E, 24EF, or 32 with soluble boron credit) (wt% 235U)
(Notes 3 and 4) 5.0 5.0 No. of Fuel Rod Locations 264 264 Fuel Rod Cladding O.D. (in.)
0.360 0.372 Fuel Rod Cladding I.D. (in.)
0.3150 0.3310 Fuel Pellet Dia. (in.)
0.3088 0.3232 Fuel Rod Pitch (in.)
0.496 0.496 Active Fuel Length (in.)
150 150 No. of Guide and/or Instrument Tubes 25 25 Guide/Instrument Tube Thickness (in.)
0.016 0.014 NOTE 1: All dimensions are design nominal values. Maximum and minimum dimensions are specified to bound variations in design nominal values among fuel assemblies.
NOTE 2: Design initial uranium weight is the nominal uranium weight specified for each assembly by the fuel manufacturer or DCPP. For each fuel assembly, the total uranium weight limit specified in this table may be increased up to 2.0 percent for comparison with DCPP fuel records to account for manufacturers tolerances.
NOTE 3: Soluble boron concentration per Technical Specification LCO 3.2.1.
NOTE 4: For those MPCs loaded with both INTACT FUEL ASSEMBLIES and DAMAGED FUEL ASSEMBLIES or FUEL DEBRIS, the maximum initial enrichment of the INTACT FUEL ASSEMBLIES is limited to the maximum initial enrichment of the DAMAGED FUEL ASSEMBLIES and FUEL DEBRIS (i.e., 4.0 wt.% 235U).
NOTE 5: Zr designates fuel-cladding material, which is made of Zircaloy-2, Zircaloy-4 and ZIRLO.
NOTE 6: Fuel assemblies meeting the characteristics may be loaded under the requirements for the listed Fuel Assembly Type, even if the name is different.
Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI TABLE 2.1-6 FUEL ASSEMBLY COOLING AND MAXIMUM AVERAGE BURNUP (UNIFORM FUEL LOADING)
Post-Irradiation Cooling Time (years)
MPC-24 Assembly Burnup (INTACT FUEL ASSEMBLIES)
(MWD/MTU)
MPC-24E/24EF Assembly Burnup (INTACT FUEL ASSEMBLIES)
(MWD/MTU)
MPC-24E/24EF Assembly Burnup (DAMAGED FUEL ASSEMBLIES and FUEL DEBRIS)
(MWD/MTU)
MPC-32 Assembly Burnup (INTACT FUEL ASSEMBLIES)
(MWD/MTU)
(Note 2) 5 40,600 41,100 39,200 32,200 6
45,000 45,000 43,700 36,500 7
44,500 37,500 8
45,000 39,900 9
41,500 10 42,900 11 44,100 12 45,000 NOTE 1: Linear interpolation between points is permitted.
NOTE 2: Burnup limits for fuel assemblies in an MPC-32 may alternatively be calculated using Section 2.3.
2.0-9 Renewed License l
DIABLO CANYON ISFSI 2.0-10 Approved Contents 2.0 TABLE 2.1-7 FUEL ASSEMBLY COOLING AND MAXIMUM DECAY HEAT (UNIFORM FUEL LOADING)
Post-Irradiation Cooling Time (years)
MPC-24 Assembly Decay Heat (INTACT FUEL ASSEMBLIES)
(Watts)
MPC-24E/24EF Assembly Decay Heat (INTACT FUEL ASSEMBLIES)
(Watts)
MPC-24E/24EF Assembly Decay Heat (DAMAGED FUEL ASSEMBLIES and FUEL DEBRIS)
(Watts)
MPC-32 Assembly Decay Heat (INTACT FUEL ASSEMBLIES)
(Watts)
[BU <45,000 MWd/MTU]
MPC-32 Assembly Decay Heat (INTACT FUEL ASSEMBLIES)
(Watts)
[BU >45,000 MWd/MTU]
5 1157 1173 1115 898 898 6
1123 1138 1081 898 898 7
1030 1043 991 898 898 8
1020 1033 981 898 898 9
1010 1023 972 898 898 10 1000 1012 962 898 898 11 996 1008 958 898 898 12 992 1004 954 898 898 13 987 999 949 898 898 14 983 995 945 898 898 15 979 991 941 898 898 NOTE 1: Linear interpolation between points is permitted.
NOTE 2: Includes all sources of heat (i.e., fuel and NONFUEL HARDWARE).
Renewed License l
DIABLO CANYON ISFSI 2.0-11 Approved Contents 2.0 TABLE 2.1-8 FUEL ASSEMBLY COOLING AND MAXIMUM AVERAGE BURNUP (REGIONALIZED FUEL LOADING)
Post-Irradiation Cooling Time (years)
MPC-24 Assembly Burnup for Region 1 (MWD/MTU)
MPC-24 Assembly Burnup for Region 2 (MWD/MTU)
MPC-24E/24EF Assembly Burnup for Region 1 (MWD/MTU)
MPC-24E/24EF Assembly Burnup for Region 2 (MWD/MTU)
MPC-32 Assembly Burnup for Region 1 (MWD/MTU)
Note 3 MPC-32 Assembly Burnup for Region 2 (MWD/MTU)
Note 3 5
45,000 32,200 45,000 32,200 39,800 22,100 6
37,400 37,400 43,400 26,200 7
41,100 41,100 44,500 29,100 8
43,800 43,800 45,000 31,200 9
45,000 45,000 32,700 10 34,100 11 35,200 12 36,200 13 37,000 14 37,800 15 38,600 16 39,400 17 40,200 18 40,800 19 41,500 20 42,200 NOTE 1: Linear interpolation between points is permitted.
NOTE 2: These limits apply to INTACT FUEL ASSEMBLIES, DAMAGED FUEL ASSEMBLIES, and FUEL DEBRIS.
NOTE 3: Burnup limits for fuel assemblies in an MPC-32 may alternatively be calculated using Section 2.3.
Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI TABLE 2.1-9 FUEL ASSEMBLY COOLING AND MAXIMUM DECAY HEAT (REGIONALIZED FUEL LOADING)
Post-Irradiation Cooling Time (years)
MPC-24 Assembly Decay Heat for Region 1 (Watts)
MPC-24 Assembly Decay Heat for Region 2 (Watts)
MPC-24E/24EF Assembly Decay Heat for Region 1 (Watts)
MPC-24E/24EF Assembly Decay Heat for Region 2 (Watts)
MPC-32 Assembly Decay Heat for Region 1 (Watts)
MPC-32 Assembly Decay Heat for Region 2 (Watts) 5 1470 900 1540 900 1131 600 6
1470 900 1540 900 1131 600 7
1335 900 1395 900 1131 600 8
1301 900 1360 900 1131 600 9
1268 900 1325 900 1131 600 10 1235 900 1290 900 1131 600 11 1221 900 1275 900 1131 600 12 1207 900 1260 900 1131 600 13 1193 900 1245 900 1131 600 14 1179 900 1230 900 1131 600 15 1165 900 1215 900 1131 600 NOTE 1: Linear interpolation between points is permitted.
NOTE 2: Includes all sources of decay heat (i.e., fuel and NONFUEL HARDWARE).
NOTE 3: These limits apply to INTACT FUEL ASSEMBLIES, DAMAGED FUEL ASSEMBLIES, and FUEL DEBRIS.
2.0-12 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI TABLE 2.1-10 NONFUEL HARDWARE COOLING AND AVERAGE ACTIVATION Post-Irradiation Cooling Time (years)
BPRA and WABA Burnup (MWD/MTU)
TPD and NSA Burnup (MWD/MTU)
RCCA Burnup (MWD/MTU) 3 20,000 Not Authorized Not Authorized 4
25,000 20,000 Not Authorized 5
30,000 25,000 630,000 6
40,000 30,000 7
45,000 40,000 8
50,000 45,000 9
60,000 50,000 10 60,000 11 75,000 12 90,000 13 180,000 14 630,000 NOTE 1: Linear interpolation between points is permitted, except that TPD and NSA burnups > 180,000 MWD/MTU and 630,000 MWD/MTU must be cooled 14 years.
NOTE 2: Applicable to uniform loading and regionalized loading.
NOTE 3: Deleted NOTE 4: Non-fuel hardware burnup and cooling times are not applicable to ITTRs since they are installed post-irradiation.
NOTE 5: Only one NSA is authorized for loading in any MPC.
2.0-13 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-13a Table 2.3-1 (page 1 of 2)
Fuel Assembly Time-Dependent Coefficients Cooling Time (years)
Vantage 5 fuel A
B C
D E
F G
> 5 40315.9
-9724 1622.89
-140.459 3170.28
-547.749 425.136
> 6 49378.5
-15653.1 3029.25
-164.712 3532.55
-628.93 842.73
> 7 56759.5
-21320.4 4598.78
-190.58 3873.21
-698.143 975.46
> 8 63153.4
-26463.8 6102.47
-201.262 4021.84
-685.431 848.497
> 9 67874.9
-30519.2 7442.84
-218.184 4287.23
-754.597 723.305
> 10 72676.8
-34855.2 8928.27
-222.423 4382.07
-741.243 387.877
> 11 75623
-37457.1 9927.65
-232.962 4564.55
-792.051 388.402
> 12 80141.8
-41736.5 11509.8
-232.944 4624.72
-787.134
-164.727
> 13 83587.5
-45016.4 12800.9
-230.643 4623.2
-745.177
-428.635
> 14 86311.3
-47443.4 13815.2
-228.162 4638.89
-729.425
-561.758
> 15 87839.2
-48704.1 14500.3
-231.979 4747.67
-775.801
-441.959
> 16 91190.5
-51877.4 15813.2
-225.768 4692.45
-719.311
-756.537
> 17 94512
-55201.2 17306.1
-224.328 4740.86
-747.11
-1129.15
> 18 96959
-57459.9 18403.8
-220.038 4721.02
-726.928
-1272.47
> 19 99061.1
-59172.1 19253.1
-214.045 4663.37
-679.362
-1309.88
> 20 100305
-59997.5 19841.1
-216.112 4721.71
-705.463
-1148.45 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI 2.0-13b Table 2.3-1 (page 2 of 2)
Fuel Assembly Time-Dependent Coefficients Cooling Time (years)
Standard, and LOPAR fuel A
B C
D E
F G
> 5 36190.4
-7783.2 1186.37
-130.008 2769.53
-438.716 519.95
> 6 44159
-12517.5 2209.54
-150.234 3042.25
-489.858 924.151
> 7 50399.6
-16780.6 3277.26
-173.223 3336.58
-555.743 1129.66
> 8 55453.9
-20420 4259.68
-189.355 3531.65
-581.917 1105.62
> 9 59469.3
-23459.8 5176.62
-199.63 3709.99
-626.667 1028.74
> 10 63200.5
-26319.6 6047.8
-203.233 3783.02
-619.949 805.311
> 11 65636.3
-28258.3 6757.23
-214.247 3972.8
-688.56 843.457
> 12 68989.7
-30904.4 7626.53
-212.539 3995.62
-678.037 495.032
> 13 71616.6
-32962.2 8360.45
-210.386 4009.11
-666.542 317.009
> 14 73923.9
-34748 9037.75
-207.668 4020.13
-662.692 183.086
> 15 76131.8
-36422.3 9692.32
-203.428 4014.55
-655.981 47.5234
> 16 77376.5
-37224.7 10111.4
-207.581 4110.76
-703.37 161.128
> 17 80294.9
-39675.9 11065.9
-201.194 4079.24
-691.636
-173.782
> 18 82219.8
-41064.8 11672.1
-195.431 4043.83
-675.432
-286.059
> 19 84168.9
-42503.6 12309.4
-190.602 4008.19
-656.192
-372.411
> 20 86074.2
-43854.4 12935.9
-185.767 3985.57
-656.72
-475.953 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI REGION 1 REGION 2 LEGEND:
90 1
2 7
4 5
6 8
9 10 11 12 17 18 16 15 14 13 270 180 0
3 22 21 20 19 24 23 DIABLO CANYON ISFSI FIGURE 2.1-1 FUEL LOADING REGIONS MPC-24 2.0-14 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI DIABLO CANYON ISFSI FIGURE 2.1-2 FUEL LOADING REGIONS MPC-24E/24EF 2.0-15 Renewed License l
Approved Contents 2.0 DIABLO CANYON ISFSI DIABLO CANYON ISFSI FIGURE 2.1-3 FUEL LOADING REGIONS MPC-32 2.0-16 Renewed License l
LCO Applicability 3.0 DIABLO CANYON ISFSI 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY LCO 3.0.1 LCOs shall be met during specified conditions in the Applicability, except as provided in LCO 3.0.2 LCO 3.0.2 Upon discovery of a failure to meet an LCO, the Required Actions of the associated Conditions shall be met.
If the LCO is met or is no longer applicable prior to expiration of the specified Completion Time(s), completion of the Required Action(s) is not required, unless otherwise stated.
LCO 3.0.3 Not applicable.
LCO 3.0.4 When an LCO is not met, entry into a specified condition in the Applicability shall not be made except when the associated ACTIONS to be entered permit continued operation in the specified condition in the Applicability for an unlimited period of time. This Specification shall not prevent changes in specified conditions in the Applicability that are required to comply with ACTIONS or that are related to the unloading of an SFSC.
