ML20135A797

From kanterella
Jump to navigation Jump to search
Forwards Rev 1 to Methodology for Evaluation of Fire Resistance of Structural Steel, Vols 1 & 2.Calculated Area Fire Durations & Temp Exceeded Structural Steel Temp Acceptance Criteria
ML20135A797
Person / Time
Site: Peach Bottom  
Issue date: 03/29/1985
From: Boyer V
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Thompson H
Office of Nuclear Reactor Regulation
Shared Package
ML20135A801 List:
References
NUDOCS 8509100277
Download: ML20135A797 (4)


Text

,

?

gg PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET PHILADELPHI A, PA.19101

v. s.3_

MAR 291985 Mr. Hugh L. Thmpson, Jr.

Docket Nos.

50-277 Division of Licensing 50-278 U.S. Nuclear Regulatory Conmission Washington, DC 20555

SUBJECT:

Peach Bottom Atomic Power Station, Units 2 and 3 Structural Steel Survivability Analysis

REFERENCE:

(1) Letter V. S. Boyer to D. G. Eisenhut dated Septonber 16, 1983 (2) Letter V. S..Boyer. to D. G. Eisenhut dated January 16, 1985

Dear Mr. Elsenhut:

As stated in the Reference (2) letter, Phliadelphia Electric Cmpany proposed to submit the Peach Bottcm Structural Steel Survivability Analysis on April 1, 1985. Enclosed for your review is that analysis (Attachment #1). The analysis is based on the same methodology that was used at PECo's Limerick Generating Station. The Limerick analysis was approved by the NRC in the Limerick Safety Evaluation Report.

Ninety plant areas have been evaluated in the Units 2 and 3 Reactor Buildings, the Radwaste Building and the Turbine Building.

A review of the calculation sunmary rmeealed that 13 calculations representing 27 plant areas had area fire durations and temperatures which exceeded the structural steel t mperature acceptance criteria.

Additionally, the calculations indicated that we had 60 cases of failure due to localized heating effects in 16 plant areas. We have enclosed (Attachment #2) a detailed discussion of the problem areas and the alternatives we are considering to correct any structural steel fire protection deficiencies.

The corrective actions we plan to take and any calculation refinements, if necessary, will be transmitted to you within 60 days.

k 7 0 '.

g y p,(e *

/CY 3HX IC'f t.Polt

'CY 8509100277 850329 M

PDR ADOCK 05000277 F

PDR

ggc, icy u

G Ge%

L

w We are anxious to discuss our proposed alternatives / actions with your staff and request that a meeting be scheduled at your convenience to discuss thaan.

A'a SXf f l'l[ tr <!w GJR/cb/03278502 Enclosures Copy to:

T. P. Johnson Site Resident inspector l

k-

Attactwnent #2 Discussion of Structural Steel Problem Areas The structural steel survivability analysis identified 27 plant areas which had expected fire durations and structural steel tenveratures which did not meet the steel temperature acceptance criteria. The areas are as follows:

1.

Radwaste Building, el. 135, Medical Station and Corridor, calc. #10 2.

Radwaste Building, el. 135, Unit 2 M-G Set Room, calc. #19 3.

Turbine Building, el. 135, Emergency switchgear Rooms (8 rooms), calc. #20 4.

Radwaste Building,~ el. 165, Fan Room (Remote Shutdown Panel Area), calc. #22 5.

Cire. Water Punp House, High Pressure Service Water Ptsnp Bay (2 rooms), calc. #26 6.

Diesel Building, Diesel Generator Rocms (4 rocms), calc. #27 7.

Diesel Building, Cardox Rocrn, calc #28 8.

Reactor Building, el. 88, Unit 2 HPCI Room,-calc. #30 9.

. Reactor Building,' el. 88, Unit 3 HPCI Room, calc. #35 10.

Reactor Building, el. 91-6, Unit 2, C RHR Ptsnp and HX Room, calc. M7-11.

Radwaste Building, el. 135, Unit 3 M-G Set, calc. #53 12.

Radwaste Building, el. 135, Radwaste Control Room, calc. #54

13. Turbine Building, el 135, Battery Rocm (4 rooms), calc. #90 The obvious fix for each of these areas is to provide structural steel fire proofing or area sprinkler protection, however, other alternatives / considerations are being reviewed for several plant areas.

a.

The HPCI rorms and the Diesel Generator Rocms are provided with automatic total flooding carbon dioxide systems.

Detection and automatic operation of the carbon dioxide system will be sufficient to control / suppress any fire until the fire brigade arrives. At no time should we reach the high heat release necessary to Jeopardize the exposed structural steel.

I

b.

The structural steel in the Diesel Bays, including the fifth diesel bay or Cardox Room, the High Pressure Service Water Ptrnp Bays and the Fan Room support ceilings which are not Appendix R, III.G.2 fire barriers. However, should the structural steel fall, we are evaluating the effects on adjacent walls which are III.G.2 fire barriers.

If the structural evaluation detennines that the adjacent walls will not fall, we do not plan to provide any steel protection. The walls in question are seismically designed reinforced concrete and are two to three feet thick.

Failures due to localized effects were evident in 16 plant areas and included a total of 60 beams plus the entire Cable spreading Room. We are considering the following alternatives to address these problems:

a.

Where cable tray crosses the axis of a beam in a perpendicular direction, we propose to coat the beam three feet in each direction from the area of flame impingement with fire proofing material or provide solid tray covers of a similar length for the cable tray. We are currently evaluating whether any cable derating is required if we install tray covers. Since the problem associated with localized effects is direct flame impingement; fire proofing or solid tray covers will protect the beam, b.

When a cable tray runs parallel to and beneath a bean, the entire beam will be coated with a three foot overlap at the ends or tray covers will be provided, c.

Beams that are Jeopardized by vertical trays will be coated five feet in each direction from the area of flane impingement.

d.

If tray covers are not acceptable due to derating, an evaluation will be made to detennine whether the bean should be coated or if sprinkler protection will be provided, e.

The Jeopardized structural members will be evaluated to determine their structural significance.

If the menbers are not required structurally, no protection will be provided, f.

The Cable Spreading Room was unusual. The area temperature did not cause a structural problem when based on cmbustible loading, however, every beam failed due to localized effects because of the close proximity of raceway to the ceiling. The Cable Spreading Rocm ceiling is not a 111.6.2 fire barrier. Autcmatic carbon dioxide is provided for the room. The CO system is actuated by cross-zoned smoke 2

detectors.

GJR/cb/03278506 L