.--. t' a . . _ . . ,

~L

,5*t,e. 9 4

NOV 15 *e72 Do * 'Nos. 50-237, 50 249, 50 254 r.d 50-265

. t Comonwealta Edison Company i -' ATTN fir. L. D. Butterfield, Jr.

Nuclear Licensing Administrator Post Office Box 767 Chicago, Illinois 60690 Genticmen.

Your letter of June 23,1972 (W. Worden to E. Dioch) , informed us of valve failures during a test of a Dreadca 2 containment instrument line. In subsequent conversations with you, we discussed the safety significt.co of the failure and additional. corrective actions t> be taken. Essed on our review of your letter and on subsequent discussions, we request that you submit the following information for Dresden Units 2 and 3 and as applicaolo for Quad-Citics Units 1 and 2:

1. Your program for lubricating oxygen sampling system isolation j valves.

l le 2. Tour analysis of the cause of two automatic icolation vn3ves j in seriou failure to close and your evaluation of the

possibility of similar valve failures in the oxygen analyzer or other systems.
3. It is our understanding that containment integrity could bc lost by the rupture of a tube in the oxygen analyzer system {

if the particulate sampling linea are open uhcn the contain- ]

ncnt is pressurized. If this is correct, we request that i

'you either:

a. modify the sampling system and test its capability to withstand full accident pressure, or

\

8709280244 870921 f PDR FDIA .

MENZ87-111 PDR g

{*

._ .h

  • . f.
  • L

/~

L Commonwealth Edison Company NOV I h 197?.

l

b. provide means for automatic isolation of the particulate sample lines or. oxygen analyzer or provida remote manual isolation with a procedure specifying when the valves are to be closed, or. ,

L

c. verify by calculation that the mari== leakage through the oxygen analyzer would not add significantly to accident doses.

We request that you submit this information within 60 days from the date of this letter

  • ch one signed and fif ty nine additional copies.

Sincerely',

L

. d*

.'i Donald J. Skovholt Assistant Director for Operating Reactors Directorate of Licensing cca John W. Rowe, Esquire i Ioham, Lincoln & Bccle . Distribution l l Counselors at Lev docket File One First National Pla::a PDRs y Chicago, Illinois 60670 Locak PLRs

{

l RP Reading Mr. Charlos Whitmore Branch Reading President and Chairman ACRS (16) .#

Iowa-Illinois Gas and JRBuchanan, ORNL Electric Cocpany DJSkovholt, L:0R j 200 East Second Avenue R0 (3) j Davenport, Iowa 52801 . JScinto, OGC I I

MKarman, OGC I DLZiemann, L: RB #2 I RDSilver, L: URB #2  !

JIRiesland, i:0RB #2 TJCarter, L:LR RMDiggs, L:t.RB #2 i

l L 2 L:0RB #2 L:0 82 QR #2 3.0. . . . . > L:0R 1

orric E . .

. p .. - . s.

u ..

SURNAME . .RDS11ver:sjh esland iggs Ziemann

. DJSkobholt

, , , , , 11/13/72 11/13/72 11/13/72 Fem AEC 318 (Rev. 9-88) AECM 0240 11//Y/72 11/h...72 'f M