ML20071K705
ML20071K705 | |
Person / Time | |
---|---|
Site: | LaSalle ![]() |
Issue date: | 07/06/1982 |
From: | COMMONWEALTH EDISON CO. |
To: | |
Shared Package | |
ML20071K493 | List: |
References | |
NUDOCS 8208020179 | |
Download: ML20071K705 (1) | |
Similar Documents at LaSalle | |
---|---|
Category:NPDES NONCOMPLIANCE NOTIFICATION
MONTHYEARML20202B8601986-06-25025 June 1986
[Table view]NPDES Noncompliance Notification:On 860531,3.7 Ppm Total Iron for Cooling Pond Blowdown Detected,Exceeding 2 Ppm 30-day Average Limit.Caused by 5.8-ppm Discharge on 860506. Request for Limits on Individual Wastestreams Submitted ML20211H3931986-06-12012 June 1986 NPDES Noncompliance Notification:On 860514,sewage Treatment Plant Influent Flow Exceeded Capacity of Polishing Pond. Caused by Backup Pump Having No Flow Control Capability. Pump Repaired & Pond Cleaned ML20199B0641986-06-0303 June 1986 NPDES Noncompliance Notification:On 860506,cooling Pond Blowdown Contained Total Iron Concentration of 5.8 Ppm. Caused by Heavy Precipitation.Total Iron Monitoring Requirement & Limit on Pond Blow Requested for Deletion ML20136C5811985-12-20020 December 1985 NPDES Noncompliance Notification:On 851112 & 30,total Iron Limit Exceeded.Caused by Heavy Rainfall ML20137R0981985-11-18018 November 1985 NPDES Noncompliance Notification:On 851031,30-day Average Limit Exceeded Due to Discharge of 39 Ppm Total Suspended Solids.Caused by High Flowrate Discharging Accumulation. Discharges Will Be Done at Low Flowrate ML20137X8161985-11-14014 November 1985 NPDES Noncompliance Notification:On 851011,30-day Average Total Suspended Solids Exceeded Due to Broken Backwash Nozzle on Media Filter B.Filter Repaired & Placed in Svc Even Though Station Short of Anthracite Coal ML20137A1071985-11-0808 November 1985 NPDES Noncompliance Notification:On 851011,39 Ppm Total Suspended Solids Discharged to Cooling Lake at High Flow Rate.Investigation Underway.Waste Neutralization Tanks Will Be Discharged to Cooling Lake at Low Flow Rate ML20137D6281985-11-0606 November 1985 NPDES Noncompliance Notification:On 851011,media Filter B Backwash Nozzle Discovered Broken & Filtering Medium Drained Into Clearwell,Underdrains & Effluent Chamber.Cause Not Stated.Nozzle Replaced & Anthracite Coal Added to Filter ML20137A1951985-11-0606 November 1985 NPDES Noncompliance Notification:On 851015,large Vol of Oil Entered & Overloaded Wastewater Treatment Sys.Caused by Oil Boom in Effluent Compartment Trapping Sheen of Oil in Vicinity Where Oil & Grease Obtained ML20137A0671985-11-0101 November 1985 Supplemented NPDES Noncompliance Notification:On 850909,23 & 30,oil Admitted to Wastewater Treatment Process.Caused by Excessive Sludge in Oil Separator Inlet Bays.Media Filter a Changed Out ML20137Z5371985-09-27027 September 1985 NPDES Noncompliance Notification:On 850831,30-day Average Limit Exceeded Due to One Discharge Which Contained 28 Ppm Total Suspended Solids.Composite Sampler Repaired ML20134Q1491985-08-28028 August 1985 Supplementary NPDES Noncompliance Notification:On 850703, Determined That Large Input of Oil Overloaded Waste Water Treatment Oil Separator.Caused by Oil Absorbent Boom Trapping Oil.Boom Replaced & Repositioned ML20134P7241985-08-27027 August 1985 NPDES Noncompliance Notification:On 850730,large