05000272/LER-1982-037, Forwards LER 82-037/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 82-037/03L-0.Detailed Event Analysis Encl
ML20054G891
Person / Time
Site: Salem 
Issue date: 06/09/1982
From: Midura H
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20054G892 List:
References
NUDOCS 8206220387
Download: ML20054G891 (3)


LER-1982-037, Forwards LER 82-037/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
2721982037R00 - NRC Website

text

,

t O PSIsG

~

~

Public Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station June 9, 1982 i

Mr.

R.

C. Haynes Regional Administrator USNRC Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Haynes:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 82-037/03L Pursuant to the requirements of Salem Generating Station Unit No. 1, Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 82-037/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, lbf Y H. J. Midura General Manager -

Salem Operations RF:ksjlJf-CC:

Distribution 8206220387 820609 PDR ADOCK 03000272 S

PDR The Energy People Np

, "m,. 3 n m

Report Number:

82-037/03L 06-09-82 l

Report Date:

Occurrence Date:

05-26-82 Facility:

Salem Generating Station, Unit 1 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCUPRENCE:

No. 12 Containment Fan Coil Unit - Inoperable.

This report was initiated by Incident Report 82-132.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 100% - Unit Load 1150 MWe.

DESCRIPTION OF OCCURRENCE:

On May 26, 1982, during routine surveillance, the Control Room Operator discovered service water flow to No. 12 Containment Fan Coil Unit (CFCU) was less than required by the Technical Specifications.

The unit was declared inoperable at 0935 hours0.0108 days <br />0.26 hours <br />0.00155 weeks <br />3.557675e-4 months <br />, and Action Statement 3.6.3.3.a was entered.

This occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Flow Control Valve 12SW223 had stuck in the closed position, resulting in low service water flow to the CFCU.

ANALYSIS OF OCCURRENCE:

Technical Specification 3.6.2.3.a requires:

With one group of containment cooling fans inoperable and both containment spray systems operable, restore the inoperable group of cooling fans to operable status within 7 days, or be in at least hot standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shudown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

)

LER 82-037/03L.

CORRECTIVE ACTION

An investigation revealed that the valve tube bundle was extensively damaged by erosion and corrosion.

A spare bundle was not available, and a spacer was installed in place of the damaged part.

.The valve was exercised, and the CFCU satisfactorily tested.

No. 12 CFCU was declared operable at 0020 hours2.314815e-4 days <br />0.00556 hours <br />3.306878e-5 weeks <br />7.61e-6 months <br />, May 28, 1982, and Action Statement 3.6.2.3.a was terminated.

The failure of service water SW223 valves is presently being investigated.

A commitment was made in LER 82-029/03L to submit a Supplemental Report upon completion.

FAILURE DATA:

Fisher Controls Co.

8 inch Vee-ball Valve Type 657-80 f

Prepared By R.

Frahm General Manager -

Salem Operations SORC Meeting No.

82-58 l

l