LRP-1110-3' Revision 4 NovembSr l9, 1987 i
3 s
ATTACHMENT A LASALLE COUNTY NUCLEAR POWER STATION UNITS ONE AND TWO s
DOCKET NUMBERS $0-373 AND 50-374 EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1987)
GASEOUS EFFLUENTS-SUMMATION OF ALL RELEASES Third Fourth Quarter
-Quarter A.
' Fission and Activation Gases 1.
Total release ci 4.14E+03 2.35E+03 2.
Average release rate for period uci/sec.
1.97E+02 1.04E+02 3.
Percent of Tech. Spec. limit s
1.48E+00 5.30E-01 B.
Iodint; 1.
Total iodine-131 Ci 9.23E-04 3.53E-03 2.
Average release rate for period uCi/sec 2.77E-04 3.31E-04 3.
Percent of Tech. Spec. limit 1.58E+00 6.60E-01 C.
Particulates 1.
Particulates with T1/2 >8 days C1 2.62E-02 4.92E-03 2.
Average release rate for period uCi/sec 6.74E-03 2.94E-03 3.
Percent of Tech. Spec. limit 8.20E-01 3.00E 01 4.
Gross alpha radioactivity C1 3.78E-06
<1.00E-11 D.
Tritium 1.
Total release ci
<1.00E-06
<1.00E-06 2.
Average release rate for period uCi/sec 0.00E+00 0.00E+00 3.
Percent of Tech. Spec. Limit 0.00E+00 0.00E+00 e
"<" indicates activity of sample is less than LLD given in uCi/mi a
DOCUMENT ID 0655h/
-~~
Y;
' h osos\\D 371238 b
PDR ADet #- 85*CO373PbR
.h't g
r
_. ~.3,-
m
,:t-
~'
- ~
LRP-1110-3 Rsvision.4 Novambar 19, 1987 4
l I
E?,UENT AND WASTE DISPOSAL REPORT (1987)
GASEOU9 EFFLUENTS-ELEVATED RELEASE Third Nuclides Released July Aug.
Sept.
Quarter 1.
Fission cases
-AT-41 Ci 7.49E-0.
0.00E+00 7.80E+00 8.61E+00 Kr-85m Ci 4.17E+0L 2.50E+02 2.93E+02 5.85E+02 Kr-87 C f.
2.53E+01 1.02E+02 1.13E+02 2.41E+02 Kr-88 Ci 6.S6E+01 3.468+02 3.78E+02 7.93E+02 Xe-133 C1 2.05E+02 6.50E+02 7.97E+02 1.65E+03 Xe-133m Ci
<1.00E-06
<1.00E-06
<1.00E-03
<1.00E-06 Xe-135 C1 2.72E+00 8.63E+02 (1.00E-06 8.65E+02 Xe-138 Ci
<l.00E-06
<1.00E-06
<l.00E-06
<l.00E-06
' total for period C1 3.45E+02.
2.21E+03 1.59E+03 4.14E+03 2.
Iodines I-131 Ci 2.97E-04 2.598-04 3.678-04 9.23E-04 I-132 C1 1.34E-03 1.18E-03 6.66E-04 3.19E-03 I-133 Ci 3.018-03 2.07E-03 6.66E-03 1.17E-02 1-134 Ci 6.CSE-04
<1.00E-11 1.43E-03 2.04E-03 1-135 Ci 1.94E-03 9.13E-04 1.60E-03 4.46E-03 w
Total for period C1 7.19E-03 4.42R-03 1.07E-02 2.23E-02 3.
