RECEIVED CORSumW3 MAY 221986 M

NUCLEAR UCEbb6tes Company

@@M oeneral offices: 212 weet Michleen Avenue, Jackson, MI 492ot + (617) 788m5o May 21, 1986 M905 Ms Sue Schweikart

[

Michigan Department of Natural Resources

(

Plainwell District Office j

PO Box 355 Plainwell, MI 49080 REPORT OF OIL, SALT OR POLLUTING MATERIAL LOSS - NEUTRALIZER TANK OVERFLOW PALISADES PLANT, COVERT, MICHIGAN

{

Enclosed are.two Reports of 011, Salt,or Polluting Material Losses, Form

(

R4616, applicable to the recent overfilling of the neutralizer tank at our Palisades Plant near Covert, Michigan. These overflows were discovered and reported to the Plainwell District MDNR on May 13 and 15, 1986.

Should you require any additional information regarding this matter, please contact this office.

f al l

R L Fobes l

Senior Environmental Advisor BCC DHAndrews, Palisades BDJohnson, P-24-606 SFPierce, Palisades JRSchepers, Palisades ATUdrys, M-1023 K

S OC0586-0035A-EN01

y s

STATE OF MICHIGAN DEPARTMENT OF NATURAL RESOURCES REPORT OF OIL, SALT OR POLLUTING MATERIAL LOSSES Pursuant to the provisions of Act 245 of the Public Acts of Michigan 1929 as amended, regulations have been issued whien require that all owners, r anagers or operators of vessels, oil storage or on land facilities shall notify the Water Resources Commission or his authorized representstive e,f oil, salt and polluting material losses. This notification shall be made promptly by telephone or telegraph, giving briefly tt'a parv,culars, and b'/ mail, giving a detailed account of events and conditions.

Dece Company Name May lb, 1986 Consumers Power Company Location of Loss i8e Specifici Palieades Plant - T921 Neutralizer Tank Amount Name of Sudace Wow involvm2 ustenee i.o.'

Spent Demin Rezenerants rH 1.7 100 gallons N/A Ouo Loss vues Discovered Time of Discovery May 13, 1986 1610 Name of Department of Naturel Resources Representative Contacted Chuck Bikfalvy, Plainvell District MDNR Tesecnoned or reisgreened cy whom Time David H Andrews, Palisades Plant

/$07 Cause of Loss (loctuce Type of Equipment and Other Details)

As the result of a previously leakinz valve which allowed an unknown a-cunt of vster *n enter the neutralize &" tank (diminishing its holding capacity) the tank overfleved to the ground during an extended regeneration cycle.

Nature of Loss (incluoe Complete Descnotion of DamayA

_The overflow of desineralizer regenerants soaked into sand under terk. There was no significant environmental harm.

I Additional Comments (Incluw Method of Control, fHens for Provermon of Recurrence, etc )

Tank level instrument was out-of-service for calibration. The level cauce and a hich level alarm were reinsts11ed on 5-16-86.

The leaking valve was scheduled for maintenance repair.

Company Name Sy (Sprol Consumers Power Company - Palisades Plant DHAndrevs/PLFebes I[F 1

24-Hr Emergency Notification Number (800) 292-4706 Return this form to:

1 Environmental Department i

Paraall Road Jackson, Michigan A4616 l

10/73 I

l i

(.

o STATE OF MICHIGAN DEPARTMENT OF NATURAL RESOURCES REPORT OF OlL, SALT OR POLLUTING MATERIAL LOSSES Pursuant to the provisions of Act 245 of the Public Acts of Michigan 1929 as amended, regulations have been issued which recuire that all owners, managers or operators of vessels, oil storage or on land facilities shall notify the Water Resources Commission or his authorized representative of oil, salt and polluting material losses. This notification shall be made promptly by telephone or telegraon, giving briefly the porticulars, and by mail, giving a detailed account of events and conditions.

Dete Company Name May 15, 1986 Consumers Power Company Location of Loss (Be Soecifici Palisades Plant - T-921 Neutralizer Tank Merena i.ost Demineralizer l ^**""'

N*me of Surface wmr sawved Rinse Water pH 2.6 (Atorox 1.000 callens N/A Date Loss was Discovered rime of Discovery May 15, 1986 Oh00 Name of Desertment of Naturet Resources Representative Contacted Sue Peelen, Plainvell District MDNR Teeononed or Tweersonas av whom, Time David H Andrews Palisades Plant 0051 Cause of Loss (include Type of Equipment and Other Deteds)

Rinse valve was inadvertent 1'f left open overfilling the tank. There is a leak in the overflow line resulting in the 16ss of material to the ground.

Nature of Loss (include Complete Description of Damage)

The overflow water was absorbed in the soil under the tank.

Addit >onal Comments (include Method of Control, Pfens fW'avention of Recurrence, etc )

The soil under the tank vas testLMr pH on 5/15/86. One sample point ceasured a pH of L.S.

All other samples ranged in W Ce from 5.0 to 7.0.

Based on these results, no further h;eratorsresponsibleforvalveoperationvillbeinstructed clean up is planned at this e

on the importance of valve closure to prevent similar spills in the future.

Company Name 8y (Segnature)

Cord users Power Company - Palisades Plant DHAndrevs/RLFebes TM 24 Hr Emergency Notification Number Return this form to:

Environmental Copartment Parnall Road Jackson, Michigan A4616 10n3

.