ML20235E726

From kanterella
Revision as of 18:11, 20 March 2021 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Requests Addl Info,Including Program for Lubricating Oxygen Sampling Sys Isolation Valves,Analysis of Cause of Two Automatic Isolation Valves in Series Failure to Close,Based on Review of
ML20235E726
Person / Time
Site: Dresden, Quad Cities, 05000000
Issue date: 11/15/1972
From: Skovholt D
US ATOMIC ENERGY COMMISSION (AEC)
To: Butterfield L
COMMONWEALTH EDISON CO.
Shared Package
ML20235B311 List: ... further results
References
FOIA-87-111 NUDOCS 8709280244
Download: ML20235E726 (2)


Text

, .

.--. t' a . . _ . . ,

~L

,5*t,e. 9 4

NOV 15 *e72 Do * 'Nos. 50-237, 50 249, 50 254 r.d 50-265

. t Comonwealta Edison Company i -' ATTN fir. L. D. Butterfield, Jr.

Nuclear Licensing Administrator Post Office Box 767 Chicago, Illinois 60690 Genticmen.

Your letter of June 23,1972 (W. Worden to E. Dioch) , informed us of valve failures during a test of a Dreadca 2 containment instrument line. In subsequent conversations with you, we discussed the safety significt.co of the failure and additional. corrective actions t> be taken. Essed on our review of your letter and on subsequent discussions, we request that you submit the following information for Dresden Units 2 and 3 and as applicaolo for Quad-Citics Units 1 and 2:

1. Your program for lubricating oxygen sampling system isolation j valves.

l le 2. Tour analysis of the cause of two automatic icolation vn3ves j in seriou failure to close and your evaluation of the

possibility of similar valve failures in the oxygen analyzer or other systems.
3. It is our understanding that containment integrity could bc lost by the rupture of a tube in the oxygen analyzer system {

if the particulate sampling linea are open uhcn the contain- ]

ncnt is pressurized. If this is correct, we request that i

'you either:

a. modify the sampling system and test its capability to withstand full accident pressure, or

\

8709280244 870921 f PDR FDIA .

MENZ87-111 PDR g

{*

._ .h

  • . f.
  • L

/~

L Commonwealth Edison Company NOV I h 197?.

l

b. provide means for automatic isolation of the particulate sample lines or. oxygen analyzer or provida remote manual isolation with a procedure specifying when the valves are to be closed, or. ,

L

c. verify by calculation that the mari== leakage through the oxygen analyzer would not add significantly to accident doses.

We request that you submit this information within 60 days from the date of this letter

  • ch one signed and fif ty nine additional copies.

Sincerely',

L

. d*

.'i Donald J. Skovholt Assistant Director for Operating Reactors Directorate of Licensing cca John W. Rowe, Esquire i Ioham, Lincoln & Bccle . Distribution l l Counselors at Lev docket File One First National Pla::a PDRs y Chicago, Illinois 60670 Locak PLRs

{

l RP Reading Mr. Charlos Whitmore Branch Reading President and Chairman ACRS (16) .#

Iowa-Illinois Gas and JRBuchanan, ORNL Electric Cocpany DJSkovholt, L:0R j 200 East Second Avenue R0 (3) j Davenport, Iowa 52801 . JScinto, OGC I I

MKarman, OGC I DLZiemann, L: RB #2 I RDSilver, L: URB #2  !

JIRiesland, i:0RB #2 TJCarter, L:LR RMDiggs, L:t.RB #2 i

l L 2 L:0RB #2 L:0 82 QR #2 3.0. . . . . > L:0R 1

orric E . .

. p .. - . s.

u ..

SURNAME . .RDS11ver:sjh esland iggs Ziemann

. DJSkobholt

, , , , , 11/13/72 11/13/72 11/13/72 Fem AEC 318 (Rev. 9-88) AECM 0240 11//Y/72 11/h...72 'f M