ML18045A630

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 800818,weekly Grab Sample Indicated 27.3 mg/1 Oil & Grease.Caused by Oil Separator Sys Ineffectively Removing Component Oil in Floor Drains.Oil Absorbent Pads Will Be Placed Throughout Plant
ML18045A630
Person / Time
Site: Palisades Entergy icon.png
Issue date: 09/09/1980
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18045A629 List:
References
P10.2.1, PAL-80-08-NC40, PAL-80-8-NC40, NUDOCS 8009220289
Download: ML18045A630 (1)


Text

  • Jlli..lc No Pl0.2.1

~i<lcnt No: PAL-SO-OS-~C40 NPOES 1'!0~CO~ll~G_I_!l~C:E NOTI FI CA"[.!_9N Possible Non<::ompliance \\ith Daily Avcr:1ge/Maximum Limitation September 9, 1980 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Sump Oil Separator Outfall No: 800218 Waste (OOG)

Parameter: Oil and G~ease Parameter No: 00556

1. Date of Noncompliance: Augu~t 18i 1980
2. Identification of specific effluent limitation exceeded: Oil and grease daily maximum limitation of 20 mg/l.
3. Descr~ption of Incident: The weekly grab sample collected on August 18, 1980 was analyzed and i.ndicated 27. 3 mg/ 1 oil and grease. It is believed that this is a transient condition and was below the limit within a short period of time . .The sample on August 26, 1980 indicated 19.7 mg/I.
4. Apparent Cause: Apparently oil from Plant components was getting into floor drains and was not being effectively removed by this oil separator system.
5. If not immediately corrected, the anticipated time the condition is expected to continue: .N/A
6. Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: Plant staff will begin placing*

oil absorbent pads, as necessary, throughout the Plant in an attempt to limit oil getting into the sump system.

7. Additional Comments: N/A
8. Signed: Ronald L Fobes "mi09S0-0127a-43 8009220151
  • -*** ****-**---*---- *:---------* *-*-------* *----*---**-----