. _ '

l unne count! NUC'.In GENERAUNG STAUCN g

N.P.D.E.S. PE3F T NO:

U 00/+8151 NCNCCMPLIANCE REPORT DISCHARGE NUM3ER AND DESCRIPTION:

Outfall 001c Low Volume Waste Wastewater Treatment Facility Effluent TX4AMETER AND PERMIT LIMIT:

Total tron, 1.0 mg/l NONCCM?LIANC2, DATE, AND DURATICN:

1.6 mg/1, 01Feb83, Unknown CAUSE OF NCNCCMPLIANCE:

The most probable cause of this non-compliance was the alum pumps not injecting alum.

s CORRECH VE ACTION:

The problem with the alum pumps was corrected, and the clearwell was pumped back to the equalization tank on 04Feb83 for reprocessing.

k j

14Feb83 DATE RECCGNIZED g A VIOLATION:

15 Feb 83 DATE nmSncATED:

8303080366 830225 yDRADOCK 05000373 PDR

..n...

.... ~

. ~....

..