. R Z C;; . s

.. FEB 151986

% CL:.J Lt '. ! L c.v 1' Power coinpany

@ @ E WI

@ W) I' U General offices: 212 West Michleen Avenue, Jackson, MI 49201 + (517) 7884550 February 12, 1986 Mr Fred Morley District Supervisor, SWQD Michigan Department of Natural Resources Plainwell District Office Building 621 North 13th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 UFI NO: 950/72*40*05/3 Years -

INCIDENT NO: PAL-86-02-NC117 This is in regard to NPDES Permit ilo MI 0001457 for the Company's Palisades Plant. In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-86-02-NC117 is submitted as a report of a failure to monitor and as a report of an apparent difference from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

%dd'Z FA R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117 KFBieszke, T-242A N ine,* P=24-600

]/ M '

JFFirlit, Palisades SFPierce, Palisades 8606110428 860530 S JRSchepers, Palisades PDR ADOCK 0500 ATUdrys, M-1023 S OC0286-20RLF-EN03

File No P10.2.1

.- Incident No: PAL-86-02-117 UFI No: 950/72*40*05/3 Years

, , NPDES NOTIFICATION Failure to Monitor and

[ Apparent Difference from daily Maximum Limitation February 12, 1986 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Mixing Basin Discharge (001) Outfall Code No: 800095 Neutralizer Tank Wastes (00E) 800213 Parameter: pH, TSS, Flow Vol Parameter Code No: 00400 00530, 50050

1. Date of Incident: February 7, 1986 1415-1500 hours
2. Identification of specific effluent limitation or monitoring requirement affected:

pH daily maximum limitation of 9.0 for mixing basin discharge.

Failure to monitor TSS and flow volume for neutralizer tank discharge.

3. Description of Incident:

On 2/7/86 a make-up water demineralizer was regenerated. The regeneration wastewater was routed to the neutralizer tank. Through an apparent over-sight, the neutralizer drain valve had not been closed following a previous release. The regeneration wastes, therefore, passed immediately through the neutralizer tank without sampling to the mixing basin and on to Lake Michi-gan. The mixing basin pH was elevated to 9.4 for 45 minutes.

4. Apparent Cause:

The neutralizer tank drain valve NV-DP1096 was left open following a previ-ous neutralizer tank release.

5. If not immediately corrected, the anticipated time the condition is expected to continue:

NA

6. Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The drain valve was closed at 1800 hours0.0208 days <br />0.5 hours <br />0.00298 weeks <br />6.849e-4 months <br /> on 2/7/86. The procedures for treating and releasing demineralizer regenerants will be reevaluated.

7. Additional Comments:

NA

8. Signed: [

Ralph F Green RP0286-21RLF-EN03 1