__

/

'N Commonwealth Edison D-< #

/

) RuralRoute #1, Box 220LaSalle County Nuclear Station

{

j} Telephone 815/357-6761 Marseilles, Illinois 61341 s\\

fR10RITYROUTH:3 M

lypai!

m-m;g-.

July 29, 1985 KQg_-l s

V fa e

-n

.s

@mM -gp g-

~

g(j(h miir

/

i fjy~

FILE g -

Mr. James G. Keppler Regional Administrator Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

In accordance with LaSalle County Station Unit 1 and Unit 2 Facility Operating License NPF-ll and NPF-18, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliance for IaSalle County Nuclear Generating Station Permit No. IL0048151.

/

G J. Diederich Station Mant.ger LaSalle County Station GJD/FRL/SKS/kg Enclosure xc: NRC Resident Inspector INPO - Records Center US NRC Document Control Desk

<AUG 51985 8509090029 850729

/' /h PDR ADOCM 05000373

. + '

S PDR

/

fl

r j

August 1, 1985 U. S. Environmental Protection Agency Region V, Enforcement Division ATTN: Chief, compliance Unit 230 South Dearborn Street Chicago, IL 60604 Illinois Environmental Protection Agency Division of Water Pollution Control compliance Management Unit 2200 Churchill Road Springfield, IL 62706

Dear Sir:

Subject:

MPDES Moncompliances for LaSalle County Nuclear Generating Station - Permit No. ILOO48151 In accordance with Standard condition 12, we wish to submit the following notice of noncompliances which are listed on the attached table.

If there are any questions, please contact Steve Davis of my staff at (815) 357-6761, extension 487.

44 G

J. Diederich Station Manager GJD/FRL/SKD/sjc xc: Director of Water Quality, Environmental Affairs Manager, Nuclear Stations Division i

DOCUMENT ID 0070h/0250A

LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151 NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION: 001(c) Wastewater Treatment System Effluent LARAMETER AND PERMIT LIMIT: Oil and Grease, 20 ppa daily maximum 011 and Grease, 15 ppe 30 day average NONCOMPLIANCE. DATE, AND DURATION:

82 ppe Oil and Grease, 17JUN85, unknown 34 pga 011 and Grease, 24JUN85, unknown 33 ppa 011 and Grease, 30-day average, 03JUL85, month of June CAUSE OF NONCOMPLIANCE:

A large volume of oil entered the Wastewater Treatment System and overloaded it.

The source of the oil and grease is unknown.

[ M ECTIVE ACTION:

Attempts are being made to identify the source of oil and grease inputs into the Wastewater Treatment System.

I The oil and grease was pumped out of the clarifiers and oil separator pits. The oil absorbent booms in the clearwell and effluent chamber were replaced.

Efforts are also being made to restore the polymer systems to an operable condition.

DATE R5000NI55D AS A VIOLATION:

03JUL85 DATE INVESTIGATED:

05JUL85 DOCUMENT ID 0070h/0250A

.