. _ _

1Mid Commonwealth Edison VI LcSall] County Nuct:2 r Station TEICEfry neury,.m l

H Rur:1 Routs #1, Box 220 Qg_:17,, g

' Marscilles, Illinois 61341 l

r
N_s, Telephone 815/357-6761 i _ ]i: 7(

u.

~

bhp / # !bli_

c 3 & L-fILGM%

November 6, 1985 Mr. James G. Keppler Regional Administrator Region III U.S. Fluclear Pegulatory Comralasion 799 Roosevelt Road Glen Ellyn, Illinola 60137

Dear Mr. Keppler:

In accordance with htSalle County Station Unit 1 and Unit 2 Facility Operating Licenae !!PF-11 and fiPF-18, Appendix B, Section 3.2, we are aubmitting to you a copy of the NPDES noncompliance for LtSalle County Nuclear Generating Station Permit tio. IL0048151.

f.0 G. J. Diederich Station Manager LnSalle County Station GJD/LHA/Hi[K/kg Encloaurc xc

!!RC Healdent Inapector INPO - Hecorda Center US NRC Document Control Desk

.NOV1619'5 0D11250435 0D1106 f

  • Dit ADOCK 0D000373 1l-U f*DH

C:mmon2ecith Edis:n Laf:

a. w No::ct: 5:a ion 4

4: n *1 Ecs :20 t.'.; sc : c:,. Mncut (1341 Te:ce.one 815/357 6761 l

November 1, 1985 U. S. Environmental Protection Agency Region V, Enforcement Division ATTN: Chief, Compliance Unit 230 South Dearborn Street Chicago, IL 60604 Illinois Environmental Protection Agency DlV1Flon of Water Fo.lution Control Cce; liance Managemant Dr.i t 2200 Churchill Road Springfield, IL 62706

Dear Sir:

Subject:

NPDES Noncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151 In accordance with Standard Condition 12, we wish to submit the following notice of noncompliances which are listed on the attached table.

If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, extension 487.

G. J. Diederic GJD/LRA/ RID;/sjc act Director of Water Quality, Environmental Affairs Manager, Nuclear Stations Division DOCUMENT ID 0070h/0250A

e LASALLE COUNTY NUCLEAR GENERATING STATION W.P.D.E.S. PERMIT NO:

ILOO4 Bib 1 f

NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION: 001(c) Wastewater Treatment System Effluent PARAMETER AND PERMIT LIMIT: Oil and Grease 20 ppa daily maximum NCWCOMPLIANCE. DATE. AND DURATION:

32 ppm Oil and Grease. 150CT85 Unknown.

CAUSE OF NONCOMPLIANCE:

A large volume of oil entered the Wastewater Treatment System and overloaded it.

The source of oil and grease is unknown.

The separator trough between the inlet and outlet bays of the Wastewater oil separator is full of sludge, as are the oil separator tube bundles.

An oil boom had been placed in the Wastewater Treatment Effluent compartment. This boom had been trapping a sheen of oil in the vicinity where Oil and Grease sa:oples are obtained.

CORRECTIVE ACTION:

Action Item Record 373-200-85-18001 has been written to track replacement of the Oil Separator tube bundles. New tube bundles will be installed within one week of their arrival on-site. The oil separator trough will also be cleaned at that time.

The Effluent Compartment oil boom has been removed and will not be reinstalled. Oil booms in the clearwell will continue to be inspected and changed out as necessary.

An Action Item Record has been written to identify the source of the oil and establish corrective action for the problem.

DATE RECOGNIZED AS A VIOLATION:

290CT85 E TE INVESTIGATED:

300CT85 DOCUMENT ID 0070h/0250A

.