ML20137Z537

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 850831,30-day Average Limit Exceeded Due to One Discharge Which Contained 28 Ppm Total Suspended Solids.Composite Sampler Repaired
ML20137Z537
Person / Time
Site: LaSalle  Constellation icon.png
Issue date: 09/27/1985
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8510080269
Download: ML20137Z537 (3)


Text

_

4, s' O,A >

Comm:nw;Ilth Ediscn f2 LaSalle County Nuclear Station Rural Route #1, Box 220 PRICRITY ROUTING i

Marseilles,lilinois 61341

!j irst g

i Telephone 815/357-6761 t

y

a ng-h OE +A4 _.__i _

Off FILE d s September 27, 1985 Mr. James G. Keppler Regional Administrator Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 i

Dear Fr. Keppler:

In accordance with LaSalle County Station Unit 1 and Unit 2 Facility Operating License NPF-11 and NPF-18, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliance for LaSalle County Nuclear Generating Station Permit No. IL00h8151.

  1. 9 ko G. J. Diederich 1

Station Manager 4

LaSalle County Station GJD/FRL/RHK/kg Enclosure xc: NRC Resident Inspector INPO - Records Center US NRC Document Control Desk Pw 1

i 8510000269 850927 8

l PDR ADOCK 05000373 S

PDR SEP 301985.

.. ~,

. =_.

Commonwealth Edison Q

LaSa e County Nxl eat Sta' ion i

R/a Ro te #1 B s 220 o

V Ma se.;es. lit.no:s C13c Te'eMone 615/357 6761 F

j September 23, 1985 i

l U. S. Environmental Protection Agency Region V, Enforcement Division ATTN: Chief Complianet. Unit j

230 South Dearborn Street l

Chicago, IL 60604 I

4 Illinois Environmental Protection Agency I

Division of Water Pollution Control l

Complidnce Manage: tent Unit i

2200 Churchill Road l

Springfield IL 62706

Dear Sir:

l

Subject:

NFDt:.E Noncocpliances for LaSalle County Nuclear Generating Station - Permit No. IL0048151 I

In accordance with Standard Condition 12, we wish to submit the following notice of noncocpliances which are listed on the attached table.

If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, extension 487 i{

i I.

c' /

+y l

i

.a f

G,J. Dioderich y

Station Manager l

W j

GJD / tT.L/FHE /s j c xc: Directo: of Water Quality, Environmental Affairs j

Manager Nuclear Stations Division f

i l

i DCCUMe.NT ID 0070h/0250A

3 i

LASALLE COUNTY NUCLEAR GENERATING STATIC;f N.P.D.E.S. PERMIT NO:

ILOO48151 NONCOMPLIANCE REPORT t

DISCHARGE NUMBER AND DESCRIPTION:

001(a) Demineralizer Regenerative Wastes.

PARAMETER AND PERMIT LIMIT: Total Suspended Solids, 15 ppm, 30 day average.

NONCOMPLIANCE, DATE, AND DURATION:

20 ppm Total Suspended Solids, 31 Aug 85, 30 day average.

CAUSE OF NONCOMPLIANCE:

The 30-day average limit was exceeded because of one discharge which contained 28 ppm total suspended solids.

A grab sample collected prior to discharge indicated the tank met NPDES discharge limits.

It is suspected that the sample was non-representatise due to sampling methodology.

_ CORRECTIVE ACTION:

The composite sampler previously out of service has been repaired and returned to service. Collected analytical data for grab and composite sampling will be evaluated to determine validity of TSS analysis for flowpath determination prior to actual discharge.

DATE RECOGNIZED AS A VIOLATION:

16SEP85 DATE INVESTIGATED:

19SEP85 1

l l

l l

Dr/'UMENT ID 0070h/0250A

. -. - ~,, -....-

-..., -.. - -.