Change Notice 001 to Rev 1 to Quality Instruction QI-014, Reinsp of Cables/I-E-CABL
ML20203A399
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 03/12/1986
From: Bajada E, Patterson A, Perrino F
EVALUATION RESEARCH CORP.
To:
Shared Package
ML20202J051 List: ... further results
References
QI-014-02, QI-14-2, NUDOCS 8607170228
Download: ML20203A399 (2)


Text

_. _

Pag 2 1 of 2 EVALUATION RESEARCH CORPORATION

,9

'\ )

  • CO N' 10_ _ D COPY CONTROL NO~ 02 mi COMANCHE PEAK RESPONSE TEAM QUALITY INSTRUCTION FOR ISSUE-SPECIFIC ACTION PLAN VII.c CHANGE NOTICE: 001 INSTRUCTION NO: QI-014 REVISION NO: 1 ISSUE DATE: 03/12/86 REINSPECTION OF CABLES /I-E-CABL l

Prepared by:

V h& k. j2spj 1sp v

Date: 3/10fN Approved by: M- M* -

Date:

Issue Coordinator Approved by: [. /

ud/4 Date: $ d!d*d On-Site QA Represe tative

Approved by
4e Date: M '

/

QA ( leview Team Leader stg7t745StBI)$5

Ch2nga Notica 001 QI-014 Rev. I

1. Change Paragraph 5.6 Note 4 to read as follows:
4. Where raceway identification cannot be visually verified, it may be verified by crosschecking the cable and raceway schedule with the raceway drawings. The use of drawings and drawing numbers shall be noted on the Checklist.
2. Change Paragraph 5.111 to read as follows:
1. Where cables terminate on terminal blocks in junction boxes (terminal boxes) that the following criteria is met:

Weidmuller SAK10 shall be utilized when terminating two No. 10 AWG cables. Weidmuller SAK 6N shall be utilized when terminating one cable (No. 10 AWG thru No. 16 AWG) and when terminating two cables (No. 12 AWG thru No. 16 AWG). In any case, the maximum conductor size terminated on Weidmuller terminal blocks shall be No. 10 AWG.