Paga 1 of 23 h

EVALUATION RESEARCH CORPORATION COMANCHE PEAK RESPONSE TEAM QUALITY INSTRUCTION FOR ISSUE-SPECIFIC ACTION PLAN VII.c C0FR0..D CO?Y CONTROL NO.M-M/-

INSTRUCTION NO.: QI-045 REVISION No.:

3 ISSUE DATE:

06/27/86 REINSPECTION OF STRUCTURAL S16EL i

' ~

'Date:

b 80 bb Prepared by:

L.

.t-Approved by:

/ W I_

MO/J

  • 6 WE~b Date:

Issue Cootditutor

~

~7, ll

[#!Z7!$[#

Approved by:g _

D Date:

g On-S e QA Representative

}

- r;! ;

?

Date:

d 27 dd Approved by:

p QA Review Team Leander 8607170075 860711 PDR ADOCK 05000445 A

PDR

s QI-045 Rev. 3 1.0 PURPOSE This procedure provides instructions and accept / reject criteria for the reinspection of structural steel.

2.0 APPLICABILITY This procedure applies to the reinspection of safety significant attributes of safety related hardware within the Structural Steel population at Comanche Peak Units 1, 2 and areas common to both units.

3.0 REFERENCES

3.1 Memo (QA/QC-RT-462) to A. A. Patterson from R. H. Brown delineating documentation used in development of procedure including specific sources for attributes and exclusions.

3.2 CPP-009, " Performance of Reinspection and Documentation Reviews".

3.3 AISC Manual'of Steel Construction 8th Edition (1980) Chicago.

3.4 AISC Manual of Steel Construction 7th Edition (1970) Chicago.

3.5 Brown & Root QI-QP-11.18-4, " Ultrasonic Examination of Hilti Eolts".

4.0 GENERAL 4.1 Responsibilities i

4.1.1 QA/QC Inspectors

(

QA/QC Inspectors perform reinspections in accordance with established project procedures and instructions.

Reference 3.2 addresses the method used to perform reinspections and to document and process the results.

4.1.2 QA/QC Discipline Engineers The QA/QC Discipline Engineers prepare the Quality Instruction delineating reinspection requirements and attributes.

4.2 Policy Activities performed under this procedure shall conform to the policies contained in the latest Comanche Peak Response Team Program Plan and Issue-Specific Action Plan VII.c.

2

i QI-045 Rav. 3 5.0 INSTRUCTIONS 5.1 General (See Notes 1 to 7)

For reinspection, the structural steel item is divided into three subcategories; A) member attributes, B) connection (s) attributes and C) field installed associated detail attributes. Checklists are prepared for each of the subcategories.

(Reference Attachment 6.1)

A.

Member Attributes A1.

Location Verify that the following attributes, where applicable, are located within the tolerance listed in table 5A to the location specified on the design drawings:

a)

Plan Location b)

Elevation c)

Plumb / Level A2.

Size

("'

Verify the member size is as specified on the design drawings. Uce the nominal dimensions of structural shapes as listed in Reference 3.3 or 3.4 for member size comparisoa. Record dimensions used for comparison of structural shapes on Attachment 6.12.

A3.

Material Identification (See Note 8)

Record the material identification, i.e. unique vendor number, heat number and/or QP number on Attachment 6.2.

A4.

Length l

Verify that the member length is as specified on the design drawing to the following tolerance:

For members specified to have both ends with full contact bearing verify only that the gap between the member end and the framing member l

does not exceed 1/32".

All other conditions

[

1 For members up to 30 feet long 1/16" 2

For members longer than 30 feet 1/8" 3

QI-045 Rsv. 3 5.0 INSTRUCTIONS (Cont'd)

O-A.

Member Attributes (Cont'd)

A5.

Orientation Verify visually, that the member orientation is as shown on the design drawing.

i A6.

Field Performed Alterations The removal of material, i.e. cutting, notching, or coping, af ter the initial vendor fabrication, shall be considered a field performed alteration. Additionally, any member site fabricated shall be inspected for the following attributes.

(Site fabrication shall be determined by the QA/QC Discipline Engineer and noted in the remarks section of the checklist under the member attribute heading.)

a.

Location Verify that the location of all field performed alterations are within i 1/8" of the location specified on the design drawing, relative to the member, b.

Size Verify that the dimension (s) of the field performed alteration is less than or equal to the dimensions specified on the design drawings.

c.

Limit of Alterations Verify that the actual alterations are limited to those specified on the design drawings. Attachments to structural steel by other disciplines, i.e..

electrical cable tray supports, HVAC supports etc., shall not be considered an alteration and are outside the scope of this reinspection. However, should a support attachment be encountered during the reinspection, Attachment 6.15 l

shall be completed.

d.

Re-entrant corners l

Verify visually, that all re-entrant corners of field performed alterations are notch-free.

4 l

[

\\

)

QI-045 Rsv. 3 5.0 INSTRUCTIONS (Cont'd)

A.

Member Attributes (Cont'd) e.

Cuts & Holes Verify that all field performed cuts & holes (excluding bolt holes) are without torn or 1

ragged edges.

B.

Connections For each connection to other building elements and member splices, perform the following inspections:

Bl.

Location Verify that the location of the connection component work. points, other than bolts / anchors and/or welds (see sections B4 through B7) relative to the member, is within 1/8" of the location specified on the design drawings.

B2.

Size Verify that the connection components, other than bolts / anchors and/or welds (see sections B4 through O

B7), are as specified on the design drawings. For structural shapes and plate use the nominal dimensions and the standard mill tolerances listed in References 3.3 and 3.4.

Components cut from stock shall have a tolerance of i 1/8" for length and width and + 1/8", -0 for thickness.

B3.

Orientation Verify visually, that the connection is orientated, j

relative to the member, as specified on the design drawing.

B4.

Field Welds l

Prior to the start of inspection assure that welds are clean of any foreign material which would impede an adequate visual inspection. Coatings need not be removed unless an inspector feels that due to excessive and/or uneven coating application he is unable to I

provide an adequate inspection of the weld. Then he shall contact the level III inspector and with his concurrence only then may the coating be removed.

i Where it is necessary to measure weld dimensions during the course of an inspection, such dimensions should be determined as accurately as is practically achievable using standard weld inspection tools.

I i

5 I

r QI-045 Rsv. 3

/~'

5.0 INSTRUCTIONS (Cont'd) k

~

B.

Connections (Cont'd)

B4.

Field Welds (Cont'd)

For welds identified as field welds on the design drawings perform the following tasks.

a)

Location Verify, visually, that the weld location is as specified per the design drawing.

b)

Weld Size Verify that the weld size, meets the requirements of the applicable drawings except that:

Fillet welds may be undersized to a maximum of 1/16" provided that the undersized portion (s) do not exceed 1/4 of the weld length.

Oversized fillet welds shall be l

acceptable if the oversized weld I

does not interfere with mating parts.

For bevel welds which are inaccessible from the back side, the L

weld size shall be verified by assuring that the joint is welded flush except as noted in Attachment 6.13.

c)

Weld Length Verify that the weld length complies with the referenced drawing with the following allowances:

Wald length Permissible Specified on underlength Drawing

<3" 1/8" 23" 1/4" Weld lengths may be longer than specified.

()

The spacing of intermittent welds may vary within 1" of the location specified on the drawing.

6

QI-045 R v. 3

~

5.0 INSTRUCTIONS (Cont'd)

U's B.

Connections (Cont'd)

B4.

Field Welds (Cont'd) d)

Fusion Verify that if any incomplete fusion is visible it complies with the following:

For fillet welds 3/8" maximum incomplete fusion in any 4" segment and 1/4" maximum incomplete fusion in welds less than 4" long.

For groove welds no incomplete fusion is permitted.

e)

Craters Verify that the weld size is met on all welds with underfilled craters. Craters outside the specified weld length are irrelevant provided there are no cracks visible through the coated surface if the weld has been O'

coated or on the uncoated surface if the coating has not been applied.

f)

Wald Profiles l

Verify, visually, that the weld profiles are acceptable per Attachment 6.13.

g)

Undercut Verify that any undercut present does not exceed the following criteria:

For base material 3/8" and less the following requirements apply:

A)

When the member is welded from both sides and the undercut is in the same plane, the following undercut is permittc:.

1) 1/32" for 1/2 the length of the

11) 1/32" for 1/4 the length of the
  • total weld and 1/16" for 1/8 the

()

length of the

l I

l 7

f.

QI-045 Rev. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

  • Total weld equals the cumulative length of both sides.

B)

For all other welds the permitted undercut is:

i) 1/32" for the full length of the weld, or

11) 1/32" for 1/2 the length of the weld and 1/16" for 1/4 the length of the weld.

For base material greater than 3/8" the following requirements apply:

A)

For members welded on both sides, where the undercut is in the same plane the permitted undercut is 1/32" for 3/4 of the length of the veld and 1/16" for the remaining 1/4 of the length of the weld on both sides.

B)

For members welded only on one side or where the undercut is not in the same plane the undercut may be 1/16" for the full length of the weld.

h)

Porosity Considering that only surface porosity whose major surface dimension exceeds 1/16" shall be considered relevant verify the following:

The sum of the diameters of porosity do not exceed 3/8" in any linear inch of weld and shall not exceed 3/4" in any 12" of weld, and If 4 or more pores are aligned the edge to edge separation of the pores shall exceed 1/16".

1)

Overlap If overlap is present verify that the required weld size and the fusion acceptance criteria are met.

If fusion in the overlap length cannot be verified then verify that the overlap length, O

whose fusion cannot be verified, does not exceed 3/8" in any 4" segment or 1/4" in welds less than 4" long.

8

QI-045 Rav. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B4.

Field Welds (Cont'd) j)

Surface Slag Verify that the major surface dimensions of the slag does not exceed 1/8" or 1/4" for any isolated surface slag.

(Slag is considered to be isolated when it does not occur more frequently than once in a 3" weld segment.)

k)

Cracks Verify that there are no cracks visible through the coated surface if the weld has been coated or on the uncoated surface if the coating has not been applied.

1)

Welder ID Symbol When the welders identification symbol (s) is present, record the symbol (s) on Attachment 6.3.

If no symbol is present note " symbol not present" on Attachment 6.3.

B5.

Structural Bolting (See Notes 9, 10 and 11) a)

Bolt Diameter i

Verify, by measurement, that the nominal diameter of the bolt conforms to the bolt diameter specified on the design drawings.

i b)

Material I

Verify, visually, that the bolt material is per the material specified on the design i

drawings. For allowable material substitution, see Attachment 6.4.

Unmarked bolts shall be considered ASTM A307.

l c)

Quantity

[

Verify, visually, that the quantity of bolts conforms to the number of bolts specified on the design drawings.

d)

Washers Verify, visually, that washers or plate washers are installed per the schedule of.5.

9

F QI-045 Rsv. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B5.

Structural Bolting (Cont'd) e)

Beveled Washers Verify, visually, that beveled washers are present for installations with a slope greater than 1:20 with respect to a plane normal to the bolt axis.

f)

Hole Coverage Verify, visually, that washer or plate washer completely covers the hole in the outer plies of the connected parts, g)

Jam Nuts Verify, visually, that jam nuts are present when specified on the design drawings and for

~

high strength bolts with a nominal diameter greater than 7/8" in bearing type connections. In lieu of jam nuts, threads may be upset.

h)

Thread Engagement Verify, visually, that the end of the bolt is flush with or projects beyond the face of the nut.

When standard nuts are used as jam nuts (outer nut) they shall have a minimum thread t

engagement of one half the nut depth.

1)

Edge Distance Verify that the edge distance, measured from the center of the bolt, is equal to or i

l, greater than the dimensions specified on the l

design drawings.

Should a dimension not be specified, the minimum edge distance (s) specified in section 1.16.5 of Reference 3.4 I

shall be followed.

j)

Tightening For unpainted high strength bolts specified for use in friction type connections verify that there is no nut rotation relative to the bolt when the following torque value is O

applied.

10

r QI-045 Rsv. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B5.

Structural Bolting".(Cont'd)

~

ASTM A325 ASTM A490' Bolt Size Torque Torque (Inches)

(Ft. Lbs.)

(Ft. Lbs.)

1/2 65 5/8 160 3/4 271 350 7/8 363 455 1

508 924 1 1/4 1834 1 1/2 3196 For painted connections note in the remarks column that the connection is painted and not verifiable.

For connection specified to be sliding connections, verify only the thread engagement per Eaction h above.

Additional tightness verification is not required.

For bearing type connections and connections >specified O

as snug tight verify that the bolt / nut canno't be rotated by hand and that there are no visible gaps between the connected plies of the connection (tight I

iron condition).

k)

Bearing Verify, visually, that the bolt head and nut '

are square to the connected plies and that there is no visible gap between the bolt head / nut and the outer plies except as allowed in Attribute B5.e.

1)

Spacing Verify that the center to center bolt spacing is within i 1/8" to the spacing shown on the design drawings.

m)

Configuration Verify, visually, that the bolt configuration is as specified on the design drawings.

O 11

QI-045 Rev. 3 5.0 INSTRUCTIONS (Cont'd) v B.

Connections (Cont'd)

B6.

Richmond Inserts a)

Thread Engagement Verify the thread engagement for Richmond inserts is at least 2 times the bolt diameter plus l'/8 inch. Thread engagement shall be calculated as shown below using bolt length specified on the design drawing. Where bolt / stud length is not specified on the design drawing, the length shall be determined by an ultrasonic examination performed by Brown and Root in accordance with Reference 3.5.

This information shall be transmitted to the inspector by Brown and Root in writing. The inspector shall include this report in the reinspection package and based on this information verify the thread engagement per the sketches shown below.

i O

12

a QI-045 s

s Rav. 3 5.0 INSTRUCTIONS (Cont'd)

O

'B.

Connections (Cont'd) i s

B6.

Richmond Inserts (Cent'd) i w

A socrs 6%

g mua g

msu q N:

I ii}:. %,<.'. ?..;

k%%%%%%%%3* W Nhsssssss x

N W

a O

z.,.-

.d

.A

, l*..' s',

l e

.;.-e.,.

6 M

G E

} 'Lw u

RICHMOND INSERTS 0NLY i

L Thread engagement (E) - L - (B + W+ M + G)

Where:

B = thickness of bolt head, in.

W = thickness of washer stack, in.

M = thickness of material, in. (i.e., baseplate, tube steel, etc.)

G = thickness of grout, in. (where applicable)

L = overall length, in. (if from design drawings; B-0)

~

l e

13 l

QI-045 Rav. 3 O

5.0 INSTRUCTIONS (Cont'd)

U B.

Connections (Cont'd)

B6.

. Richmond Inserts (Cont'd) 57005 METLith

.a..

... e.

W*%ut.

,A,

\\

p

' ', ),'

  • ?; *.' ;, 9., _.
  • ""~L:###########

(#N#NHN###NA yg; w _:. -l:. 9;.':_.C."

d

. +., '. ;,,

.,.1

  • b.

Q-5-

%)

.,.t. * -

T 4

M G

l E

bW

(

l RICHMOND INSERTS ONLY i

l l

l Thread engagement (E) = L - (T + N + W + M + G) l Where:

i.

T = extension from top of nut, in.

N = thickness of nut, in.

W = thickness of washer stack, in.

M = thickness of material, in. (i.e., baseplates)

G = thickness of grout, in. (where applicable) l L = overall length, in. (from Bill of Materials) l b)

Tightness Verify that the nut / bolt cannot be rotated by hand and that there are no visible gaps between the connected plies of the connection (tight iron O

condition).

14

QI-045 Rev. 3 5.0 ' INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B6.

Richmond Inserts (Cont'd) c)

Washer Verify, visually, that there is a washer, which completely covers the hole in the outer ply of the connection, under the turned element.

d)

Verify that the location of the Richmond Insert (s) is within 1/8", relative to the member, to the location specified on the design drawing.

e)

-Verify that the edge distance, measured from the center of the Richmond Insert (s) is equal to or greater than the dimensions specified on the design drawings. Should a dimension not be specified, the minimum edge distance (s) specified in section 1.16.5 of Reference 3.4 shall be followed.

()

B7.

Concrete Expansion Anchors (HILTI)

B7.1 Size and Number of Anchors a)

Verify, by measurement, that the nominal anchor bolt diameter is as specified on the design drawing.

b)

Verify type, length and number of anchors installed match those shown on the Design Drawings.

Determine anchor bolt length by the letter designation stamped on the top of the bolt (Attachment 6.6).

Super kwik bolts are identified by a star in addition to the letter designation.

  • If length identification is not verifiable or visible, an ultrasonic examination shall be performed in accordance with Reference 3.5 (Brown and Root shall perform UT and provide a copy of the results to the O

inspector for inclusion in the Verification Package). Once 15

QI-045 Rav. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B7.

Concrete Expansion Anchors (HILTI) (Cont'd) ultrasonic examinatien is complete, record actual length on inspsetion checklist, and initiate a deviation repert, if unacceptable.

B7.2 Embedment Length Verify that the Hilti anchor bolt embedment plus the nut thickness (from Attachment 6.6) for the anchor being measured is not less then the "Embedment Length" or " Minimum Embedment Length" identified on the drawings; or lacking such information the " Minimum Embedment" identified on.6.**

Determine the Hilti anchor bolt embedment by measuring the projected length of the anchor bolt from the structural concrete

  • surface.

Subtract the anchor projected length from designated anchor length to arrive at the Hilti anchor bolt embedment. The designated anchor length is that O

shown on Attachment 6.6 unless the stamp is indistinguishable in which case the U.T. recorded length should be used.

  • NOTE:

In floor and roof areas where topping has been placed, the thickness of the topping shall be taken into account in determining the projected length. In these areas the thickness of the topping shall be added to measured length taken from the concrete surface. The inspector shall ensure that measurement for topping is provided on the inspection checklist for all roof and floor slabs.

    • NOTE: When the letter designation stamped on Hilti bolt is not identified by Attachment 6.6, the following Hilti bolt attributes regarding length of Hiltis can conservatively be inspected by using Attachment 6.16.

B7.3 Bolt Spacin,*

a)

Verify for each Hilti, center-to-center spacing of adjacent anchors of the same size (not on the same attached element) is not less than 10 anchor diameters unless specified on design drawing. For unequal 16

QI-045 Rsv. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B7.

Concrete Expansion Anchors (HILTI) (Cont'd) sized bolts, the minimum spacing (unless shown on design drawing) is as shown on.7.

b)

Verify spacing of each Hilti to existing Richmond inserts, concrete edges, abandoned holes, Hilti anchors or embedded anchor bolts that have been cut off meet the minimum spacing requirements specified in Attachment 6.8 unless shown on design drawing, c)

Verify that the minimum distance of each Hilti anchor to any adjacent embedded plate meets the following requirements of

'.9.

Attachments located within 12 inches of a Hilti anchor bolt shall have spacing as shown on Attachment 6.9.

Os For embedment plates without any attachment within 12 inch clearance distance, the anchor may be as close as practical to the edge of the plate without damage to the plate.

B7.4 Angularity Verify each Hilti anchor installed has its longitudinal axis within 6' from the perpendicular of the surface it is set into. Attachment 6.10 gives inspection requirements.

B7.5 Concrete Damage Verify structural concrete surrounding the fixture is not broken or spalled as a result of installing the Hilti anchor. If spalling exists, verify the depth does not exceed the following:

M'ximum Acceptable a

Hole Size Spall Depth

  • 5/8 inch and under i inch 3/4 inch to 11 inch inclusive 3/4 inch

()

  • If the area in question includes a topping the maximum spall depth may be increased to the depth of topping.

17

Ql-045 Rev. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

B7.

Concrete Expansion Anchors (HILTI) (Cont'd)

B7.6 Nut Engagement and Bearing a)

Verify nut of each Hilti anchor has proper engagement such that the end of the anchor bolt is not lower than the top of nut, unless otherwise shown on the Design Drawing.

b)

Verify nut and washer of each Hilti anchor has proper bearing and that a minimum of one washer (stendard or plate) has been provided. The washer shall completely cover the hole in the base plate. A level gauge shall be used for determining if the gap is less than 1:20 (Attachment 6.11).

c)

Verify that the nut for each anchor has not bottomed out.

Use thread length in.6 (or Attachment 6.16 if information is not shown on Attachment 6.6) and measured projection to determine acceptance.

d)

Verify no visible weld has been made to anchor or nut.

B7.7 Configuration a)

Verify that the location of the Hilti(s) is within 1/8", relative to the member, to the location specified on the design drawing.

b)

Verify that the edge distance, measured from the center of the Hilti, is equal to or greater than the dimensions specified on the design drawings. Should a dimension not be l

specified, the minimum edge distance (s) specified in section 1.16.5 of Reference 3.4 shall be followed.

B8.

Baseplates Verify by measurement that baseplates fit flush against the mating surface. The fc110 wing is acceptance criteria where baseplates are not flush:

The gap between the plate and concrete for a s

i maximum of 20% of the plate perimeter may exceed 1/16 inch, but at no point shall the gap exceed 1/2 inch.

18

QI-045 Rsv. 3 5.0 INSTRUCTIONS (Cont'd)

B.

Connections (Cont'd)

If the above acceptance criteria is not met, the inspector shall, using a gage, map gap depth beneath the baseplate and determine if the area exceeding 1/16" gap is limited to less than 20% of the baseplate area. If verified, the attribute is acceptable.

B9.

Grout 4

Verify, visually,.that grout is installed when specified on the design drawings.

I' C.

Field Installed Associated Details Field installed associated details include cover plates, side plates stiffeners, or other material which were added after j

the initial vendor fabrication. Additionally, any member which was site fabricated and includes any associated details shall be inspected for the following attributes.

(Site Fabrication shall be determined by the QA/QC Discipline Engineer and noted in the remarks section of the checklist under the field installed associated details heading.) These

( Os items may have been given a unique piece mark list for fabrication, however they are to be considered part of the main member for reinspection.

C1.

Location Verify that the location of the field installed associated detail, relative to the member, is within 1/8" of the location specified on the design drawing.

C2.

Size Verify that the size of each component is as shown on the design drawing. Use the nominal dimensions and the standard mill tolerances listed in Reference 3.3 or 3.4 for member size comparison. For items cut from stock the tolerance for width and/or length shall be i 1/8" and + 1/8", -0" for thickness.

C3.

Orientation Verify, visually, that the field installed associated detail is oriented, relative to the member, as shown on the design drawing.

C4.

Weld Verify, visually, welds in accordance with Section B4.

19

e i

QI-045 Rsv. 3 1

5.0 INSTRUCTIONS (Cont'd) 1 4

C.

Field Installed Associated Details (Cont'd) i C5.

Bolting Verify bolting in accordance with Section B5.

NOTES:

1.

Design drawings shall include; the G&H drawings and associated open design changes. Vendor and/or B&R erection / shop drawings, when included in.the reinspection package, are for reference and for dimensions and details not shown on the design drawings.

Should a conflict exist between the design drawings and the vendor /B&R drawings, the design drawings shall govern.

2.

Tolerances, if specified on design drawings, shall be used if there j

is a conflict with this procedure.

3.

Inaccessible items shall be indicated in the remarks column of the Reinspection Checklist.

4.

In the course of inspection the inspector shall note any item not covered by reinspection which appears out of the ordinary as O

related to the construction of the inspected item or surrounding area. Note such in the remarks column of the reinspection checklist.

I 5.

Inspector shall record the Tool Code (Attachment 6.14), serial number, calibration due date as applicable on Attachment 6.14.

I 6.

Dimensions shall be measured to the nearest 1/16", unless otherwise specified.

l 7.

Angles shall be measured to the nearest degree.

8.

Material identification may have been painted on the member, and would no longer be verifiable if the member has been field painted.

9.

Material for structural bolts shall be ASTM A325 unless specified otherwise on the design drawing.

10. All bolted connections are bearing type unless noted otherwise on the design drawings.
11. High strength bolts are designated ASTM-A325, ASTM-A490, or ASTM-A449.

O 20

~.

i QI-045 Rsv. 3 TABLE SA Location Tolerance I

MEMBER TYPE PLAN LOCATION ELEVATION PLUMB / LEVEL (Inch)

Platform *

!1/8 2 3/4 1:500 plumb (Work point.to work point) for vertical members. 1/4" difference between ends for horiz.

members Horizontal 1/8" dif-Length 530' 1/8 2 1/8 ference be-Length M0' i 1/4 1 1/4 tween ends Vertical Length 530' i 1/8 1 1/8 1:500 (1/4"

[

in 10'-5")

i Length M0 '

i 1/4 1 1/4 1:::00 (1/4" in'10'-5")

Stairways

!2 1 3/4 t 1/4 Vertical Bracing Length 530' 21/8 11/8 N/A Length 40' 11/4 1/4 N/A

)

  • Plan location of platform assembly may vary il" from specified location.

l O

21

,---,.y

--,,.--n.-,

,n,__,mve,y

.--,__,.__,,.,mm,

QI-045 Rav. 3 p

6.0 ATTACHMENTS U

6.1 Reinspection Checklist 6.2 Material Identification Record i

6.3 Welder Identification Record 6.4 Allowable Bolt Material Substitution 6.5 Washer Requirements i

6.6 Hilti Anchor Designation and Setting Requirements 6.7 Minimum Spacing Between Hilti Expansion Anchors 6.8 Minimum Anchor Clearances 6.9 Minimum Clearances to Embedded Plates 6.10 Anchor Angularity 6.11 Nut Bearing 6.12 Structural Shape Dimension Record 6.13 Weld Profile 6.14 Inspection Tool Log 6.15 Support Attachment Record 6.16 Hilti Length Identification System

' O I

22

Attachtsnt 6.1 QI-045 Rev. 3 Page 1 of 6 COMANCHE PEAK RESPONSE TEAM CHECILIST POPULAn0N DESC VERIFICATION PKG NO.

STRUCTURAL STEEL I-S-STEL PAGE 1 0F 1 QUALIn INSTRUCTION hREINSPECTION O cut: t QI-045 EQUIPMENT MARK / TAG NO.

O occ:wEurittow RIvtIn O cutt 2 O coxxon VERITICATION A U II M ACCIPT REJECT DATE A Member N/A Information lisader A1) Location A2) Size Information Only A3) Material Ident N/A.2 A4) Length A5) Orientation A6) Alterations N/A Info rmation Header a) Location b) Size c) Limit of Alteration i

d) Re-entrant Corners e) Cuts and Holes I

l l

l l

PREFARED BT:

APPROTED BT l

DISCIPLINE ENGR.

DATE LEAD DISCIPLINE ENGR.

DATE insrtutr.u BT APPROVED BT ind r EL wn DATE LEAD INSPECTCR DATE C?P-007.lA. Revision 0

Attcchmsnt 6.1 QI-045 Rev. 3 (O

, )

4 COMANCHE PEAK RESPONSE TEAM CHECK!,IST POPULAT*,0N DESC VERIFICATION PKG NO.

STRUCTURAL STEEL I-S-STEL FAGE J 0F J VERIFICATION 3

ACCEPT REJECT DATE B Connection N/A Informati<n Header B1) Location B2) Site B3) Orientation B4) Walde N/A Informatise Reader a) Location b) Weld Site c) Weld Lenath j

d) Fusion e) Craters f) Weld Profiles a) Undereut h) Forosity l

i) Oserlas I

1) Surface Slaa k) Cracks Information Only
1) Welder ID S; i:1 N/A.3 B5) Structural Boltina N/A 1 aformatim Reader a) Bolt Diameter b) Material l

c) Quantity

.k

. ? d'?*. $ *.O n '}

2

Attcchment 6.1 QI-045 Rev. 3

'J COMANCHE PEAK RES?ONSE TEM 4 CHECKLIST POPl!LA!ICN DESC VERIFICATION PKG NO.

STRUCTURAL STEEL I-S-STEL PAGE J0F _6 t

VERIFICATION AW5ME REMARKS ACCIPT REJECT DATE B5) Structural Bolting (Cont'd) d) Washers e) Beveled Washore f) Hole Coverase a) Jan Nute h) Thread Enassement i) Edae Distance j) Tiahtenina i

k) Bearina

'd

1) Spacina a) Configuration B6) Richmond Inserto N/A informati'm Header e) Thread Enneassent b) Tiahtnese c) Washer d) Location e) Edge Distance
87) Concrete Espansion Anchore N/A i nformatim Header B7.1 Size and Number a) Diameter f

b) Type. Length.

Number 4

I C ? -00 7. ( *. 8.ev. nan 0 s

i i

3

Att:chment 6.1 QI-045 Rev. 3

\\

\\v/

i COMANCHE PEAK RESPONSE TEAM CHEC'4:.IST VER; FICA!;oN FKG No.

POP'AA!;03 DESC PAGE 40F 6

I-S-STEL I

STRUCTURAL STEEL VERIFICATION

^#EI ACCEPT REJECT 3 ATE B7.2 Embedeent Lenath N/A Informati<o Header 87.3 Bole Specina a) Center to Center Specins b) Hilti to Richmond c) Hilti to Embed Plates i

1 57.4 Anaularity 57.5 Concrete Dessas (j)

B7.6 Nut Engagement and Bearina N/A Informatiim Header i

a) Nut Enssaesent t) searina c) Bottoe-out d) Weld 37.7 Confituration N/A: aforesti m Header a) Location b) Edme Distance

88) Basesistes
89) Crout i

a s

    • 8 8=

d"'e M e

^)

6 a

4

-. _ ~..... _ _... _

Attcchment 6.1 QI-045 Rev. 3 O

COM.0;CHE PEAK RESPONSE TEAM CHECIL:ST F0PT A! ION DESC VER;FICATION PKG NO.

STRUCTURAL STEEL I-S-STEL PAGE J OT _6 VERIFICATION

^

RZMARXS ACCEPT REJECT DATE l

C) Tield Installed Detaile N/A Informatiqn Header Cl) location C2) Site C3) Orientation C4) Weld N/A Information Header a) location b) Weld Site c) Weld Lenath f

d) Fueton L

e) Cratere f) Weld Profiles a) Undercut h) Porosity

1) Overlap
1) Surface Slaa k) Cracke information Only
1) Weider ID Symbol N/A.3 C$) Boltina N/A

.nformati pn Reader a) Bolt Dieseter b) Material e) Quantity

??. 'o :.:. '..:s;3n )

5

Attechm:nt 6.1 QI-045 Rev. 3

,e i

COMANCHE PEAK RESPONSE TEAM CHECKI,IST POPLUTION DESC

'iER;IICA!!ON FKG NO.

j l

STRUCTURAL STEEL I-S-STEL PACE J 0F _6 VERIFICATION I

^

IN3 ACCEPT REJECT DATE C5) Bolting (Cont'd) l d) Washers t

e) Beveled Washers f) Hole Coverage I

I a) Jan Nute f

h) Thread Ensasement i) Edae Distance

1) Tiahtenina k) Bearina
1) Specina a) Confiauration i

i i

i l

}

i 4

??-'o?. i3. 'c uun 1 I

\\

l 1

6 f

-n----,,nn,n-~=-~r-.-,..,-,--e.n.

-v--

x r--vw----.m

~~---r---m

--*www-

~we-w~-"~=

  • ~ ~ ~~~'

' ' ~ ' "

Attachant 6.2 QI-045 l

Rev. 3 Page 1 of 1 Tl-COMANCHE PEAK REVIEW TEAM j

INSPECTION CHECKLIST VERIFICATION PACKAGE NO.

I-S-STEL MATERIAL IDENTIFICATION RECORD DESCRIPTION IDENTIFICATION INFORMATION 1

f i

4 1

4 J

i l

1 a

I i

l r

Inspector Date i

--,.==,,,==*-ween---=-ww-=,=-ww-we,

-e-.

.++ e w*Wre*-7'

--er.-

Attachssnt 6.3 QI-045 Rev. 3

^

COMANCHE REVIEW TEAM INSPECTION CHECKLIST WELDER IDENTIFICATION RECORD VERIFICATION PACKAGE NO. I-S-STEL WELD LOCATION WELD IDENTIFICATION i

O f

l O

INSPECTOR DATE

Attachmsnt 6.4 QI-045 Rev. 3 ALLOWABLE BOLT / MATERIAL SUBSTITUTION SPECIFIED ALLOWABLE SUBSTITUTION REFERENCE MATERIAL ASTM A325 SA-193 Grade B threaded rod with DCA #7974 (For Richmond ASME SA-194 double nuts

.Rev. 13 inserts only)

ASTM A325 ASTM A449 DCA #7974 Rev 13 4

i 1

i O l

(

l l

0

Attechm2nt 6.5 QI-045 a

  • Rev. 3 WASHER REQUIREMENTS

~

i CONNECTION TYPE WASHER REQUIREMENTS

& BOLT MATERIAL All but slotted holes / ASTM A490 Washer under bolt head & nut Friction / ASTM A325 Washer under turned element Slotted Hole /All 5/16" min. thickness, plate washer or continuous bar.

4 i

All Others Washer under turned element

)

O 1

I I

O

Attcchment 6.6 QI-045 Rev. 3 Page 1 of 2

(

HILTI ANCHOR DESIGNATION AND SETTING REQUIREMENTS Minimum Embedment (Before Torque)

Stamp on Actual Length Nut Anchor Bolts Sizes KWIK Super Kwik of Threads Thickness A.

1/4 x 1 5/8 1 1/8 3/4 7/32 B.

1/4 x 2 1/4 1 1/8 3/4 7/32 3/8 x 2 1/8 1 5/8 7/8 11/32 J

C.

3/8 x 2 3/4 1 5/8 7/8 11/32 1/2 x 2 3/4 2 1/4 1 1/4 7/16 D.

1/4 x 3 1 1/8 3/4 7/32 E.

1/4 x 3 1/2 1 1/8 3/4 7/32 3/8 x 3 1/2 1 5/8 1 1/8 11/32 1/2 x 3 3/4 2 1/4 1 1/4 7/16 5/8 x 3 1/2 2 3/4 1 1/2 17/32 F.

3/4 x 4 1/4 3 1/4 1 1/2 5/8 G.

5/8 x 4 1/2 2 3/4 1 1/2 17/32 3/4 x 4 1/2 3 1/4 1 1/2 5/8 3

H.

3/8 x 5 1 5/8 1 1/8 11/32 I.

1/2 x 5 1/2 2 1/4 1 1/4 7/16 3/4 x 5 1/2 3 1/4 1 1/2 5/8 J.

5/8 x 6 2 3/4 1 1/2 17/32 1x6 4 1/2 2 1/4 27/32 K.

L.

1/2 x 7 2 1/4 3 1/4 1 1/4 7/16 i

l 3/4 x 7 3 1/4 1 1/2 5/8 l

1x7 4 1/2 2 1/4 27/32 l

M.

l N.

1 1/2 17/32 O.

5/8 x 8 1/2 2 3/4 3/4 x 8 1/2 3 1/4 1 1/2 5/8 P.

1/2 x 9 3 1/4 1 1/4 7/16 1x9 4 1/2 6 1/2 2 1/4 27/32 3 1/4 1 1/32 1 1/4 x 9 5 1/2 Q.

Attech=nt 6.6 l

QI-045 Rev. 3 HILTI ANCHOR DESIGNATION AND SETTING REQUIREMENTS Minimum Embedmont (Before Torque)

Stamp on Actual Length Nut Anchor Bolts Sizes KWIK Super Kwik of Threads Thickness R.

1/2 x 10 2 1/4 1 1/4 7/16 3/4 x 10 3 1/4 1 1/2 5/8 S.

3'1/4 11/4 7/16 T.

1/2 x 12 1 x 12 4 1/2 6 1/2 2 1/4 27/32 1 1/4 x 12 5 1/2 8 1/8 3 1/4 1 1/32 U.

I x 13 1/2 4 1/2 6 1/2 2 1/4 27/32 1 1/4 x 13 1/2 5 1/2 8 1/8 3 1/4 1 1/32 y,

6 1/2 2 1/4 27/32 W.

1 x 15 1 1/4 x 15 5 1/2 8 1/8 3 1/4 1 1/32 K.

1 1/4 x 16 1/2 5 1/2 8 1/8 3 1/4 1 1/32 o

T.

Z.

1 1/4 x 18 5 1/2 8 1/8 3 1/4 1 1/32 8 1/8 3 1/4 1 1/32 DD.

1 1/4 x 22 8 1/8 3 1/4 1 1/32 EE.

I 1/4 x 23

  • Bolts of 19-inch length and greater may be stamped with number corresponding to the bolt length in inches in the same manner instead of the stamped letters as listed below.

l0 l

{

Attcchment 6.7 QI-045 Rev. 3 Page 1 of 1 p

MINIMUM SPACING BETWEEN HILTI EXPANSION ANCHORS

  • Hilti Anchor 1/4" 3/8" 1/2" 5/8" 3/4" 1"

1 1/4" Size Hilti Hilti Hilti Hilti Hilti Hilti Hilti 1/4 2 1/2 3 1/8 3 3/4 4 3/8 5

6 1/4 7 1/2 5/16 2 13/16 2 7/16 4 1/16 4 11/16 5 5/16 6 9/16 7 13/16 3/8 3 1/8 3 3/4 4 3/8 5

5 5/8 6 7/8 8 1/8 1/2 3 3/4 4 3/8 5

5 5/8 6 1/4 7 1/2 8 3/4 5/8 4 3/8 5

5 5/8 6 1/4 6 7/8 8 1/8 9 3/8 3/4 5

5 5/8 6 1/4 6 7/8 7 1/2 8 3/4 10 7/8 5 5/8 6 1/4

' 6 7/8 7 1/2 8 1/8 9 3/8 10 5/8 1

6 1/4 6 7/8 7 1/2 8 1/8 8 3/4 10 11 1/4 1 1/4 7 1/2 8 1/8 8 3/4 9 3/8 10 11 1/4 12 1/2 V

Dimension in inches.

  • The minimum spacing outlined in the above chart applies to Hilti anchors detailed on separate adjacent fixtures.

Hilti bolts details on an individual fixture drawing may have less than the minimum spacing tabulated above.

i l

I i

_ _. _ = _ _ _ _. _ _ _.. _ _ _ -. _. - - -. _ -. _ _..

Attcch2cnt 6.8 QI-045 Rev. 3 Page 1 of 1

()

MINIMUM ANCHOR CLEARANCES

  • i MINIMUM DISTANCE TO i

Abandoned Hilti Anchors or l

Hilti Richmond Screw Anchors Concrete Edge

  • Holes and Embedded Anchor Anchor Size 1-inch 1 1/2-Inch (Note 1)

Bolts that are Cut Off**

1/4 7 5/8 12 1/4 1 1/4 1/2 3/8 8 1/4 12 7/8 1 7/8 3/4 1/2 8 7/8 13 1/2 2 1/2 1

5/8 9 1/2 14 1/8 3 1/8 1 1/4 i

3/4 10 1/8 14 3/4 3 3/4 1 1/2 j

1 11 3/8 16 5

2 1 1/4 12 5/8 17 1/4 6 1/4 2 1/2

+

}

i i

  • Neasured Center-to-Center of anchors and anchor center to edge of concrete in inches.

l

    • Minimum spacing between holes covered by this column shall be measured center-to-center i

and based on size of hole being drilled.

(e.g., Pilot hole spacing is based on pilot l

bit size.)

i

{

Hilti bolts may be installed as close as practical to unused Richmond Screw Anchors which j

h:ve been plugged (i.e., grouted Richmond Screw-in plus or snap-in plus, etc.).

NOTE 1: Where embedded angles are used for framing water tight door or removable block I

w211 openings, the minimum clearance from center line of Hilti anchor to the opening edge is 5 inches + 5 times the Hilti anchor diameter.

i 4

l i

i l

l l0 i

I

Attcch3:nt 6.9 QI-045 Rev. 3 Page 1 of 1 O

MINIMUM CLEARANCES TO EMBEDDED PLATES Where the embedded steel plates are occupied by attachments within minimum distances shown below, the minimum clearance to Hilti Anchors shall be as follows:

Hilti Anchor Nelson Stud Edge of Plate Size to Hilti Anchor to Hilti Anchor l

1/4 5 1/4 3 3/4 3/8 5 7/8 4 3/8 1/2 6 1/2 5

5/8 7 1/8 5 5/8 3/4 7 3/4 6 1/4 1

9 7 1/2 1 1/4 10 1/4 8 3/4 i

Dimensions are in inches.

Distance measured with reference to center of bolts and studs.

Where location of the nearest Nelson Stud can be determined from the "S" stamps O

on the embedded steel plate, the minimum center-to-center clearance to the Hilti Anchor as shown above shall govern. Where location s' the nearest Nelson Stud cannot be so determined, the minimum clearance to Edge of Plate as shown above shall govern.

i O

Atta.hma.t 6.10 QI-045 Rev. 3 0 -

Page 1.f 1 ANCHOR ANGULARITY ANGLE GREATER THAN O'

.. ANCHOR IS LESS THAN 6

  • OUT OF PLUMS.

l PLUMENESS GAGE

  • STAMP ON i

GAGE i

SURFACE OF 6*#

ANCHORED PLATE 1

j

/

?,

kr I 3

/

{

r

!u

,L

' SPACER PLATES

}

I I

O u.. em....es.........,1.

. 1.

1. e...

1 1.........,1.... 1. 1,.

Attachmant 6.11 QI-045 Rev. 3 NUT BEARING 2

B'kVEL GAGE (OEE SKETCH BELOW) i 5

ANGLE GREATIR I

THAf4 0*.*. CONTACT BEVELED WASHER IS UNACCEPTABLE

\\

I l

l X,.


- S ).

f s

s 3,

~

I ll I

l i O.

I GAGE FCR EACH k

BOLT DLAMETER 3;T N,N,4,%',54; Wi SOLT DIA.+k.<. 96 - k+ ' 6

,s o (..

N, 1

0

Attechant 6.12 QI-045 Rev. 3

^

STRUCTURAL SHAPE DIMENSION RECORD t

VERIFICATION PACKAGE NO. I-S-STEL I

=

t II w

w I

l f

[

e d

ts b

1

,l I

'it f

b p

d d

I ---

A y

M

\\

I bi br U

d t

f f

t, SHAPE DESIGNATION O

Attacha2nt 6.13 QI-045 Rev. 3 FILLET WELD PROFILES

.i t

)

.=

f' i

Do not mensure ss\\

i Y

i B

Acceptable Convexity l

l l

g Acceptable concavity s

n _. 's e

i i

O

Attachm2nt 6.13 QI-045 Rev. 3 cRooVE WELD PROFILES

- Do not measure o

9

's D

Acceptable Convexity

- 1/32 (Underfilled)

I I

/

b I

l Acceptable Concavity or Underfi11 l

1/32 -

Grinding Depression l

l lI 5

ll

\\

]

~

t/

i 2

\\

/

t i v-u a

1 1

Acceptable 2

1

Attachm2nt 6.13 QI-045 Rev. 3 O

FLARE BEVEL PROFILE N-

- '1/32 i '

j

(

I l

Acceptable *

  • NOTE: The profile show in acceptable for flare bevel welds specified to be flush. If other fill requirements are specified, refer to project specifications for acceptance requirements.

l 3

l-

Attechaint 6.14 QI-045 Rev. 3 Page 1 of 2 INSPECTION TOOL LOC O

ATTRIBUTE CODE SER. #/CALIB. DUE DATE A Member A1) Location A2) Size A3) Material Ident A4) Lenath A5) Orientation A6) Alterations B Connection B1) Location i

B2) Alterations B3) Orientations B4) Welds B5) Structural Boltina B6) Richmond Inserts B7) Concrete Expansion files Anchors B8) Baseplates C) Field Installed Details C1) Location 1

C2) Size C3) Orientation C4) Weld CS) Bolting O

Inspector Date

Attschment 6.14 QI-045 e

Rev. 3 INSPECTION TOOL AND CODES CODE TOOL AF ANGLE FINDER BL BUBBLE LEVEL BS BOROSCOPE BW 1/32", 1/16", 3/32", 1/8" WIRE CG CONTOUR GAGE DF DRY FILM THICKNESS GAGE FG FEELER GAGES FL FLASHLIGHT FM FIBRE METAL FILLET GAGES GG GAL FILLET GAGES HL HI-LOW GAGE MG MAGNIFYING GLASS MI MICROMETERS MM MIRROR MN MAGNET PB PLUM BOB PR PROTRACTOR SC SLIDE CAUPER SR 6" RULE ST STEEL TAPE MEASURE TG TAPER GAGE TW TORQUE WRENCH UD UNDERCUT GAGE (DIAL)

UP UNDERCUT GAGE (PIT)

VC VERNIER CALIPER VT INSPECTION O

2

Attachmant 6.15 QI-045 Rev. 3 Page 1 of 1 O

SUPPORT ATTACHMENT RECORD VERIFICATION PACKAGE NO.

I-S-STEL SUPPORTED ELEMENT TYPE LINE DESIGNATION COMMENTS O

O Inspector Date

--,,n,---

-, ~ -

4 Attachnsnt 6.16 QI-045 Rsv. 3 Page 1 of I HILTI LENGTH IDENTIFICATION SYSTEM Stamp On Length of Anchor Anchor (Inches)

A 1 1/2 B

2 C

2 1/2 D

3 f

E 3 1/2 F

4 G

4 1/2 H

5 I

5 1/2 J

6 K

6 1/2 L

7 M

7 1/2 N

8 0

8 1/2 P

9 Q

9 1/2 R

10 S

11 T

12 O

U 13 V

14 W

15 I

16 Y

17 Z

18

  • To be used for checking embedment length only STANDARD HILTI DATA l

Minimum Embedment Length of i

Bolt Diameter KWIK (before torque Threads 1/4 1 1/8 3/4 l

3/8 1 5/8 varies t

1/2 2 1/4 1 1/4 5/8 2 3/4 1 1/2 l

3/4 3 1/4 1 1/2 l

1 4 1/2 2 1/4 1 1/4 5 1/2 3 1/4 O