Cimmonwccith Edison 1400 Opus PI ce Y
Downers Grove, Illinois 60515 May 16, 1990 I
Dr. Thomas E. Murley, Director i
Office of Nuclear Reactor Regulation l
U.S. Nuclear Regulatory Commission Washington, DC 20555 ATTN: Document Control Desk
Subject:
Byron Station Units 1 and 2 Braidwood Station Units 1 and 2 4
Fire Protection Report
)
-NRC Docket Nas d Q-A54/455 and 50-456/451
Reference:
(a) December 14, 1983 T.R. Tramm letter to H.R. Denton.
'I
Dear Dr. Murley:
Reference (a) provided a revised response to Open Item #4-to the July, 1983 NRC Fire Protection-Audit, performed at Byron Station for Unit 1.
3 Reference (a) provided in part, the fire loading for Fire Zones 2.1-1 and 2.1-2 of 42,300 BTU /ftb and 43,900. BTU /ft2, respectively. As a result of a recent Commonwealth Edison review, the value of.43,900 BTU /ft2 for Zone 2.1-2 was identified as not having been incorporated into the Byron /Braidwood Fire Protection Report (FPR).
As a result, the purpose-of this letter is to provide an advanced notification of a change that will be'made to FPR pages 2.2-18 and 2.3-14 that will be provided to the NRC staff in the annual FPR update in December, 1990, consistent with Edison's previous committment. Marked-up copies of;pages j
2.2-18 and 2.3-14 are provided in Attachment A.
The fire loading has remained and is below the 43,900 BTU /ft2 value in Zone 2.1-2 at both the Byron and Braidwood Stations.
Please direct any questions-regarding this submittal to this office, i
Very.truly yours, Ac9 M S.C. Hunsader Nuclear Licensing Administrator Attachments cc:
P. Shemanski - Project Manager, NRK S. Sands - Project Manager, NRR W. Shafer - RIII BY Resident Inspector BW Resident Inspector
-/Imw 0939T11 9005230279 900316 fP PDR ADOCK 05000454 F
i
/[C PDC
'l
I H-4
.4 r
'4 e
i t
t ATTAC]It2NT A
~
s BYRON /BRAIDWOOD-FIRE PROTECTION REPORT-PAGES: -2.2-18 2.3-14 i
Y 1
1 I
m i
b 1
i i
i
D/B' N
e TABLE 2.2-3 -(Cont 'd)
I FIRE AREA /20NE FIRE LOAD DES GN NUMBER AND NAME FIRE PXrrECTION FIRE (ETECTION COMBUSTIBif.
FI RE ' (B t uf f t )
2.1 2 Note 1 Ionization-
.2,000 lb of paper
-44 404-=
7
~**
Record storage
. detection 2.88 lb of gasketing gg3 9oC and toljet room (Unit 2 detec--
71.8 lb of insulatio
/
tion tone 70) 3.1-1 Unit 1 Automatic total tonisation 6000 lb cable.
45,200.
cable tunnel flooding carbon detection insulation dioalde system
.(Unit 1,detec-46.8 lb gasketing (Unit I suppres-tion tone 64) sion tone 47)
.Fenwal thermal (Unit I detection zone 65) Note 3 3.1-2 Unit 2 Automatic total tonisation.
3400 lb' cable
'25,700 cable tunnel flooding carbon detection insulation
- dioxide system (Unit 2 detec-45 lb gasketing (Unit 2 suppres.
. tion tone 64) sion tone 47)
Fenwal thermal
.(Unit 2' detection Zone 65) Note 3' 3.2-0 Auxiliary Note 1.
Ionisation ~
1200 lb cable 9,500-building El. 4 39'-0*
detection,
62 lb gasketing insulation
.(Unit 2.detec -
tion tone 61) s 3.2A-1 Unit 1 Automatic total
-Ionisation 37 lb gasketing 33,100 Nonsegregated flooding carbon
. detection 19,000 lb cable bus duct area dioxide system (Unit I detec-insulation (Unit 1 suppres.
tion tone 49)-
t alon Zone 43)
Fenwal thermal' (Unit I detection Zone 50) Note 3 3.2A-2 Unit'.2 Nonsegregated
. Automatic. total lonisation' 37 lb gasketing.
