e PHILADELPl!IA ELECTRIC COMPAllY.
Peuch Bottom Atomic Power Station l
Delta, Pennsylvania 731%
october 31, 1975 Mr. James P.
O ' R e i 21.v. D* vector office of Inspection and Enforcement b
j Recion 1 i
United States Nuclear Regulatory Commission hg\\
M 631 Park Avenue i
King of Prussia, Pennsylvania 1,9406 ~
,l S u b.} e c't :
Abnormal Occurrence 2h-Hour Not i fi c at i on Confirming R.
S.
Fleischmann's. verbal conversation with Mr. Walt Baunack, Region 1. United States Nuclear Heculatory Commission on October 30, 1975 Hoference:
License numbcr DPR-56 Technical Spe ci fi cation heference:
3 7.D.1 Report No.-
50-278-75-71 b
Report Date:
October 31, 1975 Occurrence Date:
October 30, 1975 Facility:
Peach Bottom Atomic Power Station R.D.
1, Delta, Pennsylvania-17314 Identification of occurrence:
f Isolation Valve SV 3978B failure.
Conditions Prior to Occurrence:
Unit 3 at 56% power.
l Description of Occurrence:
During routine surveillance test, 0 Analyzer Is lation Valve SV 3978D 2
failed to close.
Designatidn of Apparent Cause of Occurrenec:
Under investiCation.
I Analysis of Occurrenec:
i The safety implications of this occurrence are minimal because the i
j inner isolation vclve SV-3671B closed and scated properly when tested.
In addition, the uistream manual isolation valve has been closed to preclude any leakage.
Corrective Action:
To be determined.
m l
Failure Data:
Similar failures v'ere reported in the pant as Abnormal Occurrence Report Humbers 50-278-75-27, 50-278-75-26, 50-278-75-11 and also on 11/9/75 t'
I Very truly yours,
\\
N$
U.
T.
Ullrich, Superintendent Peach Botton Atomic Power Station s
i i
t 1
?
i l
l l
8401130377 751107 PDR ADOCK 05000278
?'
S PDR h