ML20086H068

From kanterella
Jump to navigation Jump to search
Telecopy AO 75-70:on 751024,drywell Purge Supply Isolation Valve AO-3520 Operated W/O Manual Initiation.Caused by Incorrect Implementation of Mod.Valve Failed Closed & Will Be Repaired
ML20086H068
Person / Time
Site: Peach Bottom 
Issue date: 10/24/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086H066 List:
References
AO-75-70, NUDOCS 8401130384
Download: ML20086H068 (1)


Text

{{#Wiki_filter:,_ _ _ _ _ ~ ~ y C ~ O' O ~ ,t Il PHILADELPiiIA ELECTRIO COMPANY. -- 1 i ~ panch onetem ten-4n unear n+netnA - --- -~~" - Delta,' Pennsylvania 314 October 24, 1975 I i Mr. James P. O'Reilly, Director g_ Office of Inspection and Enforcement h*?f z ?_hmM{m,J, Dv4cne1. ~ -- 1 . = - United States Nuclear Regulatory Commission 631 Park Avenue. King of Prussia, Pennsylvania 19406 { s -)

Subject:

Abnormal Occurrence 24-Hour Notification a Confirming R. S. Fleischmann's phone conversation with Mr. Walt Baunack, ] Region 1. United States Nuclear Regulatory Commission on October 24, 1975 1

Reference:

License Number DPR-56 ,1 Technical Specification

Reference:

3.7.D.1 Report No.: 50-279-75-{)70 d l Report Date: October 2 , 1975 x 2] Cecurrence Date: October 24, 1975 i Facility: Peach Bottom Atomic Power Station j R.D. 1. Delta, Pennsylvania 17314 ii Identification of Occurrence: 3 Drywell Purge Supply Isolation Valve (AO-3520) opening. E Conditions Prior to Occurrence: Reactor power 57%. i w i Description of Occurrence: I \\ Valve AO-3520 apparently operated without manual initiation. I Designation of Apparent Cause of Occurrence: I4 It appears that an air piping modification made-to similar valves to correct a similar problem in early 1974 was implemented incorrectly on this valve. Analysis' of Occurrence: 1 The other isolation valve in series with this valve would have isolated if necessary. Therefore, there is minimal safety significance. Corrective Action: The valve was, failed closed and will be repaired. All other valves of similar air piping arrangement will be inspected. i Failure Data: ). Abnormal Occurrence Report 50-278-74-15 1 Very truly yours, ) W. T. Ullrich, Superintendent Peach Bottom Atomic Power Station i l i 8401130384 751103 _..m. A' P,DRADOCK05000g8 j /}}