LCO 3.0.5 Not applicable.
3.0-1 Renewed License l
SR Applicability 3.0 DIABLO CANYON ISFSI 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY SR 3.0.1 SRs shall be met during specified conditions in the Applicability for individual LCOs, unless otherwise stated in the SR. Failure to meet a Surveillance, whether such failure is experienced during the performance of the Surveillance or between performances of the Surveillance, shall be failure to meet the LCO. Failure to perform a Surveillance within the specified Frequency shall be failure to meet the LCO except as provided in SR 3.0.3. Surveillances do not have to be performed on equipment or variables outside specified limits.
SR 3.0.2 The specified Frequency for each SR is met if the Surveillance is performed within 1.25 times the interval specified in the Frequency, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.
For Frequencies specified as once, the above interval extension does not apply. If a Completion Time requires periodic performance on a once per basis, the above Frequency extension applies to each performance after the initial performance.
Exceptions to this Specification are stated in the individual Specifications.
SR 3.0.3 If it is discovered that a Surveillance was not performed within its specified Frequency, then compliance with the requirement to declare the LCO not met may be delayed, from the time of discovery, up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or up to the limit of the specified Frequency, whichever is less. This delay period is permitted to allow performance of the Surveillance.
If the Surveillance is not performed within the delay period, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered. When the Surveillance is performed within the delay period and the Surveillance is not met, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.
SR 3.0.4 Entry into a specified condition in the Applicability of an LCO shall not be made unless the LCOs Surveillances have been met within their specified Frequency. This provision shall not prevent entry into specified conditions in the Applicability that are required to comply with Actions or that are related to the unloading of an SFSC.
3.0-2 Renewed License l
MPC 3.1.1 DIABLO CANYON ISFSI 3.1-1 3.1 SPENT FUEL STORAGE CASK (SFSC) INTEGRITY 3.1.1 MULTI-PURPOSE CANISTER (MPC)
LCO 3.1.1 The MPC shall be dry and helium filled.
APPLICABILITY:
During TRANSPORT OPERATIONS and STORAGE OPERATIONS ACTIONS
NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each MPC.
CONDITION REQUIRED ACTION COMPLETION TIME A.
MPC cavity drying demoisturizer exit gas temperature limit not met.
A.1.
Perform an engineering evaluation to determine the quantity of moisture left in the MPC.
AND 7 days A.2 Develop and initiate corrective actions necessary to return the MPC to an analyzed condition.
30 days B.
MPC helium backfill pressure limit not met.
B.1 Perform an engineering evaluation to determine the impact of helium pressure differential.
AND 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> B.2 Develop and initiate corrective actions necessary to return the MPC to an analyzed condition.
14 days (continued)
Renewed License l
MPC 3.1.1 DIABLO CANYON ISFSI 3.1-2 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME C.
MPC helium leak rate limit for vent and drain port cover plate welds not met.
C.1 Perform an engineering evaluation to determine the impact of increased helium leak rate on heat removal capability and offsite dose.
AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> C.2 Develop and initiate corrective actions necessary to return the MPC to an analyzed condition.
7 days D.
Required Actions and associated Completion Times not met.
D.1 Remove all fuel assemblies from the MPC.
30 days SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.1.1 While recirculating helium through the MPC cavity, verify that the gas temperature exiting the demoisturizer is 21 F for 30 min.
Once, prior to TRANSPORT OPERATIONS.
SR 3.1.1.2 Verify MPC helium backfill pressure is:
29.3 psig and 33.3 psig at a reference temperature of 70° F for an MPC containing only low burnup fuel.
29.3 psig and 33.3 psig at a reference temperature of 70° F for an MPC-32 originally loaded uniformly with high burnup fuel with a total heat load 24 kW.
34 psig and 40 psig at a reference temperature of 70° F for an MPC-32 containing high burnup fuel loaded up to the maximum regional or uniform total heat load.
Once, prior to TRANSPORT OPERATIONS.
SR 3.1.1.3 Verify that the total helium leak rate through the MPC vent and drain port confinement welds meets the leaktight criteria of ANSI N14.5-1997.
Once, prior to TRANSPORT OPERATIONS.
Renewed License l
SFSC Heat Removal System 3.1.2 DIABLO CANYON ISFSI 3.1-3 3.1 SPENT FUEL STORAGE CASK (SFSC) INTEGRITY 3.1.2 Spent Fuel Storage Cask (SFSC) Heat Removal System LCO 3.1.2 The SFSC Heat Removal System shall be operable.
APPLICABILITY:
During STORAGE OPERATIONS ACTIONS
NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each SFSC.
CONDITION REQUIRED ACTION COMPLETION TIME A.
SFSC Heat Removal System operable, but partially (< 50%) blocked.
A.1 Remove blockage.
8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> B.
SFSC Heat Removal System inoperable.
B.1 Restore SFSC Heat Removal System to operable status.
8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> C.
Required Action B.1 and associated Completion Time not met.
C.1 Measure SFSC dose rates in accordance with the Radiation Protection Program.
AND C.2.1 Restore SFSC Heat removal System to operable status.
OR C.2.2 Transfer the MPC into a TRANSFER CASK.
Immediately and once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter.
24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> 24 hours SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.2.1 Verify all SFSC inlet and outlet air duct screens are free of blockage.
24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Renewed License l
Fuel Cool-Down 3.1.3 DIABLO CANYON ISFSI 3.1 SPENT FUEL STORAGE CASK (SFSC) INTEGRITY 3.1.3 Fuel Cool-Down LCO 3.1.3 The MPC helium exit temperature shall be 200F.
NOTE-------------------------------------------------------------
The LCO is only applicable to wet UNLOADING OPERATIONS.
APPLICABILITY:
During UNLOADING OPERATIONS prior to re-flooding.
ACTIONS
NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each MPC.
CONDITION REQUIRED ACTION COMPLETION TIME A.
MPC helium gas exit temperature not within limit.
A.1 Establish MPC helium gas exit temperature within limit.
AND Prior to initiating MPC reflooding operations.
A.2 Ensure adequate heat transfer from the MPC to the environment 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.3.1 Verify MPC helium gas exit temperature within limit.
Prior to MPC reflooding operations.
3.1-4 Renewed License l
Supplemental Cooling System 3.1.4 DIABLO CANYON ISFSI 3.1 SPENT FUEL STORAGE CASK (SFSC) INTEGRITY 3.1.4 Supplemental Cooling System LCO 3.1.4 The Supplemental Cooling System (SCS) shall be operable.
NOTE----------------------------------------------------------------
Upon reaching steady state operation, the SCS may be temporarily disabled for a short duration
(< 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />) to facilitate necessary operational evolutions, such as movement of the TRANSFER CASK through a doorway, or other similar operations.
APPLICABILITY:
When a loaded MPC-32, containing one or more fuel assemblies with an average burnup of > 45,000 MWD/MTU, is in the TRANSFER CASK, and:
a.1 Bulk water has been removed from the MPC.
AND a.2 Forced helium dehydration has been secured for greater than 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
AND a.3 The TRANSFER CASK containing the MPC has temporary shielding installed during cask processing operations within the fuel handling building.
OR b.1 The MPC to be unloaded has been transferred into the TRANSFER CASK for greater than 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
AND b.2 The MPC was originally loaded with a helium backfill pressure of 29.3 psig and 33.3 psig at a reference temperature of 70° F.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
Supplemental Cooling System inoperable A.1 Restore Supplemental Cooling System to operable status.
7 days B.
Required Action A.1 and associated Completion Time not met.
B.1 Remove all fuel assemblies from the MPC.
30 days SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.4.1 Verify Supplemental Cooling System is operable 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 3.1-5 Renewed License l
Dissolved Boron Concentration 3.2.1 DIABLO CANYON ISFSI 3.2 Cask Criticality Control Program 3.2.1 Dissolved Boron Concentration LCO 3.2.1 The dissolved boron concentration in the water of the MPC cavity shall be as follows:
a.
For all MPCs with one or more fuel assemblies having initial enrichment of 4.1 wt% 235 U: 2000 ppmb.
b.
For MPC24/24E/24EF with one or more fuel assemblies having initial enrichment of > 4.1 and 5.0 wt% 235 U: 2000 ppmb.
c.
For MPC-32 with one or more fuel assemblies having initial enrichment of 5.0 wt% 235 U: 2600 ppmb.
NOTE-------------------------------------------------------------
For MPC-32, with maximum initial enrichments between 4.1 wt% and 5.0 wt% 235 U, the minimum dissolved boron concentration may be determined by linear interpolation between 2000 ppmb at 4.1 wt% and 2600 ppmb at 5.0 wt% 235 U, based on the assembly with the highest initial enrichment to be loaded.
APPLICABILITY:
During LOADING OPERATIONS and UNLOADING OPERATIONS with water and at least one fuel assembly in the MPC.
