___ _ _ _ _ _ _ _ _ _ _
~
O' LASALLE COUhTl NUCLEAR GDERATING STATION N.P.D.E.S. PERMIT NO:
ILOO48151 '
NONCOMPLIANCE REPORT
~
DISCHARGE NUMBER AND DESCRIPTION:
001c - Low Volume Waste Regen. Vastes Soln. Disch. Tank PARAMETER AND PERMIT LIMIT:
Total Suspended Solids NONCOMPLIANCE, DATE, AND DURATION:
22 mg/1, 29JUN82, 21 hrs.
CAUSE OF, NONCOMPLIANCE:
Excessive amounts of soluble iron collected on the Make-Up Demineralizers due to loss of hydrogen peroxide injection f rom the' temporary system. This i ron was discharged to this outfall as insoluble iron during regeneration of the demineralizers.
CORRECTIVE ACTION:
A permanent hydrogen peroxide injection system is to be installed as soon as equipment can be purchased and delivered.
Expected completion data is approximately 01JAN83 l
8208020178 820714 PDR ADOCK 05000373 01JUL82 S
PDR DATE RECOGNIZED AS _A, VIOLATION:
DATE INVESTIGATED:
_- _ _ - _ _ _ _ _ _ _