7 s
Comm:nw cith Edison LaSalle County Nuclear Station Rural Route #1, Box 220 e
Marseilles, Illinois 61341 Telephone 815/357 6761 November 24, 1982 U.S. Environmental Protection Agency Region V, Enforcement Division ATTN: Chief, Compliance Unit 230 South Dearborn Street Chicago, !L 60604 Illinois Environmental Protection Agency Division of Water Pollution Control Compilance Management Unit 2200 Churchi11 Road Springfield, IL 62706
Dear Sir:
Subject:
HPDES Noncompliances for LaSalle County Nuclear Generating Station - Permi t No. ILOO48151 In accordance wi th Standard Condi tion 12, we wish to submi t the following notice of noncompliances, which are listed chronologically in the attached table.
If there are any questions, please contact Joe Williams of my staff at (815) 357-6761, extension 201.
b G
J. Diederich Superintendent LaSalle County Station 5kQ GJD/
Jb/psl Director of Water quality, Environmental Affairs cc:
Manager, Nuclear Stations Division l
8212170214 821210 PDR ADOCK 05000373 S
LASALLI COUNTY NUC'm GENERATING STATICM N.?.D.E.S. PERMIT NO:
ILOO/.8151 NONCCMPLIANCI REPCRT DISCHARGE NUMBER AND DESCRI?TICN:
Outfal1 001c Low Volume Waste Wastewater Treatment Facility PARahs.:.x AND ?!R'.C" LIMIT:
0i1 and Grease, 15 0 mg/1 NONCCM?LIANC2, DATI, AND DURATION:
115.6 mg/1, November 12, 1982, Unknown CAUSE OF NONCCMPLIANCE:
011 was present in the faci 1ity equa1ization tank when the equalization tank mixer was placed into operation af ter repairs. The mix-ing action emulsified the oil.
CCRREw ave. ACTICN:
1.
Plant discharge was stopped.
l 2.
All treated water was returned to the equalization tank.
3 The clearwell was cleaned.
4.
Oil was skimmed off the clarifiers.
5 The equalization tank mixer was taken out of service.
6.
Oil soak bags were placed in the equalization tank, cIearwell, and effluent compartment.
November 18. 1Q82 DATI RECCGNITED AS A. 7 CLATICN:
November 23, 1982 DATI n.m STICA ED:
i
--n.
...