ACTIONS
NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each MPC.
CONDITION REQUIRED ACTION COMPLETION TIME A.
Dissolved boron concentration not met.
A.1 Suspend LOADING OPERATIONS or UNLOADING OPERATIONS AND Immediately A.2 Suspend positive reactivity additions AND Immediately A.3 Initiate action to restore boron concentration to within limits Immediately 3.2-1 Renewed License l
Dissolved Boron Concentration 3.2.1 DIABLO CANYON ISFSI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY NOTE This surveillance is only required to be performed if the MPC is submerged in water or if water is to be added to or recirculated through the MPC.
SR 3.2.1.1 Verify the dissolved boron concentration is met using two independent measurements.
Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> prior to commencing LOADING OPERATIONS AND Every 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> thereafter while the MPC is in the spent fuel pool or while water is in the MPC.
NOTE This surveillance is only required to be performed if the MPC is submerged in water or if water is to be added to or recirculated through the MPC.
SR 3.2.1.2 Verify the dissolved boron concentration is met using two independent measurements.
Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> prior to commencing UNLOADING OPERATIONS AND Every 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> thereafter while the MPC is in the spent fuel pool or while water is in the MPC.
3.2-2 Renewed License l
Design Features 4.0 DIABLO CANYON ISFSI 4.0-1 4.0 DESIGN FEATURES 4.1 Design Features Significant to Safety 4.1.1 Criticality Control a.
MULTI-PURPOSE CANISTER (MPC) MPC-24 1.
Flux trap size: 1.09 in.
2.
10B loading in the Boral neutron absorbers: 0.0267 g/cm2 (Boral) and 0.0223 g/cm2 (METAMIC) b MPC-24E and MPC-24EF 1.
Flux trap size:
Cells 3, 6, 19, and 22: 0.776 in.
All Other Cells: 1.076 in.
2.
10B loading in the Boral neutron absorbers: 0.0372 g/cm2 (Boral) and 0.0310 g/cm2 (METAMIC) c.
MPC-32 1.
Fuel cell pitch: 9.158 in.
2.
10B loading in the Boral neutron absorbers: 0.0372 g/cm2 (Boral) and 0.0310 g/cm2 (METAMIC) 4.1.2 Design Features Important to Criticality Control a.
Fuel spacers shall be sized to ensure that the active fuel region of intact fuel assemblies remain within the neutron poison region of the MPC basket with the water in the MPC.
b.
The B4C content in METAMIC shall be 33.0 wt%.
c.
Neutron Absorber Test The minimum 10B for the neutron absorber shall meet the minimum requirements for each MPC model specified in Section 4.1.1 above.
(continued)
Renewed License l
Design Features 4.0 DIABLO CANYON ISFSI 4.0-2 4.0 DESIGN FEATURES (continued) 4.1.3 Design Features Important to Thermal Analysis
- a. A maximum average yearly temperature of 65o F is the basis for a loaded overpack in the cask transfer facility, or storage on the ISFSI pad.
- b. A maximum temperature of 100o F, averaged over a 3-day period, is the basis for transfer activities in the transfer cask.
4.2 Codes and Standards The following provides information on the governing codes for the confinement boundary (important to Safety) design:
MPC (Shell and Head)
Applicable Codes Editions/Years Material Procurement ASME III, NB-2000 ASME Code, 1995 Edition. 1997 Addenda Design ASME III, NB-3200 ASME Code, 1995 Edition. 1997 Addenda Fabrication ASME III, NB-4000 ASME Code, 1995 Edition. 1997 Addenda Examination ASME III, NB-5000 ASME Code, 1995 Edition. 1997 Addenda Any specific alternatives to these codes and standards, and the codes and standards for other components followed for the Diablo Canyon ISFSI storage system, are provided in the Diablo Canyon ISFSI Safety Analysis Report (SAR).
4.2.1 Alternatives to Design Codes, Standards, and Criteria Proposed construction/fabrication alternatives to the above MPC design codes and standards, including alternatives in SAR Table 3.4-6, may be used when authorized by the Director of the Office of Nuclear Material Safety and Safeguards or designee. The licensee should demonstrate that:
1.
The proposed alternatives would provide an acceptable level of quality and safety, or 2.
Compliance with the specified requirements of ASME Code Section III, 1995 Edition with Addenda through 1997, would result in hardship or unusual difficulty without a compensating increase in the level of quality and safety.
Requests for relief in accordance with this section shall be submitted in accordance with 10 CFR 72.4.
