DMG Commonwealth Edison f.:;

LaSalla County Nuclear Station a

Rural Routa #1, Box 220 b'

Marseilles,lilinois 61341 pa1031,n R00lltiG Telephone 815/357-6761 i

912

/dp

?T

%.u

=s i

y, iL

  1. N!

g Fil June 25, 1986 i

I Mr. James G. Keppler Regional Administrator Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 l

1

Dear Mr. Keppler:

i In accordance with LaSalle County Station Unit 1 and Unit 2 Facility 1

Operating License NPF-ll and NPF-18, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliance for LaSalle County Nuclear Generating Station Permit No. IL0048151.

g. O.

G. J. Diederic Station Manager l

LaSalle County Station GJD/LRA/RHK/kg i

Enclosure i

i xc: NRC Resident Inspector i

INPO - Records Center i

US NRC Document Control Desk

+

i JUN 3 01986 o

l

/&

B607100438 860625

)'

-Cs==ga

pg Comm::nwealth Edison 3,,

,=

f Q.

LaSalle County Nuc! ear Stx cn 1 (eV Rural Route #1, Box 220 N

Marseilles. Illinois 61341 C"

Tele:: hone 815/357-6761 4

1 i

June 9, 1986 I

a U. S. Environmental Protection Agency Region V, Enforcement Division

[

}

ATTN: Chief, Compliance Unit 2

230 South Dearborn Street Chicago, IL 60604 l

Illinois Environmental Protection Agency I

Division of Water Pollution Control i

Compliance Management Unit 2200 Churchill Road Springfield, IL 62706 1

Dear Sir:

Subject:

NPDES Noncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151 l

In accordance with Standard Condition 12, we wish to submit the following notice of noncompliances which ate listed on the attached table.

If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, exteasion 487.

3 1

l 1

e

//

s f g/.

,b G. J. Diederich I

Itatica Managar GJD/L3A/3HK/jdp

{

t Xc:

Direc:or of 'ia 3r Quali:7, Ir.vironmental Affairs Manager, Nuclear 3:2:icns Divi.3icn r

)

}

F r

3C4"dMS.E *D )C"$D '2253d

1

'?

LASALLE COUNT'? NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

IL0048151 NONCCMPLIANCE REPCRT DISCHARGE NUMBER AND DESCRIPTICN:

001, Cooling Pond Blowdown PARAMETER AND PERMIT LIMIT: Total Iron, 2.0 ppm 30-day average NCNCCMPLIANCE, DATE, AND DURATICN:

3.7 ppm Total Iron, 31 May 86, unknown CAUSE OF NCNCCMPLIANCE: The 2.0 ppm 30-day average limit for cooling pond blowdown total iron was exceeded because of one discharge which contained 5.8 ppm total iron.

(This occurrence was reported on a 6 May 86 notice of noncompliance submitted 28 May 86).

The only other sample required by the permit during the month of May was below the 4.0 ppm dally maximum limit.

CORRECTIVE ACTICN: On 8 May 86 Environmental Affairs Department requested that the total iron monitoring requirement and limitation on cooling pend blowdown be deleted and alternatively impose iron limitations on any of the individual wastestreams discharging to the cooling pond or cooling pond bicwdown line. The station feels this request is necessary due to-widely fluctuating iron levels present in the Illinois River and cooling pond which occur from natural causes.

It is the station's belief that this nonccmpliance was caused by factors beyond its control.

DATE RECOGNI"ED AS A VICLATICN: