BSEP-76-1143, Ro:On 760922,engineering Analysis Delineated Potential Problem W/Primary Containment Instruments 2-CAC-AT-1259 & 2-CAC-AT-1263.Dehumidifiers May Trip in Event of Loca.Caused by Excessive Heat.Short Sensing Lines Isolated

From kanterella
Revision as of 23:37, 25 September 2022 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Ro:On 760922,engineering Analysis Delineated Potential Problem W/Primary Containment Instruments 2-CAC-AT-1259 & 2-CAC-AT-1263.Dehumidifiers May Trip in Event of Loca.Caused by Excessive Heat.Short Sensing Lines Isolated
ML20084S926
Person / Time
Site: Robinson Duke Energy icon.png
Issue date: 09/23/1976
From: Furr B
CAROLINA POWER & LIGHT CO.
To: Moseley N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
BSEP-76-1143, NUDOCS 8306200092
Download: ML20084S926 (1)


Text

. . . _ .. , .. . ,.. - , - ,

y.

c -

O i

O I Brunswick Steam Electric Plant P.O. Box 458

[ Southport, NC 28461 September 23, 1976 E FILE: B3516 SERIAL: BSEP/76-1143 E-g Mr. Norman C. Moseley, Director U.S. Nuclear Regulatory Commission Region II, Suite 818 g 230 Peachtree Street, N.W.

Atlanta, Georgia 30303

Dear Mr. Moseley:

On September 22, 1976, we received an engineering analysis from our engineering department in Raleigh which delineated a potential problem with our Primary Containment 02 /H2 instruments (2-CAC-AT-1259 L 2-CAC-AT-1263) . The analysis pointed out that in the event of a LOCA the dehumidifiers at the instruments may trip out because of excessive heat of approximately 170*F from certain short length sensing lines from the containment structure. A dehumidifier tripout renders the instrument inoperabic. The short sensing lines have been isolated and tagged out. (3 lines for 2-CAC-AT-1259 & 2 lines for 2-CAC-AT-1263),

j This constitutes a reportable occurrence as defined in Technical Specification 6.11.2.a(9) and was reported to Mr. H. A. Wilber of your office on September 22, 1976.

?

, Very truly yours, A

r C/ ,,b W B.J. Furr, Manager Brunswick S.E. Plant

. RSS/dla cc: H.R. Banks i

K 4

e i $D ' g C- k 8306200092 760923 s- PDR ADOCK 05000261 S

PDR

[ _,_ '- .

I7 .

~ '. . ' . .

- .. ,' + -

. . .. .. _ w-- x - -