ML20023B259
| ML20023B259 | |
| Person / Time | |
|---|---|
| Site: | LaSalle |
| Issue date: | 12/13/1982 |
| From: | COMMONWEALTH EDISON CO. |
| To: | |
| Shared Package | |
| ML20023B250 | List: |
| References | |
| NUDOCS 8212270170 | |
| Download: ML20023B259 (1) | |
Text
.
t J.
tant?r COUNTT NCCLIAR GEERATING STACON N.?.D.E.S. PERMIT NO:
U.0043131 NONCCMPLI.GCI RI?CET DISCHARGE NCMBER.UD DESCII? C CN: Outfall 001c Low Volume Waste Wastewater Treatment Facility
?AR.LG AND ?L"C'.I"2 Lt!I~:
Total Suspended Solids, 15 0 mg/l Total Iron, 1.0 mg/l NCNCCMPLI.ANC2, DA~I, AND DURA *!CN:
TSS 50 9 mg/1, November 16, 1982, 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Total Iron 1 7 mg/1, November 16, 1982, 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> CAUSE g, NCNCCM?tI.GCI: Oi1 was present in the faciiI ty equalization tank when the equalization tank mixer was placed into operatior, af ter repairs. The mixing action emulsified the oil.
The oil emulsion reduced flocculation and filtration efficiency, causing the noncompliance.
CCRRIC I7E ACC ON:
1.
Plant discharge was stopped.
2.
All treated water was returned to the equalization tank.
3 The clearwell was cleaned.
4.
Oil was skimmed off the clarifters.
5 The equalization tank mixer was taken out of service.
6.
Oil soak bags were placed in the equalization tank, clearwell, and effluent compartment.
19 November 1982 g
./*CLAC CN:
23 November 1982
.,7_3_,, g i
r 6 I
gg793 ADOCKoh0hh
_S PDR
_ - _. - _ -