f

[^'N Comm:nw:/:lth Edison

) LaSalle County Nuclear Station

[

c _;

- / RuralRoute #1. Box 220 v

-/ ] Telephone 815/357 6761

\\

Marseilles, Illinois 61341

\\s

/

September 21, 1983 Mr. James G. Kepple r Regional Adminir.trator Region iII U.S. Nuclear Regulatory Commission 799 RooseveIt Road Glen Ellyn, IL 6013750-5 7;4

Dear Mr. Kepp le r:

In accordance with LaSalle County Station Unit 1 Facility Operating License NPF-il, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliances for LaSalle County Nuclear Generating Station Permit No. IL0048151 l,

M G

J. Diederich Supe r i n t enden t LaSalle County Station GJD/FRL/SKD/rg Enclosure xc:

DVR Report l

1 8309300350 030921 g'

6 PDR ADOCK 05000373 1

S PDR g 76/ if(

Commonw alth Edis::n LaSabe Coun:y Nu:: ear Station

\\

^

Rural Rou:e

1. Ecx 22D Ma'seilles. Ilknois 61341 Telepncne 615/357-6761 U.S. Environmental Protection Agency Region V, Enforcement Division ATTri:

Chief, Compliance Unit 230 South Dearborn Street Chicago, IL 60604 Illinois Environmental Protection Agency Division of Water Pollution Control Compliance Management Unit 1

2200 Churchill Road Springfield, IL 62706 i

Dear Si r:

Subj ect :

ilPDES tioncompliances for LaSalle County fluclear Generating Station - Permi t tio. IL0048151 In accordance with Standard Condition 12, we wish to submit the following notice of noncompliances, which are listed chronologically in the attached table.

If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, extension 201 l

l l

l l

G J. Diederich Station Superintencent OJD/TRL/SKD/bej Director of Water Quality, Environmental Affairs xc:

t'anager, riuclear Stations Division e

4*

1 LASALLE COUhIT NUCI.ZAR GENERanUG STATION N.P.D.E.S. PERMIT NO:

ILOO48151 NCNCCMPLIANCE REPCRT DISCHARCE NUMBER AND DESCRIPTICN: 001c Wastewater Treatment Facility Effluent PARAMETER _ AND PERMIT LIMIT:

Totai Suspended So1 ids, 15 mg/1 NONCCMPLIANCE, DATE, AND DURATION: 31 mg/l Total Suspended Solids, 23 Aug 83, Unknown CAUSE OF NONCCMPLIANCE: The equa1ization tank mixer which had not been run ror s Eeral montns was allowed to run prior to collection of the composite sample on 23 Aug 83 This suspended the solids that had settled in the bottom of the tank during the time the mixer had not run and caused the total sus-pended solids concentration to exceed the 15 mg/l 14PDES permit 1imit.

CCRRECTIVE ACTION: The equalization tank mixer was shut off.

Use of the mixer will be closely monitored in the future.

The wastewater treatment facility effluent total suspended solids concentration was back within the TIPDES permit Iimit by 25 Aug 83.

t DATE RECOGNIZED AS A VIOLATION:

24 Auc 83 DATE INVESTICATED:

26 Auc 81


n---