(continued)
Renewed License l
Design Features 4.0 DIABLO CANYON ISFSI 4.0 DESIGN FEATURES (continued) 4.3 Cask Handling/Cask Transfer Facility 4.3.1 Cask Transporter A site-specific cask transporter is used to transport the TRANSFER CASK between the power plant and the CASK TRANSFER FACILITY (CTF) and the SPENT FUEL STORAGE CASK (SFSC) between the CTF and ISFSI pad. The requirements for the cask transporter are as follows:
- a. TRANSPORT OPERATIONS shall be conducted using the cask transporter.
- b. The cask transporter fuel tank shall not contain > 50 gallons of diesel fuel at any time.
c.
The cask transporter shall be designed, fabricated, inspected, maintained, operated, and tested in accordance with the applicable guidelines of NUREG-0612.
- d. The cask transporter lifting towers shall have redundant drop protection features.
- e. Lifting of a SFSC, loaded TRANSFER CASK, or loaded MPC outside of structures governed by 10 CFR 50 shall be performed with lifting devices that are designed, fabricated, inspected, maintained, operated and tested in accordance with the applicable guidelines of NUREG-0612, "Control of Heavy Loads at Nuclear Power Plants.
4.3.2 Storage Capacity The Diablo Canyon ISFSI can accommodate up to 4,400 spent fuel assemblies and other NONFUEL HARDWARE. The ISFSI storage capacity will accommodate up to 140 SFSCs (138 plus 2 spare locations).
4.3.3 SFSC Load Handling Equipment Lifting of a SFSC outside of structures governed by 10 CFR 50 shall be performed with load handling equipment that is designed, fabricated, inspected, maintained, operated and tested in accordance with the applicable guidelines of NUREG-0612, "Control of Heavy Loads at Nuclear Power Plants as clarified by Section 4.3.4 below. The CTF requirements in Section 4.3.4 below do not apply to heavy loads governed by the regulations of 10 CFR 50.
4.3.4 CTF Structure Requirements
- a. Weldment and Reinforced Concrete
- 1. The weldment structure of the CTF shall be designed to comply with the stress limits of ASME Code,Section III, Subsection NF, Class 3 for linear structures.
All compression-loaded members shall satisfy the buckling criteria of ASME Section III, Subsection NF. The applicable loads, load combinations, and associated service condition definitions are provided in Diablo Canyon ISFSI SAR Section 4.4.5.
- 2. The reinforced concrete structure of the CTF shall be designed in accordance with ACI-349-1997, as clarified in Diablo Canyon ISFSI SAR Section 4.2.1.2.
(continued) 4.0-3 Renewed License l
Design Features 4.0 DIABLO CANYON ISFSI 4.0 DESIGN FEATURES (continued)
- b. Mobile Load Handling Equipment Mobile load handling equipment used in lieu of the cask transporter, shall meet the guidelines of NUREG-0612, Section 5.1, with the following clarifications:
- 1. Mobile lifting devices shall have a minimum safety factor of two over the allowable load table for the lifting device in accordance with the guidance of NUREG-0612, Section 5.1.6(1)(a) and shall be capable of stopping and holding the load during a Design Basis Earthquake (DBE) event.
- 2. Mobile lifting devices shall conform to the requirements of ASME B30.5, Mobile and Locomotive Cranes, in lieu of the requirements of ASME B30.2, Overhead and Gantry Cranes.
- 3. Mobile cranes are not required to meet the guidance of NUREG-0612, Section 5.1.6(2) for new cranes.
- 4. Horizontal movements of the TRANSFER CASK and MPC using a mobile crane are prohibited.
4.0-4 Renewed License l
Administrative Controls 5.0 DIABLO CANYON ISFSI 5.0 ADMINISTRATIVE CONTROLS 5.1 Administrative Programs The following programs shall be established, implemented, and maintained:
5.1.1 Technical Specifications (TS) Bases Control Program This program provides a means for processing changes to the Bases of these TS.
- a. Changes to the TS Bases shall be made under appropriate administrative controls and reviews.
- b. Changes to the TS Bases may be made without prior NRC approval in accordance with the criteria in 10 CFR 72.48.
c.
The TS Bases Control Program shall contain provisions to ensure that the TS Bases are maintained consistent with the Diablo Canyon ISFSI SAR.
- d. Proposed changes that do not meet the criteria of 5.1.1.b above shall be reviewed and approved by the NRC prior to implementation. Changes to the TS Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 72.48 (d) (2).