Input of Oil Overloaded Wastewater Treatment Sys.Source of Oil Undetermined.Suspected Causes Include Polymer & Oil Separator Weir Sys.Sys Isolated & Cleaned ML20134P7151985-07-29029 July 1985 NPDES Noncompliance Notification:On 850703,large Vol of Oil Entered Wastewater Treatment Sys & Overloaded Facility. Source of Oil & Grease Unknown.Oil & Grease Pumped Out of Clarifiers & Oil Separator Pits.Absorbent Booms Replaced ML20134P6931985-07-29029 July 1985 NPDES Noncompliance Notification:On 850701,30-day Average for Total Suspended Solids Was 45 Ppm,Exceeding Limit of 15 Ppm.Caused by Discharge Containing 80 Ppm Total Suspended Solids.Regenerative Waste Solution Discharge Tanks Cleaned ML20129C5941985-06-19019 June 1985 NPDES Noncompliance Notification:On 850604,Regenerative Wastes Solution Discharge 001(a) Grab Sample Registered Ph of 9.18 & 80 Ppm Total Suspended Solids,Exceeding Limits. Caused by Inadequate Mixing ML20129B7131985-06-19019 June 1985 NPDES Noncompliance Notification:On 850603,Wastewater Treatment Facility 001(c) Effluent Registered Ph of 10.2, Exceeding Limit of 9.0.Sample Believed Unrepresentative Due to Inadequate Mixing ML20115H2611985-04-0909 April 1985 NPDES Noncompliance Notification:On 850314,free Residual Chlorine Concentration Greater than 2 Ppm Measured Every Day During Wk of 850311.Caused by Insufficient Contact Time Between Sewage Plant Effluent & Chlorine Disinfectant ML20093K7761984-10-0909 October 1984 NPDES Noncompliance Notification:On 840812,high Ph Excursion Occurred.Cause Unknown.Discharge Stopped.Clearwell Circulated Back to Equalization Tank & Neutralized.Discharge Continued ML20093D1931984-06-19019 June 1984 NPDES Noncompliance Notification:On 840530,sample of Mud Clean Sump Contained Ph Level of 11.2 Su,Exceeding Permit Limit of 9.0 Su.Sump Identified as Source of High Ph Water. Original Source Unknown.Discharge Stopped.Rept Encl ML20080L5201983-09-21021 September 1983 NPDES Noncompliance Notification:On 830823,total Suspended Solids Concentration Exceeded NPDES Permit Limits.Caused by Running of Equalization Tank Mixer Prior to Composite Sample Collection.Use of Mixer Will Be Monitored ML20071G6841983-05-12012 May 1983 NPDES Noncompliance Notification:Between 830411-17,composite Sample & Analysis Not Performed.Caused by Personnel Error. Personnel to Be Instructed on Proper Setup of Composite Sampler ML20073F7821983-04-0808 April 1983 NPDES Noncompliance Notification:On 830311,regeneration Wastes Solution Discharge Tanks Discharged 8.3 mg/1 Iron. Caused by Waste from Unit 2 Condensate Polishing Sys Regeneration.Mod Implemented on 830321 ML20072P4771983-03-23023 March 1983 NPDES Noncompliance Notification:On 830228,total Iron in Low Vol Waste Radwaste Discharge Tank Was 2.7 mg/1.Caused by Problems W/Owz Common Evaporator.Investigation Underway ML20072P4981983-03-22022 March 1983 NPDES Noncompliance Notification:On 830228,cooling Pond Blowdown Total Suspended Solids Were 21 mg/1 Above Background.Cause Unknown.No Corrective Action Taken ML20072P4961983-03-22022 March 1983 NPDES Noncompliance Notification:On 830224,low Vol Waste Radwaste Discharge Tanks Had 30 mg/1 Oil & Grease.Caused by Oil from Laundry Drain Collector Tanks.Oil Will Be Removed. Investigation Underway ML20072C2301983-02-25025 February 1983 NPDES