.I T N " COUNTY Ntf N GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151 NONCOMPLIANCE REPORT

\\

DISCHARGE NUMBER AND DESCRIPTION:

001c Low Volume Waste Regen. Wastes Soln. Discharge Tk, PARAMETER AND PERMIT LIMIT: Total Suspended Solids, 15 mg/l NONCOMPLIANCE, DATE, AND DURATION: 18 mg/1, 18JAN83, 4-1/3 hours CAUSE g NONCOMPLIANCE:

Possible causes of this noncompliance are, wastes from Unit 2 condensate polishing system regeneration, and a buildup of solids in the discharge tank.

l CORRECTIVE ACTION:

A modification has been initiated to provide the option for treatment of these tanks in:the vastewater treatment facility. The modification should be imple-mented by February 1983.

Further investigation into whether solids are building up in the discharge tank is in progress.

6 6

20JAN83 DATE RECOGNIZED M A VIOLATION:

24JAN83 DATE IN7ESTIGATED: