Text

-.

LASALLE COUNTY NUCLEAR GENERATING STMION N.P.D.E.S. PERMIT NO:

ILOO48151 NONCOMPLIANCE REPORT DISCHARGENUMBER[ANDDESCRIPTION: 001c - Low Volume Waste Wastewater Treattnent Facility. -

PARAMETER AND PERMIT LIMIT:

0i1 and Grease, 15 mg/1 NONCOMPLIANCE, DATE, AND DURATION:

18 mg/l, June 1, 1982, Unknown CAUSE OF, NONCOMPLIANCE:

Review of operator logs and round sheets, does not indicate a cause for this result.

Review of pH, total metals, and total suspended solids analyses performed concurrently do not Idnicate a system problem. An error in the sampilng or the analysis is suspected.

Since insuf ficient sample was obtained to re-arialyze, the Station cannot verify at this tire.

L CORRECTIVE ACTION:

An oil-soak boom has been placed into the outlet chamber of the Wastewater Treatment Facility.

This boom should prevent residual oil from being discharged.

Also, a duplicate grab sample for oli and grease will be obtained to allow for reanalysis, if desired, to pinpoint analytical discrepancies.

7 ova DATE RECOGNIZED AS A VIOLATION:

12JUL82 DATE INVESTIGATED:

8208020357 820714 PDR ADOCK 05000373 S