ML18045A630
From kanterella
Jump to navigation
Jump to search
ML18045A630 | |
Person / Time | |
---|---|
Site: | Palisades |
Issue date: | 09/09/1980 |
From: | Fobes R CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
To: | |
Shared Package | |
ML18045A629 | List: |
References | |
P10.2.1, PAL-80-08-NC40, PAL-80-8-NC40, NUDOCS 8009220289 | |
Download: ML18045A630 (1) | |
Similar Documents at Palisades | |
---|---|
Category:NPDES NONCOMPLIANCE NOTIFICATION
MONTHYEARML18065B0541996-11-0808 November 1996
[Table view]NPDES Noncompliance Notification:On 961023,release of Approx One Gallon of Diesel Fuel That Was Mixed W/Groundwater from Construction Dewatering Activity Was Reported to Pollution Emergency Alert Sys.Matl Was Contained & Cleaned Up ML18065A7421996-05-23023 May 1996 NPDES Noncompliance Notification:On 960228,15,000 Gallons of Demineralizer Regeneration Waste Solution Spilled Into Plant Mixing Basin ML18064A7631995-05-0808 May 1995 NPDES Noncompliance Notification:During Nov 1994 - Apr 1995, No NPDES Violations Identified.Three Repts of Oil,Salt or Polluting Matl Loss Made on 941102,11 & 29 ML18058B8491993-05-20020 May 1993 NPDES Noncompliance Notification for Nov 1992-Apr 1993.On 930105,loss of Power to Sewage Lift Pumps Occurred,Resulting in Loss of 50 Gallons of Clear Liquid Sewage to Storm Drain. No Presence of Solids or Sewage Odor Noted ML18058B2351992-11-20020 November 1992 NPDES Noncompliance Notification:On 920517 & 0713,plant Exceeded Max Chlorine Effluent Concentration to Outfall 001.Causes Unknown.Request Submitted to Reroute Backwater Flush to Storm Drain & Grab Samples Obtained ML18058A4581992-05-18018 May 1992 NPDES Noncompliance Notification:On 911210 & 920408,plant Exceeded Max Oil & Grease Concentration to Plant Mixing Basin.On 920403,inadvertent Release of 160 Gallons of CCW Occurred.Oil Absorbent Pillows Placed in Turbine Bldg ML18057B3901991-11-26026 November 1991 NPDES Noncompliance Notification:On 910710,loss of Approx 200 Gallons of Liquid Sewage from Plant Septic Sys Occurred. on 910820,hydrazine Lost from Main Outfall.Revised NPDES Permit Issued in Aug 1991 ML18057A6111990-11-30030 November 1990 NPDES Noncompliance Notification:From 900501-1031,six Sewage Overflows to Storm Drain Sys Occurred.Overflows Attributed to Increased Number of Contractors on Site,Poor Clean Out Fixture Design & Blockage of Sewage Line ML18054B1671989-11-30030 November 1989 Supplemental NPDES Noncompliance Notification:On 890107,18 & 20,daily Max Effluent Limitations Exceeded.Previous Heat Addition Values Incorrect.Actual Heat Loading Stated ML18054A7861989-05-31031 May 1989 NPDES Noncompliance Notification:On 890107,18 & 20,plant Thermal Discharge Exceeded Daily Max Heat Discharge Effluent Limitation.Caused by Failure to Adequately Monitor & Control Blowdown from Closed Cycle Condenser Cooling Sys ML20195J4901988-06-20020 June 1988 NPDES Noncompliance Notification:On 880616,TRC at Discharge Rose to 0.3 Mg/L.Caused by Higher than Normal Amount of Sodium Hypochlorite Inadvertently Added During Chlorination of Cooling Tower A.Util Will Evaluate Causes ML20195J4841988-05-23023 May 1988 NPDES Noncompliance Notification:On 880516,routine Sample of Turbine Sump Oil Separator Tank T-41 Analyzed & Reported to Be 24 Mg/L.Caused Undetermined.Quarterly Routine Cleaning of Oil Separator M-18 Occurred Between Sample & Analysis Time ML18155A2721987-12-0101 December 1987 NPDES Noncompliance Notification:On 870817,sample of Turbine Sump Oil Separator Tank T-41 Reported Oil & Grease Level Exceeding Daily Max Limit.Caused by Spill of Electrol Hydraulic Control (EHC) Fluid from Ruptured EHC Line ML20154Q5281987-08-28028 August 1987 NPDES Noncompliance Notification:On 870818,50 Gallons of Stauffer EHC Fluid Released in Lake Michigan.Caused by High Pressure Line Failure Resulting in Loss.Majority of Fluid Captured W/Oil Sorbent Matl.No Apparent Damage Noted ML20214W8611986-08-14014 August 1986 NPDES Noncompliance Notification:On 860812,overflow from Plant Neutralizer Tank Discovered.Caused by Extended Manual Rinse.No Environ Damage to Area Under Tank.No Cleanup Planned.Operators Instructed to Prevent Recurrence ML20214W8771986-07-10010 July 1986 NPDES Noncompliance Notification:On 860630,neutralizer Tank Total Suspended Solids (TSS) Concentration Found Above Limit.Caused by Tank Release on 860603 W/Abnormally High TSS Content ML20214W8971986-06-0909 June 1986 NPDES Noncompliance Notification:On 860514,19 & 31,oil & Grease Concentration for Tank T-41,turbine Sump Oil Separator,Found Above Limit.Caused by Temporary Bypass & Failure of Separator.Separator Cleaned ML20214W9211986-05-28028 May 1986 NPDES Noncompliance Notification:On 860519,daily Max Limit for Oil & Grease in Turbine Sump Oil Separator Exceeded. Caused by Failure of Separator to Adequately Remove Influent Oil to Sys.Separator Cleaned ML20214W9261986-05-21021 May 1986 NPDES Noncompliance Notification:On 860513,spent Regenerants Overflowed from Neutralizer Tank & on 860515,demineralizer Rinse Water Overflowed from Same Tank.Caused by Leaking Valve & Valve Being Inadvertently Left Open,Respectively ML20214W9351986-05-21021 May 1986 NPDES Noncompliance Notification:On 860514,daily Max Limit for Oil & Grease in Turbine Sump Oil Separator Exceeded. Caused by Temporary Bypass of Separator for Scheduled Cleaning.Cleaning Will Be Better Coordinated in Future ML20210V4821986-04-22022 April 1986 NPDES Noncompliance Notification:On 860414,oily Wastewater Treatment Sys Bypassed.Condensate Pump P-2A Developed Packing Leak & Flooded Pit Floor.Condensate Pump P-2A Taken Out of Svc for Repair ML20210V4991986-04-15015 April 1986 Corrected NPDES Noncompliance Notification:On 860303,daily Max Oil & Grease Limit Exceeded for Turbine Sump Oil Separator Discharge.Addl Readings Made to Assess Sys Performance & Several Readings Also Exceeded ML20210V5351986-04-10010 April 1986 NPDES Noncompliance Notification:On 860331,monthly Average Limit 15 Mg/L Oil/Grease Exceeded.Turbine Sump Pit Filled W/Oil from Leaking Seal on Turbine 4 Bearing Oil Lift Pump. Leak on Pump Secured & Turbine Sump Pumped to Oil Hold Tank ML20210V5401986-04-0202 April 1986 NPDES Noncompliance Notification:On 860323,daily Max Limit 20 Mg/L Oil & Grease Exceeded.Caused by Failure of Oil Removal Sys to Remove Oil from Process Stream.Sys Engineer in Process of Evaluation ML20210V5561986-03-26026 March 1986 NPDES Noncompliance Notification:On 860324,oily Waste Treatment Sys Bypassed.Normal Pathway from Turbine Sump to M-18 Emergency Bypassed Because Turbine Sump Pumps P-45A & B Inoperable.Turbine Sump Pumps P-45A & B Being Repaired ML20210V5651986-03-24024 March 1986 NPDES Noncompliance Notification:On 860314,fuel Oil Spill of 100 Gallons Number 2 Fuel Oil.Caused by Tank T-926 Overfilled by Vendor.Contaminated Soil Removed & Disposed of in Orchard Hills Landfill & Replaced W/Fresh Sand ML20210V5271986-03-11011 March 1986 NPDES Noncompliance Notification:On 860303-10,daily Max Limit 20 Mg/L Exceeded.Turbine Sump Pit Filled W/Oil from Leaking Seal on Turbine 4 Bearing Oil Lift Pump.Leak on Pump Secured.Accumulated Oil Pumped Into Oil Hold Tank ML20211A9451986-03-11011 March 1986 NPDES Noncompliance Notification:On 860303,daily Max Limit 20 Mg/L Exceeded.Turbine Sump Pit Filled W/Oil from Leaking Seal on Turbine 4 Bearing Oil Lift Pump.Leak on Pump Secured.Turbine Sump Pumped to Oil Hold Tank ML20211A9701986-02-12012 February 1986 NPDES Noncompliance Notification:On 860207,PH Daily Max Limitation of 9.0 for Mixing Basin Discharge.Neutralizer Tank Drain Valve Left Open Following Neutralizer Tank Release.Drain Valve Closed.Procedures Reevaluated ML20211B0001986-01-14014 January 1986 NPDES Noncompliance Notification:On 851201,pH Not Monitored. Technician Unaware of Required Sampling.Technicians Reminded of Sampling Requirement When Sample Pump Out of Svc ML20138K3591985-12-0202 December 1985 NPDES Noncompliance Notifications for May-Oct 1985 ML20126M7101985-05-0606 May 1985 NPDES Noncompliance Notification:On 850415,monitoring Point Outfall 00G (Tank T-41) Weekly Grab Sample for Oil & Grease Exceeded Daily Max.Caused by Abnormal High Flow of Water Through Turbine Sump ML20126M7141985-03-19019 March 1985 NPDES Noncompliance Notification:On 850228,monthly Average Oil & Grease Exceeded Limit of 15 Mg/L.Caused by Apparent Malfunction of New Oil/Water Separator.Separator Cleaned & Oil Skimming Weir Readjusted ML20126M7191985-02-0606 February 1985 NPDES Noncompliance Notification:On 850131,monthly Average Oil & Grease Concentration Measured 42 Mg/L,Exceeding Limit of 15 Mg/L.Caused by Bypass of New API Oil/Water Separator Due to Faulty Waste Oil Pump.New Pump Installed ML20126M7281985-02-0404 February 1985 NPDES Noncompliance Notification:On 850121 & 28,routine Weekly Oil & Gas Samples Measured 50.2 Mg/L & 60 Mg/L, Respectively,Exceeding Limit.Caused by Bypass of New API Oil/Water Separator Due to Faulty Waste Pump ML20126M7501985-01-21021 January 1985 NPDES Noncompliance Notification:On 850110 & 14,routine Weekly Oil & Grease Samples Measured 72.2 Mg/L & 56.1 Mg/L, Respectively,Exceeding Limit.Caused by Removal of New API Oil/Water Separator from Svc for Maint.Returned to Svc ML20126M7691984-12-0303 December 1984 NPDES Noncompliance Notification:On 841120 & 21,turbine Bldg Sump Flooded & Oily Waste Treatment Sys Temporarily Bypassed.Caused by Main Boiler Feed Pump Leakage.Leakage Cut to Flow Level Turbine Sump Pumps Could Handle.W/Addl Repts ML20067B8311982-10-13013 October 1982 NPDES Noncompliance Notification:On 821004,max Measured TRC Value in Mixing Basin Was 0.75 Ppm During Chlorination of Cooling Tower A.Caused by Excessive Chlorine Feed for Plant Conditions.Chlorination Terminated ML20067B8361982-10-12012 October 1982 NPDES Noncompliance Notification:On 820927,routine Weekly Sample for Oil & Grease Collected Measured 23.0 mg/1. Caused by Malfunction of Emulsion Breaker & Oil Removal Sys. Emulsion Breaker Oil Filters Changed ML20067B8481982-10-0101 October 1982 NPDES Noncompliance Notification:On 820920,routine Weekly Oil & Grease Sample Collected Measured 123 mg/1.Caused by Malfunction of Emulsion Breaker Sys.Emulsion Breaker Oil Filters Changed on 820921 ML20067B8561982-08-16016 August 1982 NPDES Noncompliance Notification:On 820731,daily