i T AC1771 COUNTY NUCI.ZAR GENERATING STATICN N.P.D.E.S. PERMIT NO:

ILOO48151 NONCOMPLIANCI REPORT i

DISCHARGE NUMBER AND DESCRIPTION:

Octfall 001c Low Volume Waste Wastewater treatment facIIIty PARAMETER AND ?!RMIT LIMIT: Total Suspended Solids 15 mg/l Total tron 1.0 mg/l NONCOMPLIANCE, DATE, AND DURATION:

Total Suspende, Solids,150 mg/1,14 September 1982, 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Total Iron 67 0 mg/1,14 September 1982, 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> CAUSE OF NONCCMPLIANCE:

The wastewater plant pH was upset during this period due to Unit 2 construction activi ties. An acidic floor cleaning solution was used to prepare the floors for painting. The upset pH degraded the efficiency of flocculation and filtration.

CORRECTIVE ACTION:

A work request has been initiated to Install an Inline pH monitor at the WWTF.

Installation of this equipment, and logic to trip the equalization t:nk transfer p imps on conditions of high or low pH should prevent this from occurring i

  • the future.
l-

't

!}

-l

- DATE RECOGNIZED AS, A VIOMT'9f':

27 September 1982

..l DATE INVESTIGATED:

r:m '

j OgOg4 8hh3

-f 0

PDR g

.