Noncompliance Notification:On 830201,Outfall 001c Low Vol Waste Wastewater Treatment Facility Effluent Had Measured Activity of 1.6 Mg Per Liter of Total Iron, Exceeding 1 Mg Limit.Caused by Alum Pump Malfunction ML20071A2111983-02-0707 February 1983 NPDES Noncompliance Notification:On 830118,incident Caused by Wastes from Unit 2 Condensate Polishing Sys Regeneration & Buildup of Solids in Discharge Tank.Mod Initiated to Provide Option for Treatment of Tanks ML20070T2481983-01-11011 January 1983 NPDES Noncompliance Notification:On 830103,increase in Iron Discovered in Waste Solidification Discharge Tank. Caused by Wastes from Condensate Polishing Sys Regeneration & Buildup of Solids in Discharge Tank.Mod Initiated ML20064G1621983-01-0404 January 1983 NPDES Noncompliance Notification:On 821222,analysis Results for 821206-12 Discovered Missing.Caused by Technician Misplacing Results.Results Reportedly within Permit Spec. Administrative Effort Being Made to Comply W/Program ML20023B2591982-12-13013 December 1982 NPDES Noncompliance Rept:On 821116,emulsified Oil in Equalization Tank Reduced Flocculation & Filtration Efficiency.Cause Not Stated.Plant Discharge Stopped & All Treated Water Returned to Equalization Tank ML20064G2901982-12-10010 December 1982 NPDES Noncompliance Notification:On 821124,total Suspended Solids & Total Iron Exceeded Limits.Caused by Addition to Tank of Const Wastes from Condensate Polishing Sys.Mod for Optional Treatment of Tanks Initiated ML20070E3311982-11-24024 November 1982 NPDES Noncompliance Notification:On 821112,discharge from Low Vol Waste Wastewater Treatment Facility Contained 115.6 Mg/L Oil & Grease.Cause Not Stated.Discharge Stopped, Tank Taken Out of Svc & Oil Soak Bags Placed in Tank ML20067C9171982-11-13013 November 1982 NPDES Noncompliance Notification:On 821105,temporary Hydrogen Peroxide Sys Not Injecting Hydrogen Peroxide. Injection Pump Repaired ML20066K5771982-11-12012 November 1982 NPDES Noncompliance notification:58,330 Gallons of 25.3 Mg Iron Concentration Waste Discharged on 821020.Caused by Addition of Const Wastes.Mod Initiated to Provide Option for Treatment of Tanks ML20069N1511982-11-12012 November 1982 NPDES Noncompliance Notification:On 821029,iron Concentrations of 41.3 Mg Found in Regenerated Waste Solids Discharge Tank.Caused by Addition of Const Wastes from Unit 2 Condensate Polishing Sys.Treatment Mod Initiated ML20066A9131982-10-25025 October 1982 NPDES Noncompliance Notification:On 820920,total Iron in Outfall 001c Low Vol Waste Radwaste Discharge Tanks Exceeded Allowable Limit.Cause Unknown.Present Treatment by Evaporation Provides Treatment Efficiently ML20023A7691982-09-29029 September 1982 NPDES Noncompliance Notification:On 820914,buildup of Resin Fines & Other Fine Solids Carried Through Strainers & Sumps Into Discharge Tank.Cause Not Stated.Regenerative Waste Solution Discharge Tank Will Be Cleaned ML20069H3141982-09-29029 September 1982 NPDES Noncompliance Notification:On 820910,oil & Grease in Outfall 001c Low Vol Waste Radwaste Discharge Tanks Exceeded Allowable Limit.Caused by Mechanical Failure of Radwaste Evaporator Resulting in Poor Quality Water ML20023A7221982-09-29029 September 1982 NPDES Noncompliance Notification:On 820909,total Iron at Outfall 001c Low Vol Waste Wastewater Treatment Facility Exceeded Allowable Limit.Caused by Upset Ph Due to Unit 2 Const Activities.Work Request Initiated to Install Monitor ML20065L6051982-09-29029 September 1982 NPDES Noncompliance Notification:On 820913,pH at Outfall 001c Low Vol Waste Wastewater Treatment Facility Fell Out of Specs.Caused by Acid Waste Generated from Unit 2 Const Activities.Work Request Initiated to Install Ph Monitor ML20065L5921982-09-29029 September 1982 NPDES Noncompliance Notification:On 820903,total Iron in Outfall 001c Low Vol Waste Regeneration Wastes Solution Discharge Tank Exceeded Allowable Limit.Caused by Temporary Hydrogen Peroxide Sys Not Operating Properly ML20065L5571982-09-29029 September 1982 NPDES Noncompliance Notification:On 820801,total Suspended Solids & Iron in Outfall 001c Low Vol Waste Radwaste Discharge Tanks Exceeded Allowable Limits.Caused by Mechanical Problems W/Radwaste Evaporators ML20069H3511982-09-29029 September 1982 NPDES Noncompliance Notification:On 820914,total Suspended Solids & Iron at Outfall 001c Low Vol Waste Wastewater Treatment Facility Exceeded Allowable Limits.Caused by Upset Ph Due to Unit 2 Const Activities ML20066A5791982-09-24024 September 1982 NPDES Noncompliance Notification:On 820924,tank Sampled to Verify Neutralization Prior to Discharge.Second & Third Samplings Revealed Ph Change.Error in Sampling or Analysis Suspected.Flush Time Reviewed ML20064N5431982-08-30030 August 1982 NPDES Noncompliance Notification:On 820803,effluent Water Quality Exceeded Permit Limit.Caused by Alum Skid Shutdown, Resulting in Improper Floculation.Alum Skid Restarted ML20071L1411982-07-14014 July 1982 NPDES Noncompliance Notification:On 820612,15 & 29,total Iron from Discharges Exceeded Permitted Limits.Caused by Temporary Hydrogen Peroxide Injection Sys Becoming air- Bound.Permanent Injection Sys Completion Expected by 830101 ML20071K7011982-07-14014 July 1982 NPDES Noncompliance Rept:On 820629,excessive Amounts of Soluble Iron Collected on Makeup Demineralizers.Caused by Loss of Hydrogen Peroxide Injection from Temporary Sys. Permanent Hydrogen Peroxide Injection Sys Will Be Installed ML20071L1731982-07-12012 July 1982 NPDES Noncompliance Notification:On 820712,18 Mg Per Liter Oil & Grease Released from Wastewater Treatment Facility. Error in Sampling suspected.Oil-soak Boom Placed in Outlet Chamber to Prevent Discharge ML20058G8891982-07-0606 July 1982 NPDES Noncompliance Notification:On 820703,composite Sample Initiated on Batch Discharge 001-82,batch Discharge 002-82 Commenced W/O Stopping Composite Sample Between Batches. Composite Sampler Cannot Operate Automatically 1986-06-03 Category:TEXT-ENVIRONMENTAL REPORTS MONTHYEARML20206K1951998-12-31031 December 1998
[Table view]Annual Exposure Rept of Number of Personnel & Person-Rem by Work & Job Function for 1998 for LaSalle County ML20206D5981998-12-31031 December 1998 Annual Environ Operating Rept for 1998 for Environ Protection Plan, for LaSalle County Station,Units 1 & 2 ML20206F1001998-12-31031 December 1998 Effluent & Waste Disposal Semi-Annual Rept for 1998 ML20206D9131998-12-31031 December 1998 County Station Annual Radiological Environ Operating Rept,1998. with ML20217J2311997-12-31031 December 1997 County Station Environ Protection Plan 1997 Annual Operating