Max Limit of 20 mg/1 for Oil & Grease Was Exceeded 6 Days,Resulting in Monthly Average Limit of 15 mg/1 Being Exceeded.Cause Unknown.Oil Absorbent Pillows Changed ML20067B8751982-08-0606 August 1982 NPDES Noncompliance Notification:On 820722 & 23,routine Oil & Grease Samples Measured 26.5 mg/1 & 31.8 mg/1, Respectively.Cause Unknown.Oil Absorbent Pillows Changed & Floating Oil Removal Devices Emptied ML20067B8831982-07-30030 July 1982 NPDES Noncompliance Notification:On 820720,routine Oil & Grease Sample Indicated 23.5 mg/1 Concentration.Cause Unknown.Oil Absorbent Pillows in Tank T-41 Changed ML20067B8871982-07-22022 July 1982 NPDES Noncompliance Notification:On 820712,13 & 14,routine Oil & Grease Samples Indicated 21.7 mg/1,25.5 mg/1 & 112.5 mg/1 Respectively.Caused by Clogged Oil Removal Filters in Emulsion Breaking Sys.Oil Filters Changed ML20067B8931982-07-0707 July 1982 NPDES Noncompliance Notification:On 820628,29 & 30,routine Oil & Grease Samples Indicated 37.7 mg/1,23.1 mg/1 & 20.8 mg/1,respectively.Caused by Malfunction of Oil Treatment Skid & Associated Equipment.Oil Removal Filters Changed ML19343C5171981-03-16016 March 1981 NPDES Noncompliance Notification:On 810228,daily Average Oil & Grease Concentration Exceeded Daily Average & Max Limitations.Cause Identified & Corrective Actions Taken as Reported in Util 810213 & 0303 Repts ML20126E7561981-02-13013 February 1981 NPDES Noncompliance Notification:On 810203,oil & Grease Level of Outfall 800218 Found in Excess of Daily Max Effluent Limitation.Caused by Problems W/Emulsion Breaker. Filter Replacements & Waste Oil Sys Lineup Will Be Checked ML20003C0841981-02-13013 February 1981 NPDES Noncompliance Notification:On 810131,total Suspended Solids Exceeded Tech Specs Limits.Caused by Undetermined Isolated Occurrence.Neutralizer Tank Operating Conditions Will Be Continuously Scrutinized ML20002D9351981-01-20020 January 1981 NPDES Noncompliance Notification:On 801229,effluent Sample Exceeded Tech Spec Limit.Caused by Rupture of Emulsion Breaker Filter Element.Filter Element Replaced on 810107. Oil Removal Sys Will Be Cleaned & Personnel Reinstructed ML18045A6301980-09-0909 September 1980 NPDES Noncompliance Notification:On 800818,weekly Grab Sample Indicated 27.3 mg/1 Oil & Grease.Caused by Oil Separator Sys Ineffectively Removing Component Oil in Floor Drains.Oil Absorbent Pads Will Be Placed Throughout Plant 1996-05-23 Category:TEXT-ENVIRONMENTAL REPORTS MONTHYEARML18066A4211999-03-23023 March 1999
[Table view]1998 Annual Radioactive Effluent Release & Waste Disposal Rept. ML18068A5251998-12-31031 December 1998 1998 Annual Non-Radiological Environ Operating Rept. with 990217 Ltr ML18066A4281998-12-31031 December 1998 1998 Annual Rept on Occupational Exposure, for Palisades Plant.With 990323 Ltr ML20206E8541998-12-31031 December 1998 Annual Radiological Environ Operating Rept for 1998 ML18065B2331997-12-31031 December 1997 Radiological Environ Monitoring Program (REMP) for Palisades Nuclear Generating Plant for Jan-Dec 1997. ML18065B2311997-12-31031 December 1997 Plant,Annual Radiological Environ Operating Rept for Jan-Dec 1997. ML18065B1991997-12-31031 December 1997 1997 Annual Radioactive Effluent Release & Waste Disposal Rept. ML18065B1821997-12-31031 December 1997 1997 Annual Non-Radiological Environ Operating Rept. W/ 980316 Ltr ML18067A5161997-02-0707 February 1997 Final Monthly Progress Rept for Radiological Environ Monitoring Program for Palisades,Jan-Dec 1996. ML20138B1691997-02-0505 February 1997 Radiological Environ Monitoring Program for Palisades Nuclear Generating Plant,Jan-Dec 1996 ML18067A5141996-12-31031 December 1996 1996 Annual Radiological Environ Operating Rept. ML18067A4941996-12-31031 December 1996 1996 Annual Non-Radiological Environ Operating Rept. W/970417 Ltr ML18065B0541996-11-0808 November 1996 NPDES Noncompliance Notification:On 961023,release of Approx One Gallon of Diesel Fuel That Was Mixed W/Groundwater from Construction Dewatering Activity Was Reported to Pollution Emergency Alert Sys.Matl Was Contained & Cleaned Up ML18065A7421996-05-23023 May 1996 NPDES Noncompliance Notification:On 960228,15,000 Gallons of Demineralizer Regeneration Waste Solution Spilled Into Plant Mixing Basin ML18065A6771995-12-31031 December 1995 Annual Radiological Environ Operating Rept Jan-Dec 1995. ML18065A4971995-12-31031 December 1995 1995 Annual Operating Rept Occupational Exposure. W/960213 Ltr ML18065A6091995-12-31031 December 1995 1995 Annual Radioactive Effluent Release & Waste Disposal Rept. W/960329 Ltr ML18065A6821995-12-31031 December 1995 1995 Annual Environ Operating Rept (Non-Radiological). W/ 960429 Ltr ML18064A7631995-05-0808 May 1995 NPDES Noncompliance Notification:During Nov 1994 - Apr 1995, No NPDES Violations Identified.Three Repts of Oil,Salt or Polluting Matl Loss Made on 941102,11 & 29 ML18064A6751994-12-31031 December 1994 1994 Annual Radioactive Effluent Release & Waste Disposal Rept. ML20087H6391994-12-31031 December 1994 1994 Annual Environ Operating Rept (Non-Radiological). W/ ML18059B0351994-05-31031 May 1994 Non-Radiological NPDES Permit Violation Rept,Nov 1993-Apr 1994. W/940531 Ltr ML18059A9741993-12-31031 December 1993 Annual Radiological Environ Operating Rept Jan-Dec 1993. W/940429 Ltr ML18059A9261993-12-31031 December 1993 1993 Annual Environ Operating Rept (Nonradiological). W/ 940401 Ltr ML18059A9161993-12-31031 December 1993 Annual Radioactive Effluent Release Rept Jan-Dec 1993. W/940331 Ltr ML18059A7011993-12-31031 December 1993 1993 Annual Operating Report - Occupational Exposure. W/940224 Ltr ML18058B8491993-05-20020 May 1993 NPDES Noncompliance Notification for Nov 1992-Apr 1993.On 930105,loss of Power to Sewage Lift Pumps Occurred,Resulting in Loss of 50 Gallons of Clear Liquid Sewage to Storm Drain. No Presence of Solids or Sewage Odor Noted ML18058B7861992-12-31031 December 1992 1992 Radiological Environ Monitoring Rept. ML18058B6851992-12-31031 December 1992 Semiannual Radioactive Effluent Release & Waste Disposal Rept for Period of July Through Dec 1992. W/930226 Ltr ML18058B6991992-12-31031 December 1992 Revised Semiannual Radioactive Effluent Release & Waste Disposal Rept,Jul-Dec 1992. ML18058B6931992-12-31031 December 1992 Pnpp 1992 Annual Non-Radiological Environ Operating Rept. W/930309 Ltr ML18058B2351992-11-20020 November 1992 NPDES Noncompliance Notification:On 920517 & 0713,plant Exceeded Max Chlorine Effluent Concentration to Outfall 001.Causes Unknown.Request Submitted to Reroute Backwater Flush to Storm Drain & Grab Samples Obtained ML18058B0331992-06-30030 June 1992 Semiannual Radioactive Effluent Release & Waste Disposal Rept,Jan-June 1992. ML18058A4581992-05-18018 May 1992 NPDES Noncompliance Notification:On 911210 & 920408,plant Exceeded Max Oil & Grease Concentration to Plant Mixing Basin.On 920403,inadvertent Release of 