05000311/LER-1982-046, Forwards LER 82-046/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 82-046/03L-0.Detailed Event Analysis Encl
ML20054H019
Person / Time
Site: Salem PSEG icon.png
Issue date: 06/09/1982
From: Midura H
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20054H020 List:
References
NUDOCS 8206220501
Download: ML20054H019 (3)


LER-2082-046, Forwards LER 82-046/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3112082046R00 - NRC Website

text

~ ~t

~0 PSEG Public Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station June 9, 1982 i

n Mr. R. C. Haynes Regional Administrator USNRC Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Haynes:

LICENSE NO. DPR-75 DOCKET NO. 50-311 REPORTABLE OCCURRENCE 82-046/03L Pursuant to the requirements of Salem Generating Station Unit No. 2, Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 82-046/03L. This report is required within thirty (30) days of the occurrence.

Sincerely yours, l jj', %hb& '

H. J. Midura General Manager - ,,

Salem Operations 3 RF:ks(f/) ,

CC: Distribution i

l l

l C206220501 820609 PDR ADOCK 05000311 IgtD S PDR The Energy People wo es . in

Report Number: 82-046/03L Report Date: 06-09-82 Occurrence Date: 05-27-82 Facility: Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

No. 23 Containment Fan Coil Unit - Inoperable.

This report was initiated by Incident Reports82-134 and 82-136.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 100% - Unit Load 1150 MWe.

DESCRIPTION OF OCCURRENCE:

On May 27, 1982, during routine surveillance, the Control Room Operator discovered that the service water flow to No. 23 Containment Fan Coil Unit (CFCU) was less than required by the Technical Specifications. No. 21 CFCU had been inoperable since 1450 hours0.0168 days <br />0.403 hours <br />0.0024 weeks <br />5.51725e-4 months <br />,-May 26, 1982, with a motor cooler service water leak (see LER 82-039/0lT) . Consequently, when No. 23 CFCU was declared inoperable at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br />, May 27, 1982, Action Statement 3. 6. 2. 3.b was entered.

This' occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.J.9.b.

, DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

The low service water flow to No. 23 CFCU resulted from American oysters plugging the 23SW57 valve tube bundle.

ANALYSIS OF OCCURRENCE:

Technical Specification 3.6.2.3.b requires:

With two groups. of containment fan coils inoperable and bothicontainment spray systems operable, restore at least one group of cooling fans to operable status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, or be in at least hot standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

1

,,' LER 82-04 6/03L

; .r s

CORRECTIVE ACTION:

The oysters were removed, service water flow was restored to I normal, and the CFCU was satisfactorily tested. At 0345 hours0.00399 days <br />0.0958 hours <br />5.704365e-4 weeks <br />1.312725e-4 months <br />,

! May 29, 1982, No. 23 CFCU was declared operable, and Action i Statement 3.6.2'.3.b was terminated.

An investiga~ tion is being conducted into the problem of oysters in the Service Water System. A commitment to submit a Supplemental Report was made in similar LER 82-041/03L.

l FAILURE DATA:

j Not Applicable I

i i

! Prepared by R. Frahm /./ 3 b M Q Gen (ral Manager -