5.1.2 Radioactive Effluent Control Program This program is established and maintained to:
- a. Implement the requirements of 10 CFR 72.44 (d) or 72.126, as appropriate
- b. Provide limits on surface contamination of the TRANSFER CASK and verification of meeting those limits prior to removal of a loaded TRANSFER CASK from the fuel handling building/auxiliary building.
c.
Provide MPC leakage rate limits and verification of meeting those limits prior to removal of a loaded TRANSFER CASK from the fuel handling building/auxiliary building.
- d. Provide an effluent monitoring program, as appropriate, if the surface contamination limits are greater than the values specified in Regulatory Guide 1.86; or if the leakage rate limits are greater then the values specified as Leaktight in ANSI N14.5 - 1997 Leakage Tests on Packages for Shipment.
(continued) 5.0-1 Renewed License l
Administrative Controls 5.0 DIABLO CANYON ISFSI 5.0-2 5.0 ADMINISTRATIVE CONTROLS (continued) 5.1.3 MPC and SFSC Loading, Unloading, and Preparation Program This program shall be established and maintained to implement Diablo Canyon ISFSI SAR Section 10.2 requirements for loading fuel and components into MPCs, unloading fuel and components from MPCs, and preparing the MPCs for storage in the SFSCs.
The requirements of the program for loading and preparing the MPC shall be complete prior to removing the MPC from the fuel handling building/auxiliary building. The program provides for evaluation and control of the following requirements during the applicable operation:
a.
Verify that no transfer cask handling operations are allowed at environmental temperatures below -18 °C [0 °F].
b.
Verify that the water is maintained to provide adequate cooling in the annular gap between the loaded MPC and the transfer cask during MPC reflooding operations (unloading).
c.
The water temperature of a water-filled or partially filled loaded MPC shall be shown by analysis to be less than boiling at all times.
d.
Verify that the drying times and pressures assure that fuel cladding temperature limit is not violated and the MPC is adequately dry.
e.
Verify that the inerting backfill pressure and purity assure adequate heat transfer and corrosion control.
f.
Verify that leak testing assures adequate MPC integrity and consistency with offsite dose analysis.
g.
Verify surface dose rates on the TRANSFER CASK are adequate to assure proper loading and consistency with the offsite dose analysis.
h.
Verify surface dose rates on the SFSCs are adequate to assure proper storage and consistency with the offsite dose analysis.
i.
During MPC re-flooding, verify the helium exit temperature is such that water quenching or flashing does not occur.
j.
Verify that combustible gases in the MPC are monitored and controlled to avoid combustion during MPC lid-to-shell welding or MPC cutting activities.
k.
For the MPC lid-to-shell weld and the MPC enclosure vessel and lid, the weld must be at minimum of three weld layers. If PT alone is used, it will be tested at least three different weld layers, including the root and final weld layers and each approximately 3/8-inch of weld depth.
l.
Very that fuel cladding is not exposed to an oxidizing environment by maintaining the cladding in water or an inert atmosphere.
(continued)
Renewed License l
Administrative Controls 5.0 DIABLO CANYON ISFSI 5.0 ADMINISTRATIVE CONTROLS (continued)
- m. Verify that operational controls and surveillance criteria are adequate to maintain minimum soluble boron concentrations within the MPC while outside of the spent fuel pool. The controls shall consider potential water recirculation activities in the cask system and potential use of external water sources (if any) near the system during normal and off-normal operations.
This program will control limits, surveillances, compensatory measures and appropriate completion times to assure the integrity of the fuel cladding at all times in preparation of and during LOADING, UNLOADING or TRANSPORT OPERATIONS, as applicable.
5.1.4 ISFSI Operations Program This program will implement the Diablo Canyon ISFSI SAR requirements for ISFSI operations. It will include criteria to be verified and controlled:
a)
SFSC cask storage location.
b)
Design features listed in Section 4.0 and design basis ISFSI pad parameters consistent with the Diablo Canyon ISFSI SAR analysis.
c)
Condition of the ISFSI Pad anchor bolt surface coatings exposed directly to the elements.
5.1.5 Cask Transportation Evaluation Program This program will evaluate and control the transportation of loaded MPCs between the DCPP fuel handling building/auxiliary building, the CTF and the ISFSI storage pads.
Included in this program will be pre-transport evaluation and control during transportation of the following:
Transportation route road surface conditions Onsite hazards along the transportation route Security Transporter control functions and operability CTF equipment operability SFSC auxiliary cooling capability availability 5.0-3 Renewed License l