L                                              Washington, DC 20555 Subjects        Byron Station Units 1 and 2 Braidwood Station Units 1 and 2 Amendment to Facility Operating Licenses NPF-37, NPF-66, NPF-72,                                    '
L                                              Washington, DC 20555 Subjects        Byron Station Units 1 and 2 Braidwood Station Units 1 and 2 Amendment to Facility Operating Licenses NPF-37, NPF-66, NPF-72,                                    '
and NPF-77                          4f7 tiEC Docket Nos. 50-454/455 ana _50-43fr/456 References      (a) June 17, 1987, letter from K. A. Ainger to U.S. NRC                    l
and NPF-77                          4f7 tiEC Docket Nos. 50-454/455 ana _50-43fr/456 References      (a) {{letter dated|date=June 17, 1987|text=June 17, 1987, letter}} from K. A. Ainger to U.S. NRC                    l
                                                                     .(b)        May 6, 1989, letter from K. A. Ainger to U.S. NRC
                                                                     .(b)        {{letter dated|date=May 6, 1989|text=May 6, 1989, letter}} from K. A. Ainger to U.S. NRC


==Dear Dr. Murley:==
==Dear Dr. Murley:==

Latest revision as of 02:08, 19 March 2021

Forwards Revised Tech Spec Page 3.4.6.1, RCS Leak Detection Sys to Util 870617 & 890506 Requests for Amends to Licenses NPF-37,NPF-66,NPF-72 & NPF-77
ML20245H561
Person / Time
Site: Byron, Braidwood, 05000000
Issue date: 06/23/1989
From: Chrzanowski R
COMMONWEALTH EDISON CO.
To: Murley T
Office of Nuclear Reactor Regulation
Shared Package
ML20245H564 List:
References
NUDOCS 8906290523
Download: ML20245H561 (1)


Text

- _- _ - - _ _ _ _ _ _ __

.I Com'm::nwrith Edison:

8.' _f X i 72 West Adams Street, Chicago, Illinois

'* V . AddressReply to: Post Office Box 767 N

i. : Chicago, litinois 60690 - 0767 June 23, 1989 '

Dr. Thomas E. Murley, Director Office of Nuclear Reactor Regulation ,

U. S. Nuclear Regulatory Commission l

L Washington, DC 20555 Subjects Byron Station Units 1 and 2 Braidwood Station Units 1 and 2 Amendment to Facility Operating Licenses NPF-37, NPF-66, NPF-72, '

and NPF-77 4f7 tiEC Docket Nos. 50-454/455 ana _50-43fr/456 References (a) June 17, 1987, letter from K. A. Ainger to U.S. NRC l

.(b) May 6, 1989, letter from K. A. Ainger to U.S. NRC

Dear Dr. Murley:

The referenced letters. requested a change to Technical Specification 3.4.6.1

" Reactor Coolant System Leak Detection System" for Byron and Braidwood Stations.

After numerous conversations with members of your staff, the. attached Technical Specification page is revised to. change the action statement time limit;to 7 days.

The justification for the seven days time limit is based on actual maintenance .

]

history of the leak detection system instrumentation. -The previous work performed )

-occurred during an outage condition and lasted a total'of 99 hours0.00115 days <br />0.0275 hours <br />1.636905e-4 weeks <br />3.76695e-5 months <br /> on two different I components'of the leak detection system instrumentation. During non-outage conditions, the time required to complete the work is greater due to the containment entry precautions taken during pover operations.

. Commonwealth Edison believes that the requested action statement time limit is justified, based on actual work histo;y, and conservative, since the two radioactivity monitoring system (geseous and particulate) monitors would be operable.

This change has been reviewed and approved by both on-site and off-site review in accordance with Commonwealth Edison procedures. The previously submitted no significant hazards consideration, contained in reference (a), has been reviewed and remains valid with the 7 day action statement time limit.

Please direct any further questions on this matter to this office.

Very truly yours, R. A. Chrzanowski Nuclear Licensing Administrator 0179T 1 Attachment 8906290523 DR 890623 ADOCK 05000454 PDC cc Resident Inspector-Byron Resident Inspector-Braidwood {

L. N. Olshan-NRR S. P. Sands-NRR II g

,0ffice of Nuclear Facility Safety-IDNS [

NRC Region III Office