26,700 flooding carbon detection.
15,000 lb cable.
7 bus duct area
- dioxide: system
- (Unit 2 detec-~
insulation (Unit 2 suppres '
tion l2one'49)-
sion Zone 43) renwal thermal.
(Unit 2 detection tone 50) Note 3 l
3.28-1 Lower Automatic total
. Ionization' 49.lb gaskets' 44,000 cable spreading flooding carbon detection '
820 lb. ducting area, tone D-1 dioxide system (Unit 1 detec--
insulation.
(Unit 1 suppres-tion' tono 51)'
27,000 lb cable' sion tone 44)
.Fenwat thermat insulation (Unit i detection-tone 52) Note.3
.3.20-2 Lower Automatic total'
' Ionization 14.4 lb flex 42,200 cable spreading flooding carbon detection connections area, tone B-2 dioxide system' (Unit 2 detec-26,000 lb cable (Unit 2 suppres-~
' tion Zone $1)
. insulation alon Zone 44)
Fenwal thermal (Unit 2 detection zone 52) ' Note 3 -
3.2C-1 Lower Automatic total Ionization 23,000 lb cable 69,800' cable spreading flooding carbon detection Insulation area, zone C dioxide system (Unit 1 (etec-(Unit I suppres-tion tone 53) alon' tone 45)
Fenwal' thermal.
8 Unit I detection tone 53) Note 3 3.2C-2 Lower Automatic total' Ionization
-13,000 lb cable 39,300 cable spreading flooding carbon detection insulation area, Zone C-2 dioxide system (Unit 2 detec-(Unit 2 suppres-tion Zone 53) sion. tone 45)
Fenwal thermal (Unit 2 detection Zono 54) Note 3 3.2D-1 Lower Automatic total tonization 3100 lb cable 51,400 cable spreading flooding carbon detection insulation room, 2one D-1 dioxide system
. tion Zone 55)
(Unit I detec-(Unit I suppres-sion Zone 46)
Fenwat thermal
+
(Unit I detection tone 56) Note 3 2.2 18
[s ;
B/B AMEMBMEiG 6-JAM"?."? 1^65 Fire Barrier Description
(~T 1
~'
The-floor slab at elevation 451 feet 0 inch, which is the ceiling i
of the Lower Cable Spreading Room, is a 9-inch clear cover of structural reinforced concrete over 3-inch fluted steel decking formwork.
It is suported by structural steel beams protected with a fire resistant covering and carries a 3-hour' fire rating.
All walls of the storage area are 12-inch thick hollow concrete masonry units and carry a 3-hour fire rating and they extend up i
to within 1 inch o'f the ceiling above.
This resulting space is l
packed with a-1-inch thick blanket of foil-backed Thermafiber insulation.
A 3-hour. rated Label-"A" fire door leads to the' Control Room.
The ceiling. slab at elevation 463 feet 5-inches,.which is'the floor of the Upper. Cable Spreading Room, is a-2 1/2-inch clear cover of reinforced concrete over 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> protected l~1/2-inch a
fluted steel decking.
It-is supported by protected structural steel beams and carries a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating.
An acoustical tile suspended ceiling system is provided below the ceiling slab in the storage area.
Safety-Related Equipment.
For details, see Subsection 2.3.2.2.
{
i Protection Criteria For details, see Subsection 2.3.2.2.
1 Combustible Materials
.This room will be used to store chart paper for control room recorders.
It is estimated that 2,000 pounds of paper will be stored here.
A transient load is not considered..
The-ductwork in this zone contains 2.88 pounds of gasketing and 71.8 pounds-of insulation.
The storage area = floor is covered with 203'ft of 1/8-inch thick vinyl-asbestos tile.
In addition, 59 lineal feet of:4-inch high vinyl cove base is provided at the intersection of the' walls and the floor.
Fire Loading gW.
2 With a floor area of 203 ft the. fire loading i is r499-Btu /f t Extinguishing and Detecting Capabilities
/
For details, see Subsection 2.3.2.2.
Design-Basis Fire For details, see Subsection 2.3.2.2.
l 2.3-14
'