-,:'_.-.:. '_

.i.a h

LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151 i

NONCCMPLIANCZ REPORT DISCHARGE NUMBER AND DESCRIPTICN: Outfall 001c - Low Volume Waste Wastewater Treatment Facility

[

PARAMETER AND ?!RMI'r LIMIT: ph, 6.0-9 0

.U.

NONCCMPLIANCE, DATE, AND DURATION: 3 9 S.U.,13 September 1982, 0830 until 1630 when discharge was secured CAUSE 02 NCNCCMPLIANCE:

Unit 2 construction activities, floor cleaaing prior to painting, generated acid waste which are routed to this fac!ii.r.

I E

p E

CORRECTIVE ACTION:

Discharges through this outfall were discontir.ued until the pH was brought 7

back wi thin spect fications.

In addition a work regi 3t has been initiated to install an inline pH monitor at the WWTF.

1.1sia.lation of this equip-ment and logic to trip the equalization tank transfer pumps on conditions of high or low pH should prevent this from occurring in the future.

1 I

E

^

[

E

}

DATE RECOGNITED g A 7IOLAT*g :

September 15, 1982 i

DATE IN7ESTIGATED:

Seotember 16. 1982 h

~'B210190503 820929'

~~

PDR ADOCK 05000373

- ~ -

E S.

PDR

_ _. _..