Rept ML20217M2071997-12-31031 December 1997 1997 Annual Radiological Environ Operating Rept, for LaSalle County Station ML20203K7251997-12-31031 December 1997 1997 Occupational Radiation Exposures, for Dresden,Zion, Lasalle,Byron & Braidwood Plant ML20135D8931996-12-31031 December 1996 Effluent & Waste Disposal Semi-Annual Rept Jul-Dec 1996 ML20138C7011996-12-31031 December 1996 County Station Environ Protection Plan 1996 Annual Operating Rept ML20217Q5021996-12-31031 December 1996 Addendum to 1996 Radiological Environ Operating Rept, for LaSalle County Station,Units 1 & 2 ML20148A6721996-12-31031 December 1996 Recorded Annual TEDE Exposure for CY96 for Braidwood,Byron, Dresden,Lasalle,Quad Cities & Zion ML20138C8361996-12-31031 December 1996 County Station Annual Radiological Environ Operating Rept for 1996 ML20117G4321996-08-21021 August 1996 Effluent & Waste Disposal Semi-Annual Rept (1996) Gaseous Effluents-Elevated Release for Units 1 & 2 ML20134B8791996-06-30030 June 1996 Effluent & Waste Disposal Semi-Annual Rept for 1996 Gaseous Effluents-Summation of All Releases for Period Jan-June 1996 ML20108D0211995-12-31031 December 1995 County Station Environ Protection Plan 1995 Annual Operating Rept ML20107K8001995-12-31031 December 1995 County Station Annual Radiological Environ Operating Rept 1995 ML20100J4731995-12-31031 December 1995 Effluent & Waste Disposal Semiannual Rept Jul-Dec 1995. W/ ML20082Q7661994-12-31031 December 1994 County Station Annual Radiological Environ Operating Rept 1994 ML20087H6331994-12-31031 December 1994 County Station Environ Protection Plan 1994 Annual Operating Rept ML20080J8341994-12-31031 December 1994 Effluent & Waste Disposal Semi-Annual Rept for Jul-Dec 1994 ML20086C5141994-06-30030 June 1994 Effluent & Waste Disposal Semi-Annual Rept (1994),from Jan-Jun 1994 ML20063L5581993-12-31031 December 1993 Effluent & Waste Disposal Semiannual Rept Jul-Dec 1993 for LaSalle County Nuclear Station ML20029D8471993-12-31031 December 1993 County Station Environ Protection Plan 1993 Annual Operating Rept. W/940428 Ltr ML20059A7191993-12-23023 December 1993 EAP Supporting Proposed Amends to Revise Limitations on Radioactive Materials Released in Liquid & Gaseous Effluents & Revise 10CFR20 to Recognize New Section Numbers ML20128L6161993-02-12012 February 1993 Environ Assessment Supporting Util 920605 Request to Expand Capacity of Unit 1 Spent Fuel Pool ML20044E3631992-12-31031 December 1992 Annual Radiological Environ Operating Rept,1992. W/930413 Ltr ML20046C2101992-12-31031 December 1992 Errata to LaSalle Nuclear Power Station,Units 1 & 2 Annual Environ Operating Rept ML20114C1081992-06-30030 June 1992 Effluent & Waste Disposal Semiannual Rept,Jan-June 1992 ML20095H7801991-12-31031 December 1991 County Station Annual Radiological Environ Operating Rept,1991 ML20090E4101991-12-31031 December 1991 1991 Occupational Radiation Exposures for LaSalle Nuclear Power Station ML20073D0011990-12-31031 December 1990 Annual Radiological Environ Operating Rept 1990 ML20012A2781989-12-31031 December 1989 Effluent & Waste Disposal Semiannual Rept for Jul-Dec 1989. W/900220 Ltr ML20042F1721989-12-31031 December 1989 Environ Protection Plan,1989 Annual Operating Rept. W/900425 Ltr ML20042E8321989-12-31031 December 1989 Annual Environ Radiological Operating Rept 1989. W/900423 Ltr ML20246H9891989-06-30030 June 1989 Effluent & Waste Disposal Semiannual Rept Jan-June 1989 ML20235Y8771988-12-31031 December 1988 Occupational Personnel Radiation Doses Rept for 1988 ML20151Y4791988-06-30030 June 1988 Effluent & Waste Disposal Semiannual Rept (1988) ML20151A9671988-03-25025 March 1988 Environ Protection Plan Annual Operating Rept for 1987 ML20147C5911987-12-31031 December 1987 Effluent & Waste Disposal Semiannual Rept,June-Dec 1987 ML20196G4041987-12-31031 December 1987 1987 Rept of Occupational Personnel Radiation Doses. W/ ML20153C6391987-12-31031 December 1987 Radwaste & Environ Monitoring Annual Rept 1987 ML20196C2681986-12-31031 December 1986 Errata to Effluent & Waste Disposal Annual Rept for 1986 ML20202B8601986-06-25025 June 1986 NPDES Noncompliance Notification:On 860531,3.7 Ppm Total Iron for Cooling Pond Blowdown Detected,Exceeding 2 Ppm 30-day Average Limit.Caused by 5.8-ppm Discharge on 860506. Request for Limits on Individual Wastestreams Submitted ML20211H3931986-06-12012 June 1986 NPDES Noncompliance Notification:On 860514,sewage Treatment Plant Influent Flow Exceeded Capacity of Polishing Pond. Caused by Backup Pump Having No Flow Control Capability. Pump Repaired & Pond Cleaned ML20199B3761986-06-10010 June 1986 Radioactivity Measurements Attributed to Chernobyl Nuclear Plant Accident ML20199B0641986-06-0303 June 1986 NPDES Noncompliance Notification:On 860506,cooling Pond Blowdown Contained Total Iron Concentration of 5.8 Ppm. Caused by Heavy Precipitation.Total Iron Monitoring Requirement & Limit on Pond Blow Requested for Deletion ML20205N3361986-04-23023 April 1986 Environ Protection Plan Annual Operating Rept for 1985 ML20203J8141986-04-23023 April 1986 Environ Protection Plan Annual Operating Rept for 1985 ML20205N6881986-01-16016 January 1986 Results of Foliar Survey of LaSalle County Generating Station for Rime Ice Deposition Damage ML20205N6841985-12-31031 December 1985 Operational Fog & Ice Observation Program Data Summary for Fourth Quarter 1985 1998-12-31 |
Text
, .
o .
4 LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO: ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NLHBER AND DESCRIPTION: NA PARAMETER AND PERMIT LIMIT: 0I1, None VisibIe NONCOMPLIANCE, DATE, AND DURATION: Oil Spill to Cooling Lake, 6JUL82, unknown CAUSE OF NONCOMPLIANCE:
A line break f rom the fuel oil storage tank to the diesel fire pumps allowed approximately 300 gallons to spill onto the Lake Screen House floor. Approximately 75 gallons of fuel oil was recovered f rom the floor, 220 gallons was contained in the oil s'eparator, and from 1 to 5 gallons was determined to have been discharged to the Circulating Pump 1C forebay at the Lake Screen House. Suction for the circulating pump is off of the bottom of the foretiay. Investigation has shown '
all fuel oil spilt to the forebay was contained in the forebay. No fuel oil was discharged to the Cooling Lake proper. L CORRECTIVE ACTION:
The broken line is under repair. Station personnel were notified to clean up the spilled fuel oil f rom the Lake Screen House and oil separator. Maintenance personnel removed the fuel oil that reached the ci rculating pump forebay area.
l 6JUL82 DATE RECOGNIZED,A_S,A VIOLATION:
6JUL82 l
DATE INVESTIGATED: