ML20126M750

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 850110 & 14,routine Weekly Oil & Grease Samples Measured 72.2 Mg/L & 56.1 Mg/L, Respectively,Exceeding Limit.Caused by Removal of New API Oil/Water Separator from Svc for Maint.Returned to Svc
ML20126M750
Person / Time
Site: Palisades 
Issue date: 01/21/1985
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Morley F
MICHIGAN, STATE OF
Shared Package
ML20126M704 List:
References
PAL-85-01-AD104, PAL-85-1-AD104, NUDOCS 8506200453
Download: ML20126M750 (2)


Text

.

4= u..

c,.

Y CORSum8f5 Power

..g.-

Company seneeni omese: 212 went uienigen Avenue, Jackson. u'chigen 4esot. Area coas st7 7ss-osso

(..

i_

January 21, 1985 Mr Fred Morley District Supervisor Plainwell District Office Bldg 621 North 10th Street PO Box 355 Plainwell, MI 49080 FILE NO: P10.2.1 INCIDENT NO: DAL-85-01-AD104 This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Plant. In accordance with Part II, A4, the attached " NPDES Notification,"

Incident No PAL-85-01-AD104, is submitted as a report of an apparent differ-ence from the daily maximum effluent limitations for this facility.

If you have any questions regarding the attached report, please contact this office.

R L Fobes Senior Environmental Advisor CC USEPA, Enforcement Division, Region V BCC RBDeWitt, P-26-117B KFBieszke, P-24-329 BDJohnson, P-24-606 BWMarguglio, JSC-220A JFFirlit, Palisades JRSchepers, Palisades SFPierce, Palisades ATUdrys, M-1023 OC0185-0235A-TP13 8506200453 850531 PDR ADOCK 05000255 R

PDR

Filo No P10.2.1 Incident No: PAL-85-01-AD104 4

6 NPDES NOTIFICATION Apparent Difference Fre: Daily Average / Maximum Limitation January 21, 1985 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Turbine Surp 011 Separator Outfall Code No: 800216 Discharge (00G)

Paraneter: Oil and Grease (Freon)

Parameter Code No: 00556 1.

Dates of Incident:

1/10/85 and 1/14/85 2.

Identification of specific effluent limitation or monitoring requirenent affected:

Oil and grease daily maxi =um limitation of 20 zg/L.

3.

Description of Incident:

Routine weekly grab sa:ples for oil and grease collected on 1/10/85 and 1/14/85 measured 72.2 eg/L and 56.1 mg/L. respectively.

4 Apparent Cause:

The new API oil / vater separator was re=oved from service for maintenance purposes. Tank T-41 oil separator re=ained in service during this period.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The folleving corrective action was taken or vill be taken to reduce, eliminate and prevent recurrence:

The API oil / vater separator was placed back in service on 1/16/85.

7.

Additional Comments:

The final discharge to Lake Michigan showed no visible signs of oil.

8.

Signed:

RLFobes7qy(jCI 4

MIO185-0235A-TP13

.