NPDES Noncompliance Notification:On 851011,media Filter B Backwash Nozzle Discovered Broken & Filtering Medium Drained Into Clearwell,Underdrains & Effluent Chamber.Cause Not Stated.Nozzle Replaced & Anthracite Coal Added to Filter
ML20137D628
Person / Time
Site: LaSalle  
Issue date: 11/06/1985
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8511270111
Download: ML20137D628 (3)


Text

{{#Wiki_filter:. e 'N Commonwealth Edison PAS

4) Rural Route #1, Box 220 LaSalle County Nuclear Station c

I { c-z U g f Marseilles,I!!inois61341 NG Telephone 815/357-6761 PRIORITY R0tiTING, El-{g _.1 g .y__. OfyM4!gE November 6, 1985 l Mr. James G. Keppler Regional Administrator SD - I,/ b Region III 37Y 1 U.S. Nuclear Regulatory Commission T99 Roosevelt Road ' Glen Ellyn, Illinois 60137 4 1

Dear Mr. Keppler:

In accordance with LaSalle County Station Unit 1 and Unit 2 Facility j Operating License NPF-11 and NPF-18, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliance for LaSalle County Nuclear Generating Station Permit No. ILO0h8151. 1 1 / O. B /,- G. J. Diederich Station Manager LaSalle County Station GJD/LRA/RHK/kg 2 i Enclosure f xc: NRC Resident Inspector INPO - Records Center-US NRC Document Control Desk r 3 4 / 7 i I 4 NOV 201985 B511270111 851106 s PDR ADOCK 05000373 fy PDR

/' Comm:nwrith Edison / c.O LaSalle County Nuclear Station l' t Rural Route 81, Box 220 ( ~d_ _ <]. Marseilles, Illinois 61341 gy' Telephone 815/357-676) October 21, 1985 U. S. Environmental Protection Agency Region V. Enforcement Division ATTW: Chief. Compliance Unit 230 South Dearborn Street Chicago, IL 60604 Illinois Environmental Protection Agency Division of Water Pollution Control Compliance Management Unit 2200 Churchill Road Springfield, IL 62706

Dear Sir:

Subject:

WPDES Noncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151 In accordance with Standard condition 12, we wish to submit the following notice of noncompliances which are listed on the attached table, 1 l If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, extension 487. l h f it G J. Diederich Station Manager GJD/PRL/RHK/msh xc: Director of Water Quality, Environmental Affairs Manager, Nuclear Stations Division i DOCUMENT ID 0070h/0250A

LASALLE COUNTY h*UCLEAR CENERATING STATION N.P.D.E.S. PERMIT NO: ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION: 001(c) Wastewater Treatment System Effluent PARAMETER AND PERMIT LIMIT: Total Suspended Golids, 30 ppm daily maximum l NONCOMPLIANCE. DATE. AND DURATION: 43 ppm Total Suspended Solids, 160CT85, unknown CAUSE OF NONCOMPLIANCE: On 110CT85 a backwash nczzle on 'B' media filter was discovered to be broken and the filtering medium had drained into the clearwell, underdrains, and effluent chamber. The backwash nozzle was replaced and the clearwell, underdrains, and effluent chamber were cleaned on 110CT85. When replacing the filtering medium, the station was short of the necessary amount of anthracite coal. The filter war put into service until 170CT85 when it was isolated until the proper amount of anthracite coal was received. The anionic polymer skid was out of service from 120CT85 to 170CT85 to repair a level probe. The composite sampler was found to be overflowing at sample time due to a power loss and compositor memory loss. CORRECTIVE ACTION: Anthracite coal was added to 'B' media filter to bring it to the correct level on 180CT85. The anionic polymer skid was put back into service on 170CT85, although rapairs were incomplete. Anionic polymer is currently manually mixed in the mixir.g tank. The composite sampler has been reprogrammed to sample the correct volume. DATE RECOGNIZED AS A VIOLATION: 160CT85 t l DATE INVESTIGATED: 170CT85 DOCUMENT ID 0070h/0250A "J}}