NPDES Noncompliance Notification:On 860324,oily Waste Treatment Sys Bypassed.Normal Pathway from Turbine Sump to M-18 Emergency Bypassed Because Turbine Sump Pumps P-45A & B Inoperable.Turbine Sump Pumps P-45A & B Being Repaired
ML20210V556
Person / Time
Site: Palisades 
Issue date: 03/26/1986
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Morley F
MICHIGAN, STATE OF
Shared Package
ML20210V458 List:
References
PAL-86-03-NC119, PAL-86-3-NC119, NUDOCS 8606100663
Download: ML20210V556 (2)


Text

.

r'

~:vj3D

~

C SN

. lbhb l

y m.

L'- ' - " " '

,,s..

D oY o6neral Officas: 212 West Michleen Averowe, Jackeoft, MI 49201 * (517) 789 4660 March 26, 1986 Mr Fred Morley District Supervisor Michigan Department of Natural Resources Plainwell District Office Building 631 North Kent Street F0 Box 355 Plainwell, MI 49080 FILE NO:

P10.2.1 UFI 950/72*40*05/3 Years INCIDENT NO:

PAL-86-03-NC119 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant.

In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-86-03-NC119 is submitted as a report of an apparent bypass of one of the wastewater treatment systems at the facility.

If you have any questions regarding the attached report, please contact this l

office.

l ssdxFM l

R L Fobes Senior Environmental Advisor l

l BCC KFBieszke, T-242A TCBordine, F-24-608 SFPierce, Palisades l

JRSchepers, Palisades ATUdrys, M-1023 l

8606100663 860530 PDR ADOCK 05000255 l

S PDR 1

l i

I l

OC0386-53RLF-EN03

e File No PIO,2.1 Incident No: PAL-86-03-NC119 NPDES NOTIFICATION Apparent Bypassing o,f Wastewater Treatment System Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Sump Oil Outfall Code No:

800218 Separator (001/00F)

Parameter: 011 and Grease Paramete.r Code No: 00556 1.

Date of Ir.cident: March 24, 1986 (0435-0930 Hours) 2.

Identification of specific effluent limitation or monitoring requirement

'a ffected:

Bypassing of oily waste treatment system.

3.

Description of Incident:

At 0435 on 3/24/86, M-18 API oil / water separator and T-41 turbine sump oil separator tank was bypassed until 0930 on 3/24/86. Approximately 6,000 gallons of turbine sump water was rerouted directly to the mixing basin via manhole M-18.

A sample of the discharge measured 17.0 mg/l oil and grease (within NPDES permit limits).

4.

Apparent Cause:

The normal pathway from the turbine sump to M-18 was emergency bypassed because the turbine sump pumps P-45A&B became inoperable and a temporary sump pump was put into service.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

A temporary pump was lined up to M-18 oil / water separator at 0930.

6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

Turbine sump pumps P-45A&B will be placed back into service after mainte-l nance is performed.

l 7.

Additional Comments:

An observation 'of the mixing basin at 0800 was performed; no oil was observed.

(