CP&L CO PLANT PERFORMANCE' DATA SYSTEM-
'PAGE i.
RUN DATE- 04/14/87-OPERATING DATA REPORT RPD36-000-
' RUN TIME ~i4:20:19 ROBINSON UNIT 2 Enclosure to Serial: RNPD/87-1640 Page 1 of 4.
DOCKET N0'. 050-O'261 COMPLETED BY V.
E.
FRAZIER OPERATING STATUS TELEPHONE (803)383-4524 1.~ UNIT NAME: ROBINSON UNIT 2 l NOTES I
2.
REPORTING PERIOD:. MARCH 87 i There are presently 318 Fuel I
3.
LICENSED THERMAL POWER (MWT); 2300 l Assemblies in the Spent Fuel
.I 4.
NAMEPLATE RATING (GROSS MWE): 739.0 l Pool.
1 5.
DESIGN ELECTRICAL RATING (NET MWE): 700.0 l
l 6.
MAX DEPENDABLE CAPACITY (GROSS MWE): 700.0 l l
- 7. MAX-DEPENDABLE CAPACITY (NET MWE): 665.0 8.
IF CHANGES OCCUR IN CAPACITY ~ RATINGS (ITEMS 3 THRU 7) SINCE.LAST REPORT, GIVE REASONS: N/A 9.
POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE); None
- 10. REASONS FOR RESTRICTION IF ANY: - N/A.
THIS YR TO CUMUL MONTH
'DATE ATIVE
- 11. HOURS IN REPORTING PERIOD 744.00 2160.00 141000.00
- 12. NUMBER OF HOURS REACTOR CRITICAL 559.43 1975.43 101151.35
- 13. REACTOR RESERVE SHUTDOWN HRS
.00
.00 3314.65
- 14. HOURS GENERATOR ON LINE 557.00 1973.00 98771.20
- 15. UNIT RESERVE SHUTDOWN HOURS
.00
.00 23.20
- 16. GROSS THERMAL ENERGY GEN. (MWH) 1030092.72 4233072.72-198915087.84
- 17. GROSS ELEC. ENERGY GEN. (MWH) 349450.00 1429782.00 64344260.00
- 18. NET ELEC. ENERGY GENERATED (MWH) 327257.~00 1357843.00 60754580.00
- 19. UNIT SERVICE FACTOR 74.87 91.34 70.05
- 20. UNIT AVAILABILITY FACTOR 74.87 91.34' 70.07
- 22. UNIT CAP. FACTOR (USING DER NET) 62.84 89.80 61.55
- 23. UNIT FORCED OUTAGE RATE 14.38 4.53-14.05
- 24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):
None 1
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
Fby 23,1987
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORECAST ACHIEVED INITIAL CRITICALITY 13 2---
- f 2 1-INITIAL ELECTRICITY COMMERCIAL OPERATION
~~~
~~~
~---~~--
8705050313 870429
.16 - 9 PDR ADOCK 05000261 R
~
CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE i
RUN DATE 04/01/87 APPENDIX D - AVERAGE DAILY POWER LEVEL RPD39-OOO
' RUN TIME 14:06:06 ROBINSON UNIT 2 P;ge 2 of'4 DOCKET NO. 050-0261 COMPLETED BY V.
E. FRAZIER TELEPHONE (803)383-4524 MARCH 1987 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET)
(MUE-NET) 1 688 17
.-10 2
677 18
-25 3
479 19
-24 4
679 20
-22 5
679 21 223 6
678 22 385 7
678 23 550 8
630 24 592 9
619 25 595 10 619 26 595 11
^20 27 552 12 620 28
-7 13 621 29
-16 14 620 30
-15 15 620 31
-10 16 546 1.16 - 8
Page 3 of 4 DOCKET NO. 050-0261 UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME H.
B.
Rnhinenn DATE 4-14-87 COMPIETED 3Y Valerie E.
Frazier REPORT MONTH
%rch TELEPHONE 803-383-4524
.! E 3
hE Cause & Correceive Licensee Eg Action to No.
Date
{
3g
(
jgy Event g?
g3 H
fE j ;f, g Report a mV V
Prevent Recurrence g
6 0301 870317 F
93.34 A
1 87-001 EE ENGINE While performing weekly Surveillance Test (OST-401), "B" Emergency Generator 1
tripped on a high crankcase pressure.
This cause was contributed to water leakage into Lube Oil System.
"B" Emergency Generator declared inoperable and was under a.7-day LCO limit that caused the Reactor shutdown. " B" Emergency Generator was repaired and returned to service.
3 4
I 2
Method:
Exhibit C. Instruct 6uns F: Forced Reason:
1-Manual for Preparation of Data S. Scheduled A Equipment Failure (Explain)
B-Maintenance or Test 2-Manual Scram.
Entry Sheets for Laznese 3 Automatic Scram.
Event Report (LER) File (NUREG.
C-Refueling D Regula ory Restriction 4Other (Explain) 0161)
E4perator Training & Ucense Examination 5
F Admimstrative Exhibit 1 Same Simtse G Operational Eirur (Emplain)
~
(9/77) llother (Emplain)
Page 4 of 4 050-0261 DOCKET NO.
UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME H.
B.
Robinson
"-14-D#
DATE Valerie E. Frazier March COMPLETED BY REPORT MONTH TELEPHONE 803-383-4524
~E E
a Cause & Corrective
{*3 Action to
.] ?
3 y E3 Licensee E*
No.
thie h
?
s 255 Event 17 g
Prevent Recurrence g'
$5 5
j ;f, g Report a mO 6
0302 870327 S
7.34 C
4 ZZ ZZZZZZ Unit ramped down manually to 6 power off-line for Cycle #12 Refueling.
ZZZZ 870328 S
93.42 C
1 ZZ ZZZZZZ Cycle #12 Refueling commenced, and unit was taken suberitical. This outage will continue into April.
I 2
3 4
Method:
Exhibit G. Instructiuns F: Forced Reason:
S: Scheduled A Equipment Failure (Explain) 1-Manual for Preparation of Deta B-Maintenance or Test 2-Manual Scram.
Entry Sheets for bcensee 3 Automatic Scram.
Event Repori (LER) File (NUREG-C. Refueling D Regulatory Restriction 44ther(Explain) 0161)
EOperator Training & License Examination 5
F. Administrative Exhibit I Same Soun:e G-Operational Eirur (Explain)
~
19/77) llother (Emplaini G
.