PHILADELPHIA ELECTRIC COMPANY l | |||
$l 6- Q | |||
//b[f[/ S gN. | |||
-h I( ,y 2301 MARKET STREET gg Qf* g PHILADELPHI A. PA.19101 b N'hh hQ'g7. | |||
121si 8414ooo October 13, 1974 | |||
' 8 Mr. A. Giambusso | |||
- Deputy Director of Reactor Porjects United States Atomic Energy Commission , | |||
Directorate of Licensing Washington, D.C. 20545 g | |||
==Dear Mr. Giambusso:== | |||
==Subject:== | |||
Abnormal Occurrence The.follywing occurrence was reported to Mr. Walt Baunack, 7 A.E.C. Region.1 Regulatory Operations Office on October 4, 1974. L Written notification was made to Mr. James P. O'Reilly, Region 1 Regulatory Operations Office on October 4, 1974. In accordance with Section 6.7.2.A of the Technical Specification, Appendix A'of DTR-44 for - Unit 2 Peach Bot tom Atomic Power Station, the following report is being submitted to the Directorate of Licensing as an Abnormal l > Occurrence: , ;w | |||
.W | |||
" ~ | |||
/ | |||
="}- ' | |||
==Reference:== | |||
License. Number'DPR-44, Amendment Number 1 g'F Technical, Specification Reference Table 3.1.1 | |||
+1 5 | |||
Report No.: 50-277-74-43 | |||
. Report Date: October 13,.1974 | |||
* I[ Occurrence Date: October 3,.1974 4 .' Facility: Peach Pottom Atomic Power StatioT | |||
'^ | |||
m( R.D. 1, Delta, Pennsylvania .1731]4 | |||
( ,} , | |||
l 3 Identification _of Occurrence: o l.4 Setpoint of condenser low vacuum scram pressure switch found | |||
[/g to,.be outside the limits allowed by the Technical Specifications. | |||
a Conditions Prior to Occurrence: | |||
n l -- | |||
The reactor was operating at 86% power. | |||
w gDRADOCK401270037 743013'' | |||
g 05000277 PDR 1 | |||
d80'f,' 4 ) | |||
~ | |||
107G5 con suraanos | |||
'Mr. A. Giambusso. Page 2 ~] | |||
October 13, 1974 i O O . | |||
t Description of Occurrence: . | |||
j i | |||
During a routine instrument surveillance test, the setpoint i of the condenser low vacuum scram switch, PS-2-5-llA, was found to !. | |||
' be outside the limit of greater than or equal to 23 in. IIg. The' device t performed satisfactorily. l | |||
. l' Designation of Apparent Cause of Occurrence: , | |||
This occurrence is due to setpo' int drift of the pressure [ | |||
t | |||
-switch. | |||
I. | |||
i. | |||
Analysis'of Occurrence: t | |||
- The contacts of this device are arranged in a one-out-of-two' t twice trip logic. The setpoint of.this device, not the trip function, , | |||
was unsatisfactory. All other devices monitoring the parameters of , | |||
condenser vacuum were immediately tested and found to be operational ! | |||
and correctly calibrated. Because of the above reasons this occurrence has minimal safety implications. j Corrective' Action: | |||
Li The out-of-tolerance' pressure switch was immediately re-calibrated to within the allowable limits of the technical specifications. | |||
The other three devices monitoring the same variable were tested . | |||
.and found to be satisfactory in both function ano setpoint. | |||
pm | |||
* Failure Data: * | |||
^Two occurrences of this type have been previously reported i as AO-50-277-74-1 and AO-50-277-74-19. After the latter, the device | |||
.was r'eplaced in kind. A calibration shift was again reported in , | |||
AO-50-277-74-35. , | |||
- Very truly yours, < | |||
) | |||
b. | |||
f . | |||
( oney | |||
/ | |||
i, 4 | |||
- As,'t Gen'l 'perintendent Generation Division P. O'Reilly | |||
-cc: Mr, _ J. | |||
Director _ Region 1 ; | |||
United States ' Atomic Energy Commission 631 Park Avenue , | |||
King of Prussia, PA 19406 . | |||
* I 2 | |||
x | |||
/ | |||
0 e y r r - + - eev9, ,, g ,-9 y,e--- a yev rev<*---y- w-w, - | |||
6 i-ws-e w w - e wer -,----tt- -*t-PW- e r-s--<ei= "}} |
Latest revision as of 06:03, 16 April 2020
ML20086K349 | |
Person / Time | |
---|---|
Site: | Peach Bottom ![]() |
Issue date: | 10/13/1974 |
From: | Cooney M PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC |
To: | Giambusso A US ATOMIC ENERGY COMMISSION (AEC) |
References | |
AO-74-43, NUDOCS 8401270037 | |
Download: ML20086K349 (2) | |
Text
r o
.? -
o n
, w ..
N'\
1 x
PHILADELPHIA ELECTRIC COMPANY l
$l 6- Q
//b[f[/ S gN.
-h I( ,y 2301 MARKET STREET gg Qf* g PHILADELPHI A. PA.19101 b N'hh hQ'g7.
121si 8414ooo October 13, 1974
' 8 Mr. A. Giambusso
- Deputy Director of Reactor Porjects United States Atomic Energy Commission ,
Directorate of Licensing Washington, D.C. 20545 g
Dear Mr. Giambusso:
Subject:
Abnormal Occurrence The.follywing occurrence was reported to Mr. Walt Baunack, 7 A.E.C. Region.1 Regulatory Operations Office on October 4, 1974. L Written notification was made to Mr. James P. O'Reilly, Region 1 Regulatory Operations Office on October 4, 1974. In accordance with Section 6.7.2.A of the Technical Specification, Appendix A'of DTR-44 for - Unit 2 Peach Bot tom Atomic Power Station, the following report is being submitted to the Directorate of Licensing as an Abnormal l > Occurrence: , ;w
.W
" ~
/
="}- '
Reference:
License. Number'DPR-44, Amendment Number 1 g'F Technical, Specification Reference Table 3.1.1
+1 5
Report No.: 50-277-74-43
. Report Date: October 13,.1974
- I[ Occurrence Date: October 3,.1974 4 .' Facility: Peach Pottom Atomic Power StatioT
'^
m( R.D. 1, Delta, Pennsylvania .1731]4
( ,} ,
l 3 Identification _of Occurrence: o l.4 Setpoint of condenser low vacuum scram pressure switch found
[/g to,.be outside the limits allowed by the Technical Specifications.
a Conditions Prior to Occurrence:
n l --
The reactor was operating at 86% power.
w gDRADOCK401270037 743013
g 05000277 PDR 1
d80'f,' 4 )
~
107G5 con suraanos
'Mr. A. Giambusso. Page 2 ~]
October 13, 1974 i O O .
t Description of Occurrence: .
j i
During a routine instrument surveillance test, the setpoint i of the condenser low vacuum scram switch, PS-2-5-llA, was found to !.
' be outside the limit of greater than or equal to 23 in. IIg. The' device t performed satisfactorily. l
. l' Designation of Apparent Cause of Occurrence: ,
This occurrence is due to setpo' int drift of the pressure [
t
-switch.
I.
i.
Analysis'of Occurrence: t
- The contacts of this device are arranged in a one-out-of-two' t twice trip logic. The setpoint of.this device, not the trip function, ,
was unsatisfactory. All other devices monitoring the parameters of ,
condenser vacuum were immediately tested and found to be operational !
and correctly calibrated. Because of the above reasons this occurrence has minimal safety implications. j Corrective' Action:
Li The out-of-tolerance' pressure switch was immediately re-calibrated to within the allowable limits of the technical specifications.
The other three devices monitoring the same variable were tested .
.and found to be satisfactory in both function ano setpoint.
pm
- Failure Data: *
^Two occurrences of this type have been previously reported i as AO-50-277-74-1 and AO-50-277-74-19. After the latter, the device
.was r'eplaced in kind. A calibration shift was again reported in ,
AO-50-277-74-35. ,
- Very truly yours, <
)
b.
f .
( oney
/
i, 4
- As,'t Gen'l 'perintendent Generation Division P. O'Reilly
-cc: Mr, _ J.
Director _ Region 1 ;
United States ' Atomic Energy Commission 631 Park Avenue ,
King of Prussia, PA 19406 .
- I 2
x
/
0 e y r r - + - eev9, ,, g ,-9 y,e--- a yev rev<*---y- w-w, -
6 i-ws-e w w - e wer -,----tt- -*t-PW- e r-s--<ei= "