USALLE COUNTT NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151 l

l.

NONCOMPLIANCE REPORT

' DISCHARGE NUMBER AND_ DESCRIPTION:'

Outfall 001c Low Volume Waste

(.

Regen. Wastes Soln. Discharge Tank' PARAMETER _AND PERMIT _ LIMIT: TSS, 15 eg/1.

Total Iron, 1.0 mg/l NON00MPLIANCE, DATE, AND DURATION:

TSS, 27 mg/1, 24NOV82, 11666 Gallons Total Iron, 1.3-mg/1, 24Nov82,.11666 Callons CAUSE OF NONCOMPLIANCE:

The most probabic cause of these noncompliances is the addition to tht: tank of construction wastes from the Unit 2 condensate polishing system.

CORRECTIVE _ ACTION:

A modification has been initiated to provide the option for treatment of these tanks in the wastewater trentraent facility.

The nodification should be imple-mented by February 1983.

I 10Dec82 l

DATE RECOGSIZED g A_ VIOLATION:

10Dec82 DATE INVESTICATED:

9301110420 821221 PfNt ADOCK 05000373 9