ML20086F944

From kanterella
Jump to navigation Jump to search
Telecopy AO 75-68:on 751021,leak Found on O-ring Gasket on Torus Purge Supply Valve AO 2521A.Cause Under Investigation. Corrective Action to Be Determined After Investigation
ML20086F944
Person / Time
Site: Peach Bottom 
Issue date: 10/21/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086F942 List:
References
AO-75-68, NUDOCS 8401090712
Download: ML20086F944 (1)


Text

-

i 1

O

.n

  • ~

)

i

"' t

.---._._.,..-.,.g.-~.---.--

c

.m PHILADELPHIA ELECTRIC COMPANY /

Peach Hottom Atonic Power Station j

Delta. Pennsylvania' October 21, 1975 17314 Mr. James P.

O'Reilly. Director

,;[h-office of Inspection and Enforcement

[gg Region 1 United States Euclear Regulatory Commission 631 Park Avenue Eing of Prussia, Pennsylvania 19k06

Subject:

Abnormal Occurrence 2L-Hour T(oti fi c at ion Confirming R.

S. Fleischmann's phone convercation with Mr. Walt Baunack Region 1. United States Nuclear Regulatory Commission on October 21, 1975

Reference:

License Number DPR kk Technical Specification

Reference:

k.T.A.2.f Report No.:

50-277-75-68 Report Date:

October 21, 1975 Occurrence Date:

October 21, 1975-l.

Facility:

Peach Botton Atomic Power Station R.D.

l ', Delta. Pennsylvania 17314 i

Identification of occurrence:

0-Rin'g gasket leak on Torus Purge Supply Valve AO-2521A.

Conditions Prior to Occurrence:

i Reactor power 56%.

1 Description of Occurrence:

. While preparing for a local leak rate test on the outboard finnge

[

of the torus purge inboard isolation valve. (containment atmosphere

, was found to leak out.

The inboafd 0-ring leaks.

.k Designation of Apparent Cause of Occurrence:

T, ~ ~

1' Under investigation.

y Analysis of Occurrence:

Both the inboard and outboard isolation valves were closed at the time and both were. verified to be leak tight.

Because the isolation valves were leak tight and the outer 0-ring is leak tight, safety l

f significance is minimal.-

3

. Corrective Action:,

To be determined after investigation.

i l '.

l 3

Failure Data:

None.

g

')

Very truly yours.

l

/WF N

W. T. Ullrich. Superintendent Peach Botton Atomic Power Station t.

l (Jvs) l

+

i i'

0401070712 751031 j

PDR ADOCK 05000277

~

S PDR

^

9 e

y 4