a i
LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:
ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION:
Outfall 001c t.ow Volume Waste Radwaste Discharge Tanks s
PAkAMETER AND PERMIT LIMIT:
pH, 6.0-9 0 S.U.
l'ONCOMPLIANCE, DATE, AND DURATION:
4.6, 24SEP82, 8 Hours CAUSE OF NONCOMPLIANCE:
At 0550 Hrs. 23SepS2, the tank was sampled to verify neutralization
"~
prior to discharge. The result was 6.1 S.U. pH.
At the end of the discharge a second sample was pulled which showed the pH to be 4.6 S.U.
A third sainple,was pulled that verified the 4.6 pH.
The cause of the pH change is unknown all inputs to the tank were isolated from the time
~
of the first sample on.
CORRECTIVE ACTION:
An error in the sampling or analysis is suspected. A review of the flush time used for flushing the sample line is being done to insure the time is adequate to obtain a representative sample.
F DATE RECOGNIZED AS A VIOLATION:
September 24, 1982 September 24, 1982
/
DATE INVESTIGATED:
/
l 8211060128 820924 PDR ADOCK 05000373 S