LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:
ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION:
Outfall 001c Low Volume Waste Regen. Wastes Soln. Discharge Tank PARAMETER AND PERMIT LIMIT
- Total Iron, 1.0 mg/l NONCOMPLIANCE, DATE, AND DURATION: 25.3 mg/1, 20 October 1982, 58,330 gallons j
CAUSE OF NONCOMPLIANCE:
The normal influents to this tank contain, iron concentrations of less than 5 mg/l iron as verified by sampling on 11/11/82.
The most probable cause I
of the high iron concentration was the addition to the tank of construction wastes from the Unit 2 condensate polishing system.
CORRECTIVE _ ACTION _:
A modification has been initiated to provide the option for treatment of these tanks in the Waste Water Treatment Facility. The modification should be implemented by February 1983..
1 November 1982 DATE RECOGNIIED_ AS A VIOLATION _:
12 November 1982 DA H INVESTICATED:
O211290508 821118 PDR ADOCK 05000 S
.