NPDES Noncompliance Notification:On 820720,routine Oil & Grease Sample Indicated 23.5 mg/1 Concentration.Cause Unknown.Oil Absorbent Pillows in Tank T-41 Changed
ML20067B883
Person / Time
Site: Palisades 
Issue date: 07/30/1982
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18047A680 List:
References
PAL-82-07-AD73, PAL-82-7-AD73, NUDOCS 8212060421
Download: ML20067B883 (1)


Text

__

Fils No P10.2.1 Incid;nt No: PAL-82-07-AD73 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation July 30, 1982 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Sump 011 Separator Outfall No: 800218 Wastes (00G)

Parameter: Oil and Grease - Freon Parameter No: 00556 1.

Date of Incident:

7/20/82 2.

Identification of specific effluent limitation or monitoring requirement affected: 011 and grease are limited to 20 mg/l daily maximum concentration.

3.

Description of Incident:

A routine oil and grease sample collected on 7/20/82 indicated 23.5 mg/1.

Samples collected 7/19/82 and 7/21/82 measured 11.6 mg/l and 13.2 mg/1, respectively. The oil appeared to be turbine lube oil.

4.

Apparent Cause:

No particular event could be identified as the cause.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The oil absorbent pillows present in Tank 7-41 and the turbine sump were changed to better absorb any oil present in those tanks.

7.

Additional Comments:

Daily observation of the discharge showed no visible oil on the lake surface.

The oil treatment facility filters were changed on 7/16/82. The normal expected" life of the filters is greater than four days.

8.

Signed: Ronald L Fobes fjf/T j

8212060421 821124 PDR ADOCK 05000255 4

S PDR mi0782-0613a160

- - -