O PSsG Public Service Electric and Gas Company P.O. Box E Hancocks Br;dge, h,ew Jersey 08038 i

Salem Generating Station May 19, 1982 1

J Mr.

R. C.

!!aynes Regional Administrator a

USNRC Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Ilaynes:

LICENSE NO. DPR-75 DOCKET NO. 50-311 REPORTABLE OCCURRENCE 82-029/03L Pursuant to the requirements of Salem Generating Station Unit No.

2, Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 82-029/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, y f.k4 H. J. Midura General Manager -

Salem Operations RF:ks CC:

Distribution i

i l

l 8206100139 820519 6gtt' l

PDR ADOCK 05300311 S

PDR 95 2 W) (20Y) 1181 L

Report Number:

82-029/03L Report Date:

05-19-82 Occurrence Date:

04-23-82 Facility:

Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Containment Sump Monitoring System - Inoperable.

This report was initiated by Incident Report 82-096.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 100% - Unit Load 1120 MWe DESCRIPTION OF OCCURRENCE:

At 0100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />, April 23, 1982, during routino operation, the Control Room Operator reported that the containment sump pumps had both been running continuously since 2214 hours0.0256 days <br />0.615 hours <br />0.00366 weeks <br />8.42427e-4 months <br /> the previous day.

A containment entry was made; however, no increased leakage was evident.

The containment sump monitoring system was declared inoperable, retroactive to 2214 hours0.0256 days <br />0.615 hours <br />0.00366 weeks <br />8.42427e-4 months <br />, April 22, 1982, and Action Statement 3.4.7.1 was entered.

This occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

The cycling of Breaker No. 3 in Cabinet 26RC7, while searching for grounds on the 28 VDC bus, had closed Sump Pump Discharge Valve 2WLl6, restricting the pumps discharge.

ANALYSIS OF OCCURRENCE:

l Technical Specification 3.4.7.1 requires:

With only two of the required leakage detection systems operable, operation may continue for up to 30 days, provided grab samples of the containment atmosphere are obtained and analyzed at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the gaseous and/or particulate radioactivity monitoring system is inoperable; otherwise, be in at least hot standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

L

LER 82-029/03L..

CORRECTIVE ACTION

During an investigation of the problem, it was noticed that Discharge Valve 2WL16 was closed.

The valve was reopened, and the sump pumps were observed to cycle properly with a satisfactory leak rate indicated.

Analysis of the valve control circuit showed that the valve will stay in the closed position following cycling of Breaker No. 3 in Cabinet 26RC7.

At 0643 hours0.00744 days <br />0.179 hours <br />0.00106 weeks <br />2.446615e-4 months <br />, April 23, 1982, the containment sump monitoring system was declared operable, and Action Statement 3.4.7.1 was terminated.

FAILURE DATA:

Not Applicable Prepared By R.

Frahm f/ Q.Iv/d G6n'erhl Manager -

Salem Operations SORC Meeting No.

82-51