_ _ - _ _ _ _ _ _ _ _ _ _ _ _ _

N Commonwealth Edison LaSalle County Nuclear Station Rural Route 01, Box 220 Marseilles,I!!inois 61341 Telephone 815/357-6761 l

July 14, 1982 U. S. Environmental Protection Agency l

Region V, Enforcement Division ATTN:

Chief, Compliance Unit 230 South Dearborn Street Chicago, i11inois 60604 lilinois Environmental Protection Agency Division of Water Pollution Control Compiiance Management Unit 2200 Churchill Road Springfield, Illinois

SUBJECT:

NPDES Noncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151

Dear Sir:

In accordance with Standard Condition 12, we wish to submit the following notices of noncompliance, which are listed chronologically in the attached table.

If there are any questions, please contact Charles L. Nash of my staff ai-(815)357-6761, extension 235 u

yy R. H. Holyoak Superintendent LaSalle County Station RHH

/CL /gew

Attach, Di rector. of Water Quali ty, Envi ronmental Af fai rs cc:

Manager, Nuclear ~ Stations Division 4

8208020346 820714 PDR ADOCK 05000373 S

PDR

LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151' NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION:

001c - Low Volume Waste Regen. Wastes Soln. Discharge Tank, PARAMETER AND PERMIT LIMIT:

Total fron, 1.0 mg/l NONCOMPLIANCE, DATE, AND DURATION:

2.2 mg/l; 12JUN82, 2i hrs.

2.4 mg/1; 15JUN82, 24 hrs.

4.2 mg/l, 29JUN82, 2i hrs.

CAUSE OF, NONCOMPLIANCE:

The excessive total iron found on June 12, 1982, June 15, 1982, and June 29, 1982 was due to the temporary hydrogen peroxide injection system becoming air-bound, and not operating properly.

e.

L CORRECTIVE ACTION:

A permanent hydrogen peroxide injection system is to be installed as soon as equipment can be purchased and delivered.

Expected completion date is approximately 01JAN83 12JUL82 DATE RECOGNIZED AS,A VIOLATION:

13JUL82 DATE INVESTIGATED: