i
. i. ' '
Cp&L Carolina Power & Light ggany H.B.ROBINSONSTEAMELECTRIC' PLANS 8,*
Post Office Box 790 Hartsville, South Carolina 29550 NOV2 31993 Robinson File No: 13510C Serial:RSEP/83-1401 Mr. James P. O'Reilly Regional Administrator U. S. Nuclear Ragulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 H. B. ROBINSON STEAM ELECTRIC PLANT Docket No.
50-261 License No. DPR-23 PROMPT NOTIFICATION - STEAM GENERATOR INSPECTION RESULTS
Dear Mr. O'Reilly:
The H. B. Robison Plant was shut down for a Steam Generator tube inspection at 0452 hours0.00523 days <br />0.126 hours <br />7.473545e-4 weeks <br />1.71986e-4 months <br />, on November 3,1983. The Steam Generator inspection results, to date, f all into Category C-3 of Technical Specification 4.2.5.1.2 (b) and are reported as a Prompt Notification pursuant to Technical Specification 6.9.2.a.
The results of the Steam Generator tube inspection to date are as follows:
"A" Steam Generator Tubes to be plugged this outage -
-116 Total % of tubes plugged af ter this outage 15.03 "B" Steam Generator Tubes to be plugged this outage-215 Total % of tubes plugged af ter this outage -
28.84 "C"
Steam Generator Tubes to be plugged this outage =
242 Total % of tubes plugged af ter this outage--
23.96 l
hCK05000261 238 831123 S
__.c f '
Y E
s
'/0
Y"
,,,2 Letter to Mr. James P. O'Reilly Serial:RSEP/83-1401
'Page 2 Because this outage is in progress, the above numbers may. change slightly. The fourteen (14) day LER will provide the final figures.
This information was reported on November 23, 1983, to NRC Region II and to Mr. Guy Beatty, Manager, Robinson Nuclear Project Department.
If you have any questions concerning this information, please contact my st.If o r me.
W f
/
[ General Manager R. E. Morgan H. B. Robinson S. E. Plant CLW:FMG:pb cc.
S. P. Weise