ML13310B619

From kanterella
Jump to navigation Jump to search

Informs That Licensee 840709 Proposal to Resolve TMI Item II.F.1.4 Acceptable.Computer Software Will Be Modified So That Data Will Be Collected Once Per Second & Highest Value Over Each Minute Will Be Recorded
ML13310B619
Person / Time
Site: San Onofre 
Issue date: 08/03/1984
From: Paulson W
Office of Nuclear Reactor Regulation
To: Baskin K
SOUTHERN CALIFORNIA EDISON CO.
References
TASK-2.F.1, TASK-TM LSO5-84-08-003, LSO5-84-8-3, TAC-44128, NUDOCS 8408070331
Download: ML13310B619 (2)


Text

August 3, 1984 Docket No. 50-206 LS05-84-08-003 Mr. Kenneth P. Baskin, Vice.President Nuclear Engineering Licensing and Safety Department Southern California Edison Company 2244 Walnut Grove Avenue Post Office Box 800 Rosemead, California 91770

Dear Mr. Baskin:

SUBJECT:

CONTAINMENT PRESSURE MONITORING SYSTEM (TMI ITEM II.F.1.4)

Re:

San Onofre Nuclear Generating Station Unit No. 1 By letter dated April 16, 1984 the staff issued its safety evaluation report on TMI Item II.F.1.4 which concluded that your proposed recording capability for containment pressure of one data point per minute was unacceptable. By letter dated July 9, 1984 you committed to modify the software for the computer such that data will be collected once per second and the highest value over each minute will be recorded. This modification resolves our concern and we therefore conclude that Item II.F.1.4 is satisfactorily resolved for San Onofre.

Sincerely, Original signed by Walter A. Paulson, Acting Chief Operating Reactors Branch #5 Division of Licensing cc: See next page DL:7 5

DL B#5 EMcKenna:jb Pson

-1/3 /84 p/ /84 PDR8ADC 840803 PDR ADOCK'05000206 P.PDR

.9

Mr. Kenneth August 3, 1984 cc Charles R. Kocher, Assistant General Counsel James Beoletto, Esquire Southern California Edison Company Post Office Box 800 Rosemead, California 91770 David R. Pigott Orrick, Herrington & Sutcliffe 600 Montogmery Street San Francisco, California 94111 Dr. Lou Bernath San Diego Gas & Electric Company P. 0. Box 1831 San Diego, California. 92112 Resident Inspector/San Onofre NPS c/o U.S. NRC P. 0. Box 4329 San Clemente, California 92672 Mayor City of San Clemente San Clemente, California 92672 Chairman Board of Supervisors County of San Diego San Diego, California 92101 Director Energy Facilities Siting Division Energy Resources Conservation &

Development Commission 1516 -

9th Street Sacramento, CA 95814' U.S. Environmental Protection Agency Region IX Office ATTN:

Regional Radiation Representative 215 Freemont Street San Francisco, California 94105 John B. Martin, Regional Administrator Nuclear Regulatory Commission, Region V 1450 Maria Lane Walnut Creek, California 94596