Particulates Mn-54 C1 4.13E-05 1.30E-05 6.218-05 1.16E-04 Co-58 Ci 1.09E-05
<1.00E-04
<1.00E-04 1.09E-05 Fe-59 Ci
<1.00E 04
<1.00E-04
<l.00E-04
<1.00E-04 Co-60 Ci 1.94E-04 2.56E-02 2.66E-04 2.60E-02 Zn-65 Ci
<1.00E-04
<1.00E-04
<l.00E-04
<l.00E-04 Sr-89 Ci
<1.00E-11 6.48E-06 3.94E-05 4.595-05 Sr-90 Ci 6.48E-06
<1.00E-11 2.16E-06 8.64R-06 Mo-99 Ci
<1.00E-04
<l.00E-04
<1.00E-04
<l.00E-04 Cs-134 Ci
<1.00E-04
<1.00E-04
<1.00E-04
<l.00E-04 Cs-137 Ci
<l.00E-04
<1.00E-04
<1.00E-04
<l.00E-04 Ce-141 Ci
<1.00E-04
<1.00E-04
<l.00E-04
<1.00E-04 Co-144 Ci
<1.00E-04
<l.00E-04
<l.00E-04
<l.00E-04 Total for period Ci 2.53E-04 2.56E-02 3.69E-04 2.628-02
"<" indicates activity of sample is less than LLD given in uci/ml l
DOCUMENT ID 0655h/
l
- +,
- P LRP-1110
- Revision 4 Novemb3r 19, 1987 4
EFFLUENT AND WASTE DISPOSAL REPORT (1987)
GASECUS EFFLUENTS-ELEVATED RELEASE Fourth Nuclides Released Oct.
Nov.
Dec.
Quarter 1.
Fission Gases Ar-41 Ci 6.69E+00 2.38E+00 0.00E+00 9.07E+00 Kr-85m C1 1.71E+02 5.478+0L 9.12E+01 3.17E+02 Kr-87 Ci
<1.00E-06.
<1.00E-06
<1.00E-06
<1.00E Kr-88 Ci-1.90Et02 3.42E+01 1.268+02 3.50E+02 Xe-133 Ci 9.64E+02 2.86E+02 4.19E+02 1.67E+03 Xe-133m Ci
<l.00E-06
<1.00E-06
<1.00E-06
<l.00E-06 Xe-135 Ci 9.00E-04
<l.00E-06
<1.00E-06 9.00E-04 Xe-138 Ci
<1.00E-06
<1.00E-06
<1.00E-06
<l.00E-06
.y Total for period C1 1.33E+03 3.778+02 6.36E+02
.2.35E+03 2.
Iodines 1-131 Ci 9.13E-04 2.19E-03 4.26E-04 3.53E-03 1-132 Ci 7.14E-03 6.60E-03 3.65E-03 1.74E-02 1-133 Ci 7.13E-03 5.52E-03 3.99E-03
.l.66E-02 1-134 Ci 3,80E-03 8.47E-04
<1.00E-11 4.65E-03 I-135 Ci 1.08E-02 5.04E-03 4.26E-03 2.01E-02 Total for period C1 2.98E-02 2.02E-02 1.23E-02 6.23E-02
~ 3.
Particulates Cr-51 Ci 4.22E-04 4.32E-04 0.00E+00 8.54E-04 Mn-54 Ci 5.51E-05 7.00E-04 2.50E-05 7.80E-04 Co-58 Ci
<1.00E-04 3.89E-05
<l.00E-04 3.89E-05 1
Fe-59 Ci
<1.00E-04
<1.00E-04
<1.00E-04
<1.00E-04 Co-60 C1 2.28E-04 2.82E-03 2.04E-04 3.25E-03 Zn-65 Ci
<l.00E-04
<1.00E-04
<1.00E-04
<1.00E-04 Sr-89 Ci
<1.00E-11
<1.00E-11
<l.00E-11
<1.00E-11 Sr-90 Ci
<1.00E-11
<l.00E-11
<1.00E-11
<l.00E-11 Mo-99 Ci
<1.00E-04
<1.00E-04
<1.00E-04
<1.00E-04 Cs-134 Ci
<1.00E-04
<1.00E-04
<1.00E-04
<1.00E-04 Cs-137 Ci
<l.00E-04
<1.00E-04
<1.00E-04
<1.00E-04 Ce-141 Ci
<1.00E-04
<1.00E-04
<l.00E-04
<1.00E-04 Ce-144 Ci
<1.00E-04
<l.00E-04
<1.00E-04
<1.00E-04 Total for period Ci 7.05E-04 3.99E-03 2.298-04 4.92E-03
"<" indicates activity of sample is less than LLD given in uCi/mi DOCUMENT ID 0655h/
r p------
-e a-u---
-me.
--,w,,---%.--
-imm--w,y-,,y.,y--*wnv3---mee--geq.*
t mt---ee7-'*-+W-u-**--^'7
-'- - --**=wr'v-wv=
c.
LRP-1110-3 e.
Revision 4 Novemb3r 19, 1987 5
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1987)
LIQUID EFFLUENTS-SUMMATION OF ALL RELEASES Third Fourth Quarter Quarter A.
Fission and Activation Gases 1.
Total release'(not including Ci 6.20E-02
- 7. 90 E- 01 tritium, gases, alpha) 2.
Average concentration released uci/sec 6.21E-06 6.06E-05 3.
Maximum concentration released uCi/sec 8.10E-05 1.50E-03 4.
Percent of Tech. Spec. limit 2.85E-06 3.03E-05 B.
Tritium 1.
Total release Ci 3.62E-01 5.94E-01 2.
Average concentration released uCi/mi 3.70E-04 3.13E-04 3.
Percent of Tech. Spec. 10mit i
1.86E-05 1.48E-04 C.
Dissolved Noble Gases 1.
Total release ci 0.00E+00 0.00E+00 2.
Average concentration released uCi/ml
<1.00E-05
<1.00E-05 3.
Percent of Tech. Spec. Ilmit 0.00E+00 0.00E400 D.
Gross Alpha Radioactivity 1.
Total release ci 3.06E-06 5.19E-06 2.
Average concentration released uC1/ml 2.588-09 2.60E-09 E.
Volume of Waste Released liters 1.18E+06 2.02E+06 F.
Volume of Dilution Water liters 2.16E+09 6.068+08
"<" indicates activity of sample is less tnan LLD given in uCi/ml DOCUMENT ID 0655h/
-- _, _ _ _ = _,
LRP-1110-3 Rsvision 4-Novembst 19, 1987 6
EFFLUENT AND WASTE DISPOSAL REPORT (1987)
LIQUID EFFLUENTS Third Nuclides Released July Aug.
Sept.
Quarter Na-24 C1 1.10E-05 0.00E+00 No 1.10E-05 Cr-51 Ci 1.59E-02 2.20E-02 Releases 3.79E-02 Mn-54 Ci 2.23E-03 3.348-03 5.57E-03 Fe-55 C1 3.90E-04 8.87E-04 1.28E-03 Co-58 Ci 5.36E-04 8.49E-04 1.398-03 Fe-59 Ci
<5.00E-07 3.16E-04 3.16E-04 Co-60 Ci 6.73E-03 8.62E-03 1.54E-02 Zn-65 Ci 7.90E-05 1.16E-04 1.95E-04 Sr-89 C1 1.55E-06 4.68E-06 6.23E-06 St-90 Ci 6.70E-07 1.01E-06 1.68E-06 Mo-99 Ci
<5.00E-07
<5.00E-07
<5.00E-07 I-131 Ci
<1.00E-06
<1.00E-06
<1.00E-06 Xe-133 Ci
<1.00E-05
<1.00E-05
<1.00E-05 Xe-133m Ci
<1.00E-05
<1.00E-05
<1.00E-05 Cs-134 Ci
<5.00E-07
<5.00E-07
<5.00E-07 Xe-135 Ci
<1.00E-05
<1.00E-05
<1.00E-05 Cs-137 Ci
<5.00E-07
<5.00E-07
<5.00E-07 Ce-141 Ci
<5.00E-07
<5.00E-07
<5.00E-07 Ce-144 Ci
<5.00E-07
<5.00E-07
<5.00E-07 Total for period Ci 2.59E-02 3.61E-02 0.00E+00 6.20E-02
"<" indicates activity of sample is less than LLD given in uCi/ml l
I DOCUMENT ID 0655h/
i i
I
,n
-n,,
, e en
'LRP-1110-3 Ravlsion 4 NovimbLr 19, 1987 6
EFFLUENT AND WASTE DISPOSAL REPORT (1987)
LIQUID EFFLUENTS Fourth Nuclides Released Oct.
Nov.
Dec.
Quarter Na-24 Ci
'2.79E-03 No 1.548-03 4.33E-03 Cr-51 C1 1.92E-01 Releases 4.38E-01 6.30E-01 Mn-54 Ci 2.57E-02 1.55E-02 4.12E-02 Fe-55 C1 1.69E-03 4.84E-04 2.17E-03 Co-58 Ci 6.67E-03 2.868-03 9.63E-03 Fe-59 C1 2.84E-04 1.00E-03 1.25E-03 Co-60 Ci 7.33E-02 1.848-02 9.17E-02 Zn-65 Ci 3.91E-03 3.05E-03 6.96E-03 St-89 Ci 9.32E-06 2.22E-06 1.54E-05 Sr-90 Ci 2.19E-06 6.64E-07 2.85E-06 Nb-95 Ci 0.00E+00 7.10E-05 7.10E-05 Mo-99 C1 3.89E-05
<5.00E-07 3.89E-05 Tc-99m Ci 0.00E+00 1.15E-05 1.15E-05 Ag-110m C1 3.47E-04 7.088-04 1.05E-03 1-131 Ci
<1.00E-06 1.10E-03 1.10E-03 l
I-133 Ci 5.67E-05 0.00E+00 5.67E-05 Xe-133 Ci
<l.00E-05
<1.00E-05
<1.00E-05 Xe-133m Ci
<l.00E-05
<l.00E-05
<l.00E-05 Cs-134 Ci
<5.00E-07 1.03E-04 1.03E-04 Xe-135 Ci
<1.00E-05
<1.00E-05
<l.00E-05 Cs-136 Ci 0.00E+00 1.84E-04 1.84E-04 Cs-137 Ci 2.38E-05 2.31E-04 2.54E-04 Ce-141 Ci
<5.00E-07
<5.00E-07
<5.00E-07 Ce-144 Ci
<5.00E-07
<5.00E-07
<5.00E-07 Total for period C1 3.078-01 0.00E+00 4.83E-01 7.90E-01
"<" indicates activity of sample is less than LLD given in uci/ml DOCUMENT ID 0655h/
l
7-LRP-1110-3 Asvision 4 Novemb3r 19, 1987 7
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL f(EPORT (1987)
SOLID WASTE SHIPPED OFFSITE POR BURI7.L OR DISPOSAL Third July Aug.
Sept.
Quarter 1.
Spent resins, filter sludges evaporator bottoms, etc.
a.
Quantity shipped cu.m. 1.97E+01 7.00E+01 6.26E+01 1.52E+02 b.
Total activity C1 1.17E+02 5.70E+01 2.49E+02 4.23E+02 (measured) c.
Major nuclides (estimate)
Co-60 25 25 26 Fe-55 57 55 03 Mn-54 11 11 17 Cr-51 03 04 61 d.
Container volume cu.m. 3.94E+00 4.62E+00 4.62E+00 2.128-01 3.29E-01 2.12E-01 f.
Solidification agent Cement Cement Cement 2.
Dry compressible waste, contaminated equipment, etc.
a.
Quantity shipped cu.m. 7.39E+01 3.62E+01 1.71E+01 1.27E+02 b.
Total activity C1 1.69E+00 8.21E-01 4.89E-01 3.00E+00 (measured) c.
Major nuclides,(estimate)
Co-60 28 28 06 Fe-55 04 03 35 Mn-54 28 28 06 Cr-51 15 16 35 d.
Container volume cu.m. 1.90E+01 2.72E+00 2.72E+00 2.72E+00 2.12E-01 3.29E-01 2.12E-01 2.12E-01 DOCUMENT ID 0655h/
~
LRP-1110 3 '
Revision 4 Novemb3r 19, 1987
?.
7 EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1987)
SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL Fourth-Oct.
Nov.
'Dec.
Quarter-1.
Spent resins, filter sludges evaporator bottoms, etc.
a.
Quantity shipped cu.m. 7.21E+01 6.14E+01 6.89E+01 2.02E+02 b.
Total-activity C1 2.20E+02 3.24E+02 1.36E+02 6.30E+02 (measured)-
c.
Major nuclides (estimate)
Co-60 25 05 25 Co-58 03 23 02 Fe-55 55 08 55 Mn-54 11 43 11 d.
Container volume cu.m. 4.62E+00 4.62E+00 4.62E+00 3.29E-01 3.29E-01 3.29E-01 2.12E-01 2.128-01 2.12E-01 f.
Solidification agent Cement Cement Cement 2.
Dry compressible waste, contaminated equipment, etc.
i a.
Quantity shipped cu.a. 0.00E+00 0.00E+00 1.95E+01 1.95E+01 b.
Total activity Ci 0.00E+00 0.00E+00 3.15E-02 3.15E-02 (measured) c.
Major nuclides.(er,timatel Co-60 N/A N/A 28 Mn-54
's N/A N/A 28 Cr-51 N/A N/A 16 d.
Container type N/A N/A LSA e.
Container volume cu.m. N/A N/A 2.12E-01 DOCUMENT ID 0655h/
f-?s
.LRP-ll10-3 4
R3 vision'4
~
November 19, 1987
- a 8
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1987)
OOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL 3.
Solid waste disposition Date Transport Company Destinacion 07/16/87 HN Beatty, NV 07/31/87 HN Beatty, NV 07/22/87 HN Beatty, NV 07/27/87 HN Beatty, NV 07/03/87 HN Beatty, NV 08/07/87 HH Barnwell, SC 08/10/87 HN Hanford, SC 08/19/87 TSMT Beatty, NV 08/19/87 TSMT Hanford, WA 08/20/87 TSMT Hanford, WA 08/13/87 HN Barnwell, SC 07/17/87 TSMT Waltz Mill, PA 07/21/87 TSMT Waltz Mill, PA 07/21/87 TSMT Hanford, WA 07/11/87 TSMT Hanford, WA 09/04/87 HN Barnwell, SC 08/25/87 HN Hanford, WA 08/28/87 HN Beatty, NV 08/27/87 TSMT Hanford, WA 08/31/87 HN Beatty, NV 09/02/87 HN Beatty, NV 09/03/87 HN Beatty, NV 09/04/87 HN Beatty, NV 09/09/87 HN Barnwell, SC 09/14/87 HN Barn' sell, SC 09/11/87 HN Hanford, WA 09/11/87 HN Beatty, NV 09/14/87 HN Beatty, NV 09/18/87 TSMT Beatty, NV 09/17/87 HN Beatty, NV 09/18/87 HN Beatty, NV 09/17/87 HN Barnwell, SC 09/20/87 HN Barnwell, SC 09/21/87 HN Beatty, NV Transport Company key CN = Chem Wuclear HN = Hittman Nuclear TSMT = Tri-State Motor Transport DOCUMENT ID 0655h/
LRP-il10-3 Ravision 4 a
Novtmber 19, 1987 i
8 3.
Solid waste disposition (continued)
Date Transport company Destination 09/25/87 HN Beatty, NV 09/22/87 HN Beatty, NV 09/22/87 HN Beatty, NV 09/24/87 HN Beatty, NV 09/28/87 HN Beatty, NV 09/29/87 HH Beatty, NV 10/01/87 HN Beatty, NV 10/01/87 HN Beatty, NV 10/05/87 HN Beatty, NV 10/02/87 HN Beatty, NV 10/06/87 HN Beatty, NV 10/06/87 HN Beatty, NV 10/07/87 hN Beatty, NV 10/08/87 HN Beatty, NV 10/08/87 MW Beatty, NV 10/09/87 HN Beatty, NV 10/09/87 HN Beatty, NV 10/13/87 HN Beatty, NV 10/13/87 HN Beatty, NV 10/14/87 HN Beatty, NV 10/15/87 HN Beatty, NV 10/15/87 HN Beatty, NV 10/16/87 HN Beatty, NV 10/23/87 HN Beatty, NV 10/23/87 HN Barnwell, SC 11/02/87 HN Barnwell, SC 10/27/87 HN Beatty, NV 10/30/87 HN Beatty, NV 11/05/87 HN Barnwell, SC 11/06/87 HN Barnwell, SC 11/06/87 HN Beatty, NV 11/10/87 HN Beatty, NV 11/10/87 HN Beatty, NV 11/12/87 HN Beatty, NV 11/12/87 HN Beatty, NV 11/16/87 HN Beatty, NV 11/16/87 HN Beatty, NV 11/18/87 HN Barnwell, SC Transport company Key CN = Chem Nuclear HN = Hittman Nuclear TSMT = Tri-State Motor Transport DOCUMENT ID 0655h/
LRP-1110-3 Revision 4 November 19, 1987 8
3.
Solid waste disposition (Continued)
D, ale Transport Company Destination 11/17/87 HN Beatty, NV 11/18/87 HN Beatty, NV 11/19/87 HN Beatty, NV 11/20/87 HN Barnwell, NV 11/20/87 HN Beatty, NV 11/23/87 HN Beatty, NV 11/23/87 HN Beatty, NV 11/30/87 HN Beatty, NV 11/30/87 HN Beatty, NV 12/01/87 HN Beatty, NV 12/07/87 HN Barnwell, SC 12/03/87 HN Beatty, NV 12/03/87 HN Beatty, NV 12/04/87 HN Beatty, NV 12/07/87 HN Beatty, NV 12/08/87 HN Beatty, NV 12/17/87 HN Barnwell, SC 12/09/87 HN Beatty, NV 12/1r/87 HN Beatty, NV 12/14/87 HN Beatty, NV 12/16/87 HN Beatty, NV 12/16/87 HN Beatty, NV 12/18/87 HN Beatty, NV 12/28/87 HN Beatty, NV 12/29/87 CN Channahon, IL Transport Company key CN = Chem Nuclear HN = Hittman Nuclear TSMT = Tri-State Motor Transport DOCUMENT ID 0655t./
- i -
CN C:mmanwealth Edison DA@
j
- \\. LaSaile County Nuclear Station I_, / Rural Rout 3 81. 80x 220 g
Marsedles, Illinois 61341 payp87IY O' yg J
~
Telephone 815/357 6761 g103 s
j n,,
90 Q.~
op is February 10, 1988' sa Th Mr. A. Bert Davis Regional Administrator Directorate of Inspection and Enforcement Region III U.S. Nuclear Regulatory Consission 799 Roosevelt Road Glen Ellyn, IL 60137
SUBJECT:
LaSalle County Nuclear Station Operating Report, NRC Dockets 50-373 and 50-374.
Dear Mr. Davis:
Enclosed is the radioactive effluent report for June through December, 1987 for LaSalle County Nuclear Power Station.
Two copies of the report are provided for your use. One copy will be forwarded to Document Control and the NRC Resident Inspector will receive a Report as outlined in the November 1986 Federal Register.
Sincerely, f
/ "
G/ J. Diederich hk[
Station Manager LaSalle County Station GJD/KFK/msh Enclosure f'~
DOCUMENT ID 0655h/
/
1 MAR 10123
- - - -.