7 s

c LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION: 001(c) Wastewater Treatment Facility Effluent PARAMETER AND PERMIT LIMIT:

pH, 6.0-9.0 S.U.

MONCOMPLIANCO DATE, AND DURATION:

10.2 S.U. pH, 03Jun85, approximately 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 40 minutes.

CAUSE OF NONCOMPLIANCE:

The OWM03T Regenerative Wastes Solution Discharge Tank was pumped to the Wastewater Treatment Facility immediately prior to discovering the 10.2 S.U. pH, and is suspected to be the cause of this excursion. A sample of the 0WM03T tank was analyzed for pH prior to being pumped to the Wastewater Treatment Facility. The 8.5 S.U. result indicated the tank met MPDES permit liais.

However, it is believed the sample collected prior to pumping to the Wastewater Treatment Facility was not representative of the tank due to inadequate mixing. The mixing is believed to be inadequate since only low flow can be obtained through the transfer pumps.

CORRECTIVE ACTION:

The Wastewater Treatment Facility discharge was isolated. The clear well was i

pumped back to he equalization tank and neutralized.

AIR l-85-67012 has been written to track the investigation of low flow through j

the transfer pumps.

DATE RECOGNIZED AS A VIOLATION:

03JUN85 DATE INVESTIGATED:

03JUN85 8507150578 850619 PDR ADOCK 05000373 s

PDR DOCUMENT ID 0070h/0250A

Commonwealth Edison DM LaSille County Nuclear Station PF:ICRITY FOUTI';G Rur:I Route #1, Box 220 iisA__ - Si Marseilles, Illinois 61341

!?_}_t_; L f 1_ _ ! '

Telephone 815/357-6761 m

y W

t:tl4Iv.% -- 1l

~

g FILE M June 19, 1985

-3/g o -87Y Mr. James G. Keppler Regional Adninistrator Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

In accordance with LaSalle County Station Unit 1 and Unit 2 Facility Operating License NPF-11 and NPF-18, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliance for LaSalle County Nuclear Generating Station Permit No. IL0048151.

$S-h G. J. Diederich Station Manager IaSalle County Station GJD/FRL/SKS/kg Enclosure xc: NRC Resident Inspector INPO - Records Center US NRC Document Control Desk 7

I t w

sy

Commonwealth Edison L:S:lis County NucI::r Station Rural Route #1, Box 220 Marseilles. Illinois 61341 Telephone 815/357-6761 June 6, 1985 U. S. Environmental Protection Agency Region V, Enforce *aent Division ATTN: Chief, Compliance Unit 230 South Dearborn Street Chicago, IL 60604 Illinois Environmental Protection Agency Division of Water Pollution Control Cosoliance Management Unit 2200 churchill Road Springfield, IL 62706 Dear Sir

Subject:

NPDES Noncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151 In accordance with Standard Condition 12, we wish to submit the folicwing notice of noncompliance which is listed on the attached table.

If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, extension 487.

/

/

J. Diederich G

ation Manager GJD/FRL/SKD/jdp xc: Director of Water Quality, Environmental Affairs Manager, Nuclear Stations Division DOCUMENT ID 0070h/0250A i

.-._ ___