NPDES Noncompliance Notification:On 820712,13 & 14,routine Oil & Grease Samples Indicated 21.7 mg/1,25.5 mg/1 & 112.5 mg/1 Respectively.Caused by Clogged Oil Removal Filters in Emulsion Breaking Sys.Oil Filters Changed
ML20067B887
Person / Time
Site: Palisades Entergy icon.png
Issue date: 07/22/1982
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18047A680 List:
References
PAL-82-07-AD72, PAL-82-7-AD72, NUDOCS 8212060431
Download: ML20067B887 (1)


Text

,

File No P10.2.1 Incident No: PAL-8 7-AD72 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limita*. ion July 22, 1982 Plant: Palisados

- Permit No: MI 0001457 Outfall

Description:

Turbine Sump 011 Separator Outfall No:

800218 Wastes (00G)

Parameter: 011 and Grease - Frcon Parameter No: 00556 1.

Date of Incident: 7/12/82, 7/13/82, 7/14/82 2.

Identification of specific effluent limitation or monitoring requirement affected:

011 and grease are limited to 20 mg/l daily maximum concentration.

3.

Description of Incident:

A routinc sampic collected 7/12/82 indicated 21.7 mg/l oil and grease.

Sam-plcs co11ceted 7/13 and 7/14 measured 25.5 and 112.5 mg/1, respectively. The oil appeared to be turbine lube oil.

4.

Apparent Cause:

Apparent clogging of oil removal filters in the emulsion breaking system.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The oil removal filters were changed on 7/16/82 after receiving notification of sample results on 7/15/82. Oil absorbent pillows were changed in the tur-bine sump and the turbine sump oil separator tank (T-41).

7.

Additional Comments: