Text

3p -;

TAMAft? COUNT! NUCLEAR GENERATING STATION N.P.D.E.S. PE M T NO:

ILOO48151 NONCCMPLIANCE REPCRT DISCHARGE NUMBER AND DESCRI? TION:

Outfall 001c Low Volume Waste Regen. Waste Soln. Discharge Tank PARAMETER AND ?!3MIT LIMIT: Total Suspended Solids, 15 mg/l NONCCMPLIANCE, OATE, AND DURATION: 22 mg/1, 14 September 1982, 2i hours CAUSE _OF NONCOMPLIANCE:

A buildup of resin fines and other fine solids carried through the strainers and sumps into the discharge tank.

CORRECTIVE ACTION:

A work request is in progress to clean the regenerative wastes solution discharge tank, make-up demineralizer acid sump,demineralizer regenerative waste transfer pumps suction strainers, and the make-up demineralizer waste strainer.

t 2

I

- I t

22 September 1982 DATE RECCGNIZED AS A VIOLATION:

27 September 1982 i'

DATE IN7ESTICATED:

,I l

l 8210 20 0 c07 [

.