160 Gallons of CCW Occurred.Oil Absorbent Pillows Placed in Turbine Bldg ML18058A3701991-12-31031 December 1991 1991 Radiological Environ Monitoring Rept. W/920423 Ltr ML18058A4981991-12-31031 December 1991 Annual Rept Covering Occupational Exposure During 1991.W/ 920529 Ltr ML18058A3691991-12-31031 December 1991 1991 Annual Environ Operating Rept (Nonradiological). W/920422 Ltr ML18057B3901991-11-26026 November 1991 NPDES Noncompliance Notification:On 910710,loss of Approx 200 Gallons of Liquid Sewage from Plant Septic Sys Occurred. on 910820,hydrazine Lost from Main Outfall.Revised NPDES Permit Issued in Aug 1991 ML18057B2371991-06-30030 June 1991 Semiannual Radioactive Effluent & Waste Disposal Rept,Jan-June 1991. ML18057B4121991-06-30030 June 1991 Rev to Semiannual Radioactive Effluent Release & Waste Disposal Rept,Jan-June 1991. ML18057A8131990-12-31031 December 1990 1990 Range Summary Rept. W/910314 Ltr ML18057A7661990-12-31031 December 1990 Semiannual Radioactive Effluent Release & Disposal Rept for Jul-Dec 1990. W/910228 Ltr ML18057A8181990-12-31031 December 1990 1990 Annual Environ Operating Rept. W/910318 Ltr ML18057A8701990-12-31031 December 1990 Annual Radiological Environ Operating Rept 1990. W/910424 Ltr ML18057A6111990-11-30030 November 1990 NPDES Noncompliance Notification:From 900501-1031,six Sewage Overflows to Storm Drain Sys Occurred.Overflows Attributed to Increased Number of Contractors on Site,Poor Clean Out Fixture Design & Blockage of Sewage Line ML18057A4311990-06-30030 June 1990 Semiannual Radioactive Effluent Release & Waste Disposal Rept Jan-June 1990. W/900831 Ltr ML18054B5821989-12-31031 December 1989 1989 Annual Environ Operating Rept. W/900430 Ltr ML18054B5791989-12-31031 December 1989 1989 Radiological Environ Operating Rept. W/900430 Ltr ML18054B4751989-12-31031 December 1989 Semiannual Radioactive Effluent Release & Waste Disposal Rept Jul-Dec 1989. W/900228 Ltr ML18054B1671989-11-30030 November 1989 Supplemental NPDES Noncompliance Notification:On 890107,18 & 20,daily Max Effluent Limitations Exceeded.Previous Heat Addition Values Incorrect.Actual Heat Loading Stated 1999-03-23 |
Text
- Jlli..lc No Pl0.2.1
~i<lcnt No: PAL-SO-OS-~C40 NPOES 1'!0~CO~ll~G_I_!l~C:E NOTI FI CA"[.!_9N Possible Non<::ompliance \\ith Daily Avcr:1ge/Maximum Limitation September 9, 1980 Plant: Palisades Permit No: MI 0001457 Outfall
Description:
Turbine Sump Oil Separator Outfall No: 800218 Waste (OOG)
Parameter: Oil and G~ease Parameter No: 00556
- 1. Date of Noncompliance: Augu~t 18i 1980
- 2. Identification of specific effluent limitation exceeded: Oil and grease daily maximum limitation of 20 mg/l.
- 3. Descr~ption of Incident: The weekly grab sample collected on August 18, 1980 was analyzed and i.ndicated 27. 3 mg/ 1 oil and grease. It is believed that this is a transient condition and was below the limit within a short period of time . .The sample on August 26, 1980 indicated 19.7 mg/I.
- 4. Apparent Cause: Apparently oil from Plant components was getting into floor drains and was not being effectively removed by this oil separator system.
- 5. If not immediately corrected, the anticipated time the condition is expected to continue: .N/A
- 6. Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: Plant staff will begin placing*
oil absorbent pads, as necessary, throughout the Plant in an attempt to limit oil getting into the sump system.
- 7. Additional Comments: N/A