ML20137R098

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 851031,30-day Average Limit Exceeded Due to Discharge of 39 Ppm Total Suspended Solids.Caused by High Flowrate Discharging Accumulation. Discharges Will Be Done at Low Flowrate
ML20137R098
Person / Time
Site: LaSalle, 05003738  
Issue date: 11/18/1985
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8512050425
Download: ML20137R098 (3)


Text

y pgg3 7--

/

) LaSill.a County Nucl ar Station

}i lg@h ng l

] RurilRout2 #1. Box 220

(

'/

Marseilles, Illinois 61341 i

.y

""/ Telephone 815/357-6761 g-iT

.(f, s h s

,. a 4 -

4 ' %;- f, w-4,-;

N g

November 18, 1985 Mr. James G. Keppler Regional Administrator Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 6013T

Dear Mr. Keppler:

In accordance with LaSalle County Station Unit 1 and Unit 2 Facility Operating License NPF-11 and NPF-18, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliance for InSalle County Nuclear Generating Station Permit No. ILO0h8151.

e.o. #4

[ G. J. Diederich Station Manager InSalle County Station GJD/LRA/RHK/kg Enclosure xc: NRC Resident Inspector INPO - Records Center US NRC Document Control Desk l'u

%gI 8512050425 851118 PDR ADOCK 0S000373 NOV 2 51985 6

S PDR w

.._?.

[D C:mm:nwealth Edison

) Ruta! Route +1. Bcx 220

+

Lasane Counw Nxic.v Sta' ion f

<u2 g

Marseines, Illinois 61341 Telephone 815/357 6761 November 1. 1985 U. S. Environmental Protection Agency Region V. Enforcement Division i

ATTN: Chief. Compliance Unit 230 South Dearborn Street Chicago, IL 60604 Illinois Environmental Protection Agency

)

Division of Water Pollution Control Compliance Management Unit 2200 Churchill Road Springfield. IL 62706

Dear Sir:

subject:

NPDES Woncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151 i

1 In accordance with Standard condition 12, we wish to submit the following notice of noncompliances which are listed on the attached table.

If there are any questions please contact Steve Davis of my staff at (815) 357-6761, extension 487.

.1 4

G. J. Diederi h Station Manager GJD/LRA/RHK/sjc sc: Director of Water Quality. Environmental Affairs j

Manager. Nuclear Stations Division i

DOCUMENT ID 0070h/0250A

>e o

LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. pBRMIT NO:

ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION: 001(a) Demineralizer Regenerant Wastes PARAMETER AND PERMIT LIMIT:

Total Suspended Solids 15 ppm 30-day average.

NONCOMPLIANCE. DATE. AND DURATION:

39 ppe Total Suspended Solids. 31 Oct 85. 30-day average CAUSE OF NONCOMPLIANCE:

The 30-day average limit was exceeded because of one discharge which contained 39 ppe total suspended solids.

(This occurrence was reported in a noncompliance report submitted 15 Oct 85). A grab sample collected prior to discharge indicated the tank met NPDES discharge limits.

It was suspected that solids from low flowrate (< 100 GPM) discharges to the j

Wastewater Treatment System accumulated in the lowpoint of the discharge piping and that higher flowrate (> 500 GPM) discharges to the cooling lake dislodges the accumulated solids, thus creating a solids excursion.

CORRECTIVE ACTION:

Investigation into the problem concluded that discharges to the lake will be done only at a low flowrate (< 100 GPM). A caution card was hung on crosstie valve OWM213 to ensure this.

The standstill acid sump will be cleaned. Also, any solids on the floor in areas which drain to the acid sump will be cleaned.

DATE RECOGNIZED AS A VIOLATION:

'jlCCT85 DATE INVESTIGATED:

3'lOCT85 m

.~

/t

.x a

.9-

+

,r DOCUMENT ID 0070h/0250A

,%..