'q) 5 Carolinit Power & Light Company Raleigh, Nor h Carei na 27602 i
SepterOcr 11, 1972
\\
\\
-.\\
)
a'
~,
tl, -
if sN/.
Mr. John F. O' Leary, Director g.'._f. /
Directorate of Licensing
' ' ' # 'y. /
U. S. ALonic Energy Coulssion
~
Washington, D. C.
50545 H. B. ROBINSON PI M T LICENSE DPR-23 MALFUNCTION OF PART IT.NGT:I ROD CONTROI, SYSTDI Cear Mr. O'Lcary:
At 5:58 P.M. on July 26, 1972, an alarm was received on the Part Length Rod Control Systen. A frequency act or relay which conitors the 60 cycle current to the logic cabinet van found inoperable. This relay was replaced and the Part Length Rod Centrol Syrtem returned to narcal at 8:52 P.M. July 26, 1972.
Reactor pouer was 99.9% at this tire cud vns not changed during the period that the Part Length Rods were inoperable.
The Part Length I:ods were not in use during this period.
This is reported in accordance with Section 6.().3, Technical Specifications.
Yours very truly,
~.-
y
(-